Schneider 3-pole main contacts LC1D38BD - Contator,disjuntor,sensor,Codificador,CLP,Conversor

Conversamos: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Sobre Contato |

Schneider 3-pole main contacts LC1D38BD - Contator,disjuntor,sensor,Codificador,CLP,Conversor

contator/

Schneider 3-pole main contacts LC1D38BD

Schneider TeSys Deca series, 3-contatos principais do pólo, 24Bobina VCC. Designed for motor start/stop, HVAC and automation control cabinets. Built-in 1NO+1NC auxiliary contacts. ✅ Model Code Definition LC1: Standard contactor D: TeSys D (Deca) série 38: Rated operational current 38A @ AC-3, 400V BD: 24V DC coil (integrated coil surge suppression) 📌 Key Electrical Specifications ...

  • Detalhes do produto

Schneider TeSys Deca series, 3-contatos principais do pólo, 24Bobina VCC. Designed for motor start/stop, HVAC and automation control cabinets. Built-in 1NO+1NC auxiliary contacts.

✅ Model Code Definition

LC1: Contator padrão

D: TeSys D (Deca) série

38: Rated operational current 38A @ AC-3, 400V

BD: 24V DC coil (integrated coil surge suppression)

📌 Key Electrical Specifications

ItemEspecificação
Principais Contatos3P Normalmente Aberto (3NÃO)
AC-3 @ 400V38UM, controls motor power up to 18.5kW
Carga resistiva AC-150UM
Tensão operacional nominal Ue (circuito principal)690V e
Coil voltage Uc24Em DC
Contatos auxiliares integrados1NÃO + 1NC (NC is mirror contact for safety circuits)
Max operating frequency3600 ciclos/hora
Temperatura ambiente-5℃ ~ +60 ℃ (sem desclassificação)
MontagemMontagem em trilho DIN / Screw panel mounting
Largura45milímetros
Peso líquido0.54kg
TerminaisEverLink screw-clamp terminals, compatible with cable lugs

🛠️ Typical Applications

Direto on-line, star-delta and forward/reverse control of 3-phase asynchronous motors

Sistemas HVAC, bombas de água, fãs, compressores de ar

Equipamento de automação, packaging machinery and production line control cabinets

Direct coil drive by PLC 24VDC digital outputs (no intermediate relay required)

🧩 Compatible Accessories

Relé de sobrecarga térmica: Série LRD (LRD35…), snap-fit directly below the contactor

Bloco de contato auxiliar: LA1DN (for extra NO/NC contacts)

Módulo de intertravamento mecânico: LA9D4001 (for forward/reverse interlock)

Supressão de surto: Integrated inside coil, no external component needed

🔁 Alternative & Compatible Selection

  1. AC coil variants within the same series: LC1D38M7 (220VAC), LC1D38B7 (24VAC)
  2. Alternativa doméstica: CJX2-3811 DC24V (note differences in dimension, terminals and mechanical life)

⚠️ Importante: BD = 24VDC, B7 = 24VAC. Coils are NOT interchangeable.

📋 Certifications & Padrões

CEI 60947-1/-2/-4-1, CCC, cULus. Complies with IEC60335-1 flame retardant standard and A2L refrigerant safety certification for HVAC.

🧪 Second-hand Inspection Checklist

  1. Bobina: Continuity check on A1/A2. Apply 24VDC; armature pulls in without noise or overheating.
  2. Principais contatos: L1/L2/L3 ↔ T1/T2/T3. Conductive when closed, high resistance when open; inspect contact erosion.
  3. Contatos auxiliares: 13-14(NÃO), 21-22(NC). Switch synchronously with main contacts.
  4. Mecânico: No sticking; housing free of cracks or carbon blackening.

Referência do Código HS

8536410000 (Electromagnetic contactor, voltage ≤60V)

Typical Engineering Application Cases for LC1D38BD

Principais vantagens: DC24V coil, direct PLC drive without intermediate relay; built-in surge suppression and certified mirror NC contact; 18.5kW max 3-phase motor @ AC-3, 50A for AC-1 resistive loads

Caso 1: Chilled water pump DOL start for HVAC BMS (Sistema de automação predial)

Carregar: 15kW 3-phase chilled water pump, 380V, motor rated current ≈28A

Control scheme: CLP (Siemens / Schneider M241) DO directly drives LC1D38BD 24VDC coil

Circuito principal: 3P circuit breaker → LC1D38BD → LRD35 thermal overload relay → pump motor

Lógica de controle: BMS outputs 24VDC based on water temperature/pressure differential to energize contactor and start pump. Built-in 1NO auxiliary contact feeds running status back to PLC; built-in mirror NC contact for fault acquisition.

Selection rationale: DC coil provides strong anti-interference. BMS cabinets commonly adopt DC24V control. Wide temperature range -5~+60℃ suits high-temperature equipment rooms. 45corpo estreito de mm economiza espaço no gabinete.

Acessórios: LRD35 thermal relay (28~36A), Montagem em trilho DIN.

Caso 2: Air compressor motor control (OEM machinery manufacturer)

Carregar: 18.5kW screw air compressor main motor, 400V

Control scheme: PLC directly drives LC1D38BD with pressure switch interlock for shutdown

Circuito: Circuit breaker → LC1D38BD → LRD thermal relay → air compressor motor

Características: Parada frequente (máx. 3600 ciclos/hora). DC coil pulls in stably without AC hum. Built-in coil surge suppression protects PLC output points against back EMF.

Observação: AC-3 operation reaches the 38A rating limit. Derating evaluation is recommended for heavy-duty frequent cycling.

Caso 3: Water treatment — duty/standby mutual interlock control cabinet for sewage lift pumps

Carregar: Two 15kW sewage pumps, duty-standby auto-switching by liquid level

Configuração: 2 × LC1D38BD + LA9D4001 mechanical interlock module

Lógica: Pump starts on high liquid level. If main pump trips (thermal relay fault), PLC automatically switches to standby pump. Mechanical interlock prevents simultaneous closure and short circuit.

Safety feature: Built-in mirror NC contact for safety loop and fault diagnosis, meeting water treatment control cabinet safety specifications.

Aplicativo: Municipal sewage, factory circulating water, rainwater lift pumping stations.

Caso 4: Forward/reverse circuit for conveyor motors in packaging machinery / linhas de produção

Carregar: 11~15kW belt conveyor motor requiring forward and reverse rotation

Configuração: 2 × LC1D38BD (KM1 forward, KM2 reverse) + LA9D4001 mechanical interlock

Controlar: PLC 24VDC digital outputs drive each contactor coil separately. Electrical interlock (using built-in NC auxiliary contacts) plus mechanical interlock provides double protection to prevent power short circuit.

Vantagem: DC coil has better EMI immunity than AC coils in workshops dense with inverters and sensors, reducing accidental pull-in faults.

Caso 5: Star-delta reduced voltage starting for 18.5kW dust extraction fan

Carregar: 18.5kW dust removal fan with high inrush current, star-delta starting adopted

Configuração: 3 × LC1D38BD, serving as main contactor, star contactor and delta contactor respectively

Lógica: PLC outputs 24VDC sequential control; star reduced-voltage start first, then time-delayed switch to delta full-voltage operation. Built-in contactor auxiliary contacts provide status feedback and electrical interlock.

Observação: High inrush current occurs at delta switching in star-delta circuits; contact life must be reviewed.

Caso 6: Carga resistiva AC-1: Industrial heating module control

Carregar: 3-phase heating elements, total resistive load ≤33kW (AC-1 50A @400V)

Recurso: Resistive load has no starting inrush current. AC-1 rated 50A capacity higher than motor duty. PLC 24V DO directly controls heating circuit on/off.

Aplicativo: Fornos, constant temperature units, process heating equipment.

Caso 7: Cleanroom air handling unit for medical facilities (medical HVAC)

Carregar: 15kW supply air fan for operating room clean air conditioning

Características: Medical equipment demands high reliability and low EMI. LC1D38BD DC coil with built-in surge suppression, no electromagnetic noise from AC coils. Complies with IEC60335 HVAC safety standard, suitable for A2L refrigerant HVAC equipment, widely used in hospital BMS control cabinets.

Seleção Geral & Construction Key Points (Valid for All Cases)

  1. DC coil critical note: BD = 24VDC, MUST NOT be connected to AC24V. PLC output capacity must meet coil power consumption (~15VA).
  2. Contatos auxiliares: Built-in 1NO (feedback em execução) +1NC (mirror safety contact, NOT for normal latching). Add LA1DN auxiliary contact block for more contacts.
  3. Proteção contra sobrecarga: Must be fitted with LRD thermal overload relay, set per motor nameplate current and shall not exceed motor rated current.
  4. Utilisation category distinction

AC-3 (partida-parada normal do motor): 38UM, max 18.5kW @400V

AC-1 (pure resistive heating): 50UM

AC-4 (frequent jogging, plug braking): desclassificação necessária

Not Suitable Applications

Direct-on-line starting of 3-phase motors above 18.5kW (AC-3)

High-power capacitor switching (use dedicated LC1DxxKQ capacitor contactors)

Áreas perigosas de explosão (explosion-proof series required)

LC1D38BD (TeSys D DC Coil) Contorno & Dimensões de montagem

Without attached accessories (contatos auxiliares, relé térmico, intertravamento mecânico), Versão de bobina DC

Dimensões do contorno (L × A × P)

45 milímetros × 85 milímetros × 92 milímetros

Largura: 45milímetros (DIN rail module, 1 module unit)

Altura: 85milímetros

Profundidade: 92milímetros (from mounting backplate to front face)

Panel screw mounting holes (DC coil specific, round holes for M4)

Horizontal center distance between two holes: 35 milímetros

Vertical center distance between two holes: 70 milímetros

Screw size: M4, two round holes (⚠️ AC coil LC1D38M7 uses slotted holes; mounting layout differs from BD DC version)

Montagem em trilho

Compatível com trilho DIN padrão de 35 mm (TH35-7,5), clip-on installation, no drilling required.

Cabinet Layout Recommendations

  1. Mounting LRD thermal relay at bottom: overall height increases; reserve adequate clearance.
  2. Mounting LA1DN auxiliary contact block on top: extra depth and height required.
  3. Multiple contactors side-by-side: 45mm largura, can be mounted tightly on rail without gap. Reserve heat dissipation gap for high-temperature environments.

Operating Principle of Schneider LC1D38BD Contactor

LC1D38BD is an electromagnetic contactor with DC coil (Série TeSys D). Essencialmente, it is a remotely controlled electrical switch driven by 24VDC electromagnet, using low DC signal to switch high-power 3-phase main circuit.

  1. Basic Structure
  2. Electromagnetic actuation section (Bobina A1/A2): 24V DC excitation coil, fixed core, moving armature, mola de retorno
  3. Principais contatos (power circuit L1/L2/L3 → T1/T2/T3): 3 pairs of normally-open main contacts, rated 38A AC-3, carrying high current for 3-phase motors / heating loads
  4. Contatos auxiliares (feedback de sinal): Built-in 1NO (13-14)+1NC (21-22) mirror auxiliary contacts for status feedback and electrical interlock
  5. Arc chamber: Extinguishes electric arc when main contacts open, protecting contacts from rapid erosion

✅ Key feature for BD model: DC coil with integrated surge suppressor.

  1. Full Operating Sequence

2.1 Bobina Energizada (Pull-in action)

Apply DC24V to A1 and A2 via PLC or external control circuit:

DC coil generates constant magnetic field, magnetizing fixed core, overcoming return spring force and pulling in moving armature.

Armature drives contact carrier synchronously:

3 pairs of main NO contacts close → 3-phase main circuit energized, motor/load powered on

Auxiliary contacts switch simultaneously: 13-14(NÃO) fecha; 21-22(NC) abre

Characteristic of DC coil: constant current after pull-in, no vibration or hum from AC coils.

2.2 Coil De-energized (Drop-out action)

DC24V control signal removed:

Magnetic field of coil disappears, return spring pulls armature back.

All main contacts open, cutting high-current main circuit.

Auxiliary contacts reset: 13-14(NÃO) abre; 21-22(NC) restores closed state.

Built-in surge suppression absorbs back EMF generated at coil de-energization, protecting upstream PLC output points.

  1. Core Differences Between DC Coil (BD) and Conventional AC Coil
  2. Bobina CA: operates on alternating magnetic field, prone to vibration and hum; alta corrente de partida; contact bounce under voltage fluctuation.
  3. LC1D38BD DC24V coil:

Stable magnetic field, armature free of vibration, operação silenciosa

Pull-in current ≈ holding current, baixa irrupção

Built-in freewheeling suppression, ideal for direct PLC DO drive

Desvantagem: Must never connect to AC supply; AC input burns coil immediately.

  1. Typical Functions of Auxiliary Contacts

1NÃO (13-14): Running status feedback to PLC to detect contactor pull-in state

1NC (21-22, mirror contact): Safety circuits, fault detection, electrical interlock (forward/reverse circuits)

⚠️ Mirror contact property: NC contact cannot close when main contacts are welded shut, complying with safety circuit requirements.

  1. Mandatory Protection Logic for Engineering

The contactor only performs switching and has NO overload protection:

Fit LRD thermal overload relay in main circuit: on motor overload, thermal relay NC contact opens contactor coil circuit to cut motor power.

Circuit breaker installed upstream: fast short-circuit protection for main power supply.

Resumo de uma frase:

Apply DC24V to A1/A2; electromagnetic force actuates internal contacts to close high-power 3-phase main circuit. Remove 24V supply; spring resets and opens main circuit. Low-voltage 24V signal remotely switches high-power loads. Auxiliary contacts provide status feedback and safety interlock.

Anterior:

Deixe uma resposta

Deixe um recado