Pedido nº.: 2903154
Contato Fênix TRIO POWER 2nd-generation three-phase DIN rail switching fonte de energia with Push-in spring terminals. Designed for powering PLCs, sensors and actuators inside electrical control cabinets. Widely used in machine manufacturing, linhas de produção automatizadas, HVAC and hoisting equipment.
O código 2901354 often appears in industry documents as shorthand; the complete official part number is 2903154.
✅ Definição de modelo
TRIO: TRIO POWER series industrial power supply
PS: Fonte de energia
2G: 2Segunda Geração
3AC: 3-phase AC input
24CC: 24Saída V CC
10: Rated output current 10A
📌 Key Technical Specifications
Entrada
Avaliado: 3×400~500V AC; capable of emergency operation with 2×400~500V AC two-phase supply
Faixa operacional: 3×320~575V AC
Freqüência: 50/60Hz
Corrente de entrada: 3×0.6A @400VAC
Saída
Avaliado: 24V DC /10A (240C)
Adjustable output: 24~28V CC
Dynamic Boost: 15Um para 5 segundos (para lidar com cargas de partida de motores e capacitores)
Ondulação & barulho: ≤50mVpp
Proteção contra sobretensão OVP: Saída fixada ≤30V DC
Mecânico & Ambiental
Montagem: Trilho DIN 35mm
Dimensões (L × A × P): 42 ×130 ×160mm
Fiação: Terminais de mola push-in sem parafusos
Temperatura operacional: -25℃ ~ +70 ℃; redução de 2,5%/K acima de 60°C
Eficiência: >92%
Operação paralela: Suporta conexão paralela para expansão de capacidade e redundância; conexão em série para aumento de tensão
Proteções: Sobrecorrente, curto-circuito, temperatura excessiva, sobretensão de saída
Sinal: Contato de alarme de relé (Sinal DC OK)
📋 Certificações & Aplicativos
Padrões: EN61010, UL, CE, Tensão extrabaixa protetora PELV
Aplicações típicas: Linhas de produção automatizadas, máquinas de embalagem, sistemas de transporte, 24Fonte de alimentação V para gabinetes de controle que alimentam PLC, Módulos DI/DO, sensores e válvulas solenóides
Alto MTBF, adequado para 24/7 operação industrial contínua
⚠️ Seleção & Notas de substituição
- Distinção de modelo: 2903154 é trifásico 3AC; versão monofásica 1AC é 2903149, não os misture
- Alternativa doméstica: Significa Bem SDR-240-24, Delta DRP-240-24 (observação: sem capacidade de reforço dinâmico para corrente de partida)
- Solução de redundância: Ao colocar em paralelo dois 2903154 unidades, use módulo de redundância como QUINT-DIODE
- Instalação: Mantenha uma folga vertical ≥50 mm na parte superior e inferior para dissipação de calor; as unidades podem ser montadas lado a lado com folga horizontal zero
🛠️ Guia de solução de problemas
LED DE ENERGIA apagado: Verifique a alimentação de rede trifásica L1/L2/L3; a perda de qualquer fase pode impedir a partida; verifique a conexão de aterramento PE
Queda de tensão de saída / capacidade de carga insuficiente: Priorize a verificação de terminais soltos, baixa tensão de entrada e desclassificação de alta temperatura
OK, contato aberto: Sobrecorrente de saída / proteção contra curto-circuito ou superaquecimento interno. Desconecte a carga e teste novamente
Tropeçar na energização devido a irrupção: Utilize o recurso de reforço e avalie a corrente de pico de comutação
📦 Código HS para Exportação
8504401400 (Conversores estáticos, fonte de alimentação de comutação industrial, apenas para referência alfandegária, sujeito à determinação alfandegária local)
TRIO-PS-2G/3AC/24DC/10 (Número do pedido. 2903154)
Eficiência: >92%
Condição de teste: 400Entrada V CA, carga nominal completa
Parâmetros Adicionais de Consumo de Energia
Consumo de energia sem carga: <1.1 W
Power loss at rated load: <22 W
Observação: This value is the nominal figure from Phoenix Contact official datasheet. Actual efficiency under light load (20%~50% load) will be slightly lower than the 92% full-load rating.
TRIO-PS-2G/3AC/24DC/10 (Número do pedido. 2903154)
Dimensões gerais (L × A × P): 42 milímetros × 130 milímetros × 160 milímetros
📌 Installation Clearance (Critical for cabinet layout)
Horizontal sides: Zero gap side-by-side mounting allowed at ambient ≤40℃; reserve 10mm side clearance when temperature approaches 70℃
Vertical: ≥50mm clearance at top and bottom (obrigatório)
Trilho de montagem: Standard NS35 DIN rail (EN60715)
Peso
Aprox.. 1.1kg
Phoenix Contact TRIO-PS-2G Series Full Model List (TRIO POWER 2nd Generation, Terminais push-in)
Recursos comuns da série: Montagem em trilho DIN35, dynamic Boost (1.5×rated current for 5s), DC-OK relay alarm, parallel redundancy support, -25~+70℃, redução de 2,5%/K acima de 60°C
1-phase Input 1AC (100~240 VCA)|24VDC Output
| Modelo | Número do pedido. | Classificação de saída | Dimension W×H×D(milímetros) |
| TRIO-PS-2G/1AC/24DC/3/C2LPS | 2903147 | 24V 3A /72W | 30 ×130 ×115 |
| TRIO-PS-2G/1AC/24DC/5 | 2903148 | 24V 5A /120W | 36 ×130 ×115 |
| TRIO-PS-2G/1AC/24DC/10 | 2903149 | 24V 10A /240W | 42 ×130 ×160 |
| TRIO-PS-2G/1AC/24DC/20 | 2903151 | 24V 20A /480W | 65 ×130 ×160 |
3-phase Input 3AC (3×320~575VAC, rated at 3×400VAC)|24VDC Output (Seu grupo de modelos alvo)
| Modelo | Número do pedido. | Classificação de saída | Dimension W×H×D(milímetros) |
| TRIO-PS-2G/3AC/24DC/5 | 2903153 | 24V 5A /120W | 36 ×130 ×115 |
| TRIO-PS-2G/3AC/24DC/10 | 2903154 | 24V 10A /240W | 42 ×130 ×160 |
| TRIO-PS-2G/3AC/24DC/20 | 2903155 | 24V 20A /480W | 65 ×130 ×160 |
| TRIO-PS-2G/3AC/24DC/40 | 2903156 | 24V 40A /960W | 120 ×130 ×160 |
1-phase Input 1AC|48VDC Output
| Modelo | Número do pedido. | Classificação de saída | Dimension W×H×D(milímetros) |
| TRIO-PS-2G/1AC/48DC/5 | 2903159 | 48V 5A /240W | 42 ×130 ×160 |
| TRIO-PS-2G/1AC/48DC/10 | 2903160 | 48V 10A /480W | 65 ×130 ×160 |
- Common Matching Accessories (For cabinet integration)
- QUINT-DIODE/12-24DC/20 Redundancy diode module for dual power supply redundancy
- CBM E4 24DC/0.5-10A NO-R 4-channel 24V electronic circuit breaker (2905743)
- CBM E8 24DC/0.5-10A NO-R 8-channel electronic circuit breaker (2905744)
✅ Key Selection Guidelines
- Suffix C2LPS: Only available for the 3A single-phase variant with SIL capability; not required for standard automation projects
- 3AC three-phase models can run on two phases (L1/L2 only)
- Width reference: 3A=30mm; 5A=36mm; 10A=42mm; 20A=65mm; 40A=120mm, o layout do gabinete depende principalmente da largura
Lista de certificação da série Phoenix Contact TRIO-PS-2G (Incluindo TRIO-PS-2G/3AC/24DC/10, Pedido nº 2903154)
Todos os modelos desta série compartilham o mesmo pacote de certificação. Somente o modelo com sufixo C2LPS possui capacidade SIL0 extra; modelos padrão são SIL=0
✅ Certificações Globais
- CE (UE)
Diretiva de Baixa Tensão LVD 2014/35/EU
Diretiva EMC 2014/30/UE
- UL / cULus (Listado pela UL)
UL508 (Equipamento de controle industrial)
UL60950-1 (Segurança da tecnologia da informação)
ANSI/ISA-12.12.01, Classe I Divisão II Grupos A/B/C/D (adequado para áreas perigosas da América do Norte)
- Certificado IECEE CB (Esquema CB, base para conversão de certificação multipaíses)
- Certificação da União Aduaneira EAC (Rússia, Bielorrússia, Cazaquistão e outros mercados da EAEU)
- Certificado Marítimo DNV GL (Adequado para gabinetes de controle marítimos e offshore)
- BIS (Licença BIS para o mercado indiano)
✅ Conformidade Ambiental
RoHS (UE)
ALCANÇAR
REEE em conformidade com a diretiva de resíduos de equipamentos elétricos e eletrônicos
✅ Segurança & Padrões Funcionais (Padrões ≠ Certificados; especificações de conformidade do produto)
CEI 60950-1: Tensão extrabaixa de segurança SELV
EM 50178: Tensão Extra-Baixa Protetora PELV
EM 60204-1: Segurança de equipamentos elétricos de máquinas (amplamente utilizado para máquinas)
EM 50121-4: Padrão EMC ferroviário
CEI 61508: SIL 0 (Modelos padrão desta série; TRIO-PS-2G/1AC/24DC/3/C2LPS é especificamente marcado como segurança funcional SIL0)
Inflamabilidade da carcaça: UL94 V0
✅ Padrões de compatibilidade eletromagnética EMC
EM 61000-6-1 / 6-2: Imunidade (residencial / ambientes industriais)
EM 61000-6-3 / 6-4: Irradiado & emissões conduzidas
EM 61000-3-2: Limites de corrente harmônica
📌 Observações de seleção
- Projetos nacionais: Sem certificado CCC, não está dentro do escopo 3C obrigatório. CE para exportação da UE, UL para a América do Norte, EAC para Rússia/Ásia Central, DNV para projetos marítimos.
- Nível SIL: O padrão TRIO-PS-2G não pode ser usado para circuitos de segurança SIL1 e superiores. Se for necessário um nível mais alto de SIL, selecione fontes de alimentação com classificação SIL da série QUINT.