3-contator CA de pólo, rated current 115A (AC-3), 220VAC coil, 1Contatos auxiliares NO+1NC, terminais de parafuso
Número do pedido: LC1D11500M7C (modelo completo), LC1D115M7C (abbreviated model)
Domestic TeSys D series, phased out (launched in July 2025). Recommended replacements: LC1D115KUEC or LC1E120M5N
Complete certifications: UL, CSA, CEI, CCC, EAC, etc.. Compliant with RoHS/REACh standards
- Explicação do código do modelo
| Segmento | Código | Descrição |
| Categoria de produto | LC1 | Contactor series |
| Construction Type | D | TeSys D Series (Domestic high-current type) |
| Corrente nominal | 115 | Rated operational current 115A (AC-3, ≤440V) |
| Contatos Auxiliares | 0 | Configuração padrão: 1NÃO + 1Contatos auxiliares NC |
| Coil Rating | M | 220VAC coil voltage |
| Frequency Code | 7 | Universal coil for 50/60Hz |
| Manufacturing Code | C | Manufactured by SSIC (faixa: 9~620A) |
Modelo Completo: LC1D11500M7C (official standard model), Abbreviated Model: LC1D115M7C
- Especificações principais
| Categoria | Detalhes |
| Parâmetros Básicos | 3-pólo (3P), 3SEM contatos principais, 1Contatos auxiliares NO+1NC, screw terminal connection |
| Corrente nominal | AC-1: 200UM (≤440V, ≤60°C); AC-3: 115UM (≤440V, ≤60°C) |
| Tensão nominal | Circuito principal: ≤1000VAC; Circuito de controle: 220VAC, 50/60Hz |
| Motor Control Rating | 30kW (220~230V), 55kW (380~400V), 75kW (500V) |
| Vida Mecânica | 10 milhões de operações (AC-3), 10 milhões de operações (AC-1) |
| Vida Elétrica | 1 million operations at rated current (AC-3), 1 million operations at rated current (AC-1) |
| Características da bobina | Pick-up power: 1200VA; Holding power: 120VA; Impedance: 0.6MΩ |
| Montagem | 35mm DIN rail mounting or direct panel mounting |
| Dimensões & Peso | Altura: 158milímetros; Largura: 120milímetros; Profundidade: 136milímetros; Peso: aprox.. 2.5kg |
| Classe de Proteção | IP20 (per IEC 60529) |
| Certificações | UL, CSA, CEI, CCC, EAC, Marinho, RINA, DNV, etc.. |
- Lista completa de modelos (LC1D Series 115A)
| Modelo | Tensão da bobina | Tipo de terminal | Observações |
| LC1D11500M7C | 220VAC | Parafuso | Tipo padrão (modelo original) |
| LC1D11500P7C | 380VAC | Parafuso | Common alternative voltage |
| LC1D11500F7C | 110VAC | Parafuso | Controle de baixa tensão |
| LC1D11500B7C | 24VAC | Parafuso | Safety extra-low voltage control |
| LC1D115006M7C | 220VAC | Ring terminal | For special wiring requirements |
| LC1D115KUEC | 100~250VAC/DC | Parafuso | Universal voltage, modelo de substituição |
| LC1D115ABD | 24CCV | Parafuso | DC coil version |
| LC1D115ALBD | 24CCV | Parafuso | Low-power DC coil |
- Cruzar & Replacement Model List
4.1 Schneider Original Replacements
| Modelo original | Modelo de substituição | Motivo da substituição | Compatibilidade |
| LC1D115M7C | LC1D115KUEC | Universal voltage coil (100~250VAC/DC), higher flexibility | Totalmente compatível, identical mounting dimensions |
| LC1D115M7C | LC1E120M5N | Upgraded TeSys E Series with improved performance | Identical mounting dimensions; verify auxiliary contact configuration |
| LC1D115M7C | LC1D11500M7C | Full official model, identical to abbreviated version | 100% compatível |
4.2 Cross-Brand Replacements
| Marca | Modelo de substituição | Principais diferenças | Applicability |
| ABB | A145-30-11 | Rated current 145A with larger margin | Different mounting dimensions; layout adjustment required |
| Siemens | 3RT2036-1BB40 | 125UM, AC-3, 220Bobina V | Same auxiliary contact layout, substituição direta |
| Interruptor Changshu | CJX2-1210 | Alternativa doméstica, econômico | Slightly lower performance, for general working conditions |
| Chint | NC1-1210 | Alternativa doméstica, desempenho de alto custo | Meets basic requirements, shorter service life |
- Aplicativo & Casos da Indústria
5.1 Cenários Aplicáveis
Controle Motor: Começar, stop and reverse control for 30~75kW three-phase squirrel-cage motors
Automação Industrial: Control circuits for production lines, transportadores, compressors and pumps
Distribuição de energia: Switching control for non-inductive or weakly inductive loads such as resistance furnaces and heaters (AC-1)
Sistemas HVAC: Control of large air conditioning compressors and ventilation fans
Marinho & Engenharia Offshore: Certified by marine classification societies for offshore equipment
5.2 Cenários não recomendados
Operação de alta frequência: Mais do que 120 starts/stops per minute (use LC1D170 series or dedicated contactors)
Ambientes Adversos: Heavy dust, corrosive gas or severe vibration (additional protection required)
DC Loads: Use dedicated DC contactors (por exemplo. LC1D115ABD)
High Altitude: Derating required above 2000m (10% derating per additional 1000m)
5.3 Casos de aplicação típicos
Caso 1: Fan Control in Steel Plant
Operating conditions: 380V, 55kW fan, AC-3, 10 starts per day, 20-hour continuous operation
Solução: LC1D115M7C + LRD3365 thermal overload relay
Vantagens: 3 years of stable operation without failure, baixo custo de manutenção
Caso 2: HVAC System in Pharmaceutical Factory
Operating conditions: 400V, 45kW compressor, AC-3, 24-hour continuous operation and frequent cycling
Solução: LC1D115M7C + Controle CLP + supressor de surto
Vantagens: Low noise and power consumption, compliant with GMP standards
- Solução de problemas & Maintenance Manual
6.1 Diagnóstico de falhas comuns
| Fenômeno de falha | Possíveis causas | Soluções |
| Contactor fails to close | 1. No voltage on coil; 2. Bobina queimada; 3. Mechanical jam | 1. Measure voltage across terminal A1/A2; 2. Check coil resistance (normal: aprox.. 320Oh); 3. Desligar, inspect mechanism and remove foreign objects |
| Loud noise after closing | 1. Subtensão; 2. Oil contamination on core contact surface; 3. Anel de sombreamento quebrado | 1. Ensure voltage within ±10% of rated value; 2. Clean core surface; 3. Substitua o conjunto da bobina |
| Overheated / burnt main contacts | 1. Overload current; 2. Mau contato; 3. Failed arc suppression | 1. Check for load overload; 2. Limpe ou substitua os contatos; 3. Inspect arc chute integrity |
| Auxiliary contact malfunction | 1. Oxidação de contato; 2. Fiação solta; 3. Desgaste mecânico | 1. Limpar contatos; 2. Reaperte os terminais; 3. Replace auxiliary contact block |
| Repeated coil burnout | 1. Flutuação severa de tensão; 2. Frequent cycling; 3. Excess ambient temperature | 1. Instale o estabilizador de tensão; 2. Replace with high-cycle model; 3. Improve heat dissipation |
6.2 Cronograma de Manutenção & Procedures
| Item de manutenção | Intervalo | Operação |
| Inspeção Visual | Mensal | Check for overheating marks, abnormal odors and loose parts |
| Inspeção de contato | Trimestral | Medir a resistência de contato (<50m惟), check for ablation |
| Coil Inspection | Semestralmente | Measure coil resistance and insulation performance |
| Mechanical Lubrication | Anualmente | Lightly lubricate moving parts (silicone grease recommended) |
| Overhaul | Todo 2 anos | Disassemble for full inspection, replace worn parts and clean interior |
- Phase-Out & Migration Guide
7.1 Phase-Out Information
Phase-out Plan: Schneider launched the phase-out of domestic high-current TeSys D series (115-170UM) in July 2025
Transition Period: July 2025 – December 2026. Production will cease after the period
Inventory: Stock is still available via some distributors. Procurement or model replacement is recommended as soon as possible.
7.2 Migration Solutions
| Migration Type | Modelo recomendado | Vantagens | Notas |
| In-Series Upgrade | LC1D115KUEC | Universal voltage coil for wider application | Identical mounting size, no cabinet modification needed |
| Cross-Series Upgrade | LC1E120M5N | TeSys E Series with enhanced performance and longer service life | Auxiliary contact layout may differ; verify control circuit |
| Cost-Saving Replacement | Changshu CJX2-1210 / Chint NC1-1210 | 30-50% redução de custos | Slight performance difference; for non-critical applications |
7.3 Migration Steps
- Confirm voltage and current requirements of the original control circuit
- Select suitable replacement model (LC1D115KUEC recommended)
- Verify compatibility of mounting dimensions and fixtures
- Confirm quantity and type of auxiliary contacts
- Replace contactor and conduct commissioning test
- Keep spare parts of the original model until the end of transition period
- Diretrizes de seleção
Regras de referência rápida
- LC1D: Schneider TeSys D series contactor
- 115: 115Uma corrente nominal (AC-3), matches 55kW motor at 400V
- M7C: 220VAC 50/60Hz coil, manufactured by SSIC
- 00: Standard 1NO+1NC auxiliary contacts
- Phase-out Notice: Prioritize LC1D115KUEC for replacement since July 2025
- Conformidade com frete aéreo & Certificações
Classificação de Transporte: Mercadorias não perigosas. Sem bateria de lítio embutida / supercapacitor, compliant with IATA regulations
Certificação CE: Compatível com EN 60947-4-1, CE marked
Certificação Ambiental: Compliant with RoHS/REACh directives, Green Premium product
Embalagem: Individual packaging to prevent damage during transit. Original packaging is recommended.