Application Fields of Schneider LTMR27MFM (TeSys T)
Current rating: 1.35~27A intelligent management controller for 3-phase asynchronous motors, equipped with Modbus-RTU communication. Widely deployed inside MCC cabinets for integrated motor protection, current monitoring and remote data transmission.
Detalhamento do código do modelo
LTMR27MFM
LTMR: TeSys T motor management controller base unit
27: Current measuring range 1.35~27 A (integrated current transformers)
M: Communication interface → Modbus RS485
FM: Control supply 100~240 VAC (AC)
Cross reference within series: LTMR27EFM = Ethernet; LTMR27CFM = CANopen
- Principais Especificações Elétricas
| Item | Parâmetro |
| Motor current range | 1.35 … 27 UM (built-in CT, no external current transformer required) |
| Controller power supply | 100~240 V AC 50/60 Hz (wide tolerance: 93.5~264 V) |
| Comunicação | Modbus RTU RS485, bloco terminal + RJ45 dual port; address 1~247; baud rate 1.2k~19.2k |
| E/S digitais | 6 entradas digitais; 3 NO relay outputs + 1 fault relay (1NÃO+1NC) |
| Relay contact rating | 5A /250VAC; 5A /30VDC |
| Montagem | Montagem em trilho DIN |
| Dimensões gerais | W91 mm × H61 mm × D122.5 mm; Peso líquido 0.53 kg |
| Temperatura operacional | -20 ℃ ~ +60 ℃; Storage temperature -40~80 ℃ |
| Classe de proteção | IP20 (for cabinet internal installation) |
- Built-in Protection Functions
✅ Thermal overload protection (thermal model)
✅ Phase loss & 3-phase current unbalance protection
✅ Locked rotor protection, proteção de início longo
✅ Underload protection (dry-running/belt breakage monitoring)
✅ Earth fault protection (internal or external zero-sequence CT)
✅ Support for PTC motor thermistor input
✅ Fault logging, trip history, operating hour counter
- Measurement Capability (Tensão & power measurement with LTME extension module)
Base unit measurement: 3-phase current, average current, unbalance current, earth fault current;
When fitted with LTME extension module: additional 3-phase voltage, potência ativa/reativa, fator de potência, medição de energia.
- Commissioning Software
Configuration via SoMove software (TeSys T DTM). Connect PC directly via front RJ45 HMI port for parameter setting, fault reading and real-time monitoring.
Optional local display panel: LTMCU / LTMCUF.
- Lifecycle Notice
The full LTMR TeSys T series is undergoing phase-out (EOL).
Official order cutoff date: 30 Sep 2026; Technical support ends: 31 Jan 2027
New Generation Replacement: TeSys Tera
Main unit: LTMTMFM (Modbus, 100~240VAC/DC)
Match current sensor:
2.5~25A → LTMTCTV25UT (closest match for original 1.35~27A application)
⚠️ Wiring layout and Modbus register mapping are not fully compatible between old and new series. On-site retrofit requires program re-commissioning.
- Aplicação Típica
Centros de controle de motores MCC, bombas de água, fãs, compressores, transportadores; projects in water treatment, AVAC, metallurgy and cement industries.
- Quick Distinction of Similar Models
LTMR27MFM:1.35~27A, Modbus, 100~240VAC
LTMR100MFM:5~100A, Modbus, 100~240VAC
LTMR27EFM:1.35~27A, Ethernet/IP
Main Industry Segments
- Municipal Water Supply & Tratamento de Águas Residuais (Aplicação mais comum)
✅ Municipal wastewater plants, waterworks, pumping stations
✅ Typical loads: bombas submersíveis, centrifugal pumps, bombas de retorno de lodo, aeration blowers, scrapers
Key requirements satisfied: proteção contra subcarga (dry-run prevention), proteção contra falha à terra, remote fault alarming, energy monitoring.
- AVAC, Edifícios Comerciais & Construindo Sistemas Eletromecânicos
✅ Shopping malls, hospitais, centros de dados, industrial park chiller plants
✅ Typical loads: chilled water pumps, cooling water pumps, cooling tower fans, exaustores, AHU fans
Vantagem: sobrecarga térmica & locked rotor protection; Modbus connection to building BA system for current data and fault signals.
- Cimento, Materiais de Construção & Aggregate Mining Production Lines
✅ Belt conveyors, elevadores de caçamba, auxiliary drives for roller presses, dust extraction fans, silo discharge equipment
✅ Targeted protection: locked rotor protection, proteção de início longo, phase unbalance protection to avoid motor burnout caused by mechanical jamming.
- Químico & Indústria Farmacêutica
✅ Circulation pumps, agitator motors, auxiliary air compressor motors, dust fans
✅ Supports PTC thermistor connection for motor winding temperature monitoring; fast tripping upon phase loss and earth faults to meet industrial safety standards.
- Comida & Bebida, Packaging Production Lines
✅ Conveyor motors, sopradores, wash pumps, packaging machine drives
Accurate underload monitoring to detect material shortage or belt detachment; fault history facilitates production maintenance.
- Trânsito Ferroviário & Tunnel Electromechanical Systems
✅ Tunnel jet fans, drainage pumps, exaustores de fumaça
Reliable protection for fire service motors; data upload to tunnel PLC control system.
- Power Plant Auxiliary Equipment
✅ Circulating water pumps, ventilation fans, ash handling conveyors; standard component inside power station MCC rooms.
- Porta & Armazenagem Logística
✅ Conveyors, stacker auxiliary drives, dust extraction fans, bombas de óleo de estação hidráulica
Matching Motor Power Reference (380V 3-phase motors)
LTMR27MFM measuring range 1.35~27A
Suitable motor power range: 0.75kW~13kW three-phase asynchronous motor.
Cenários de aplicativos não recomendados
- Motors above 13kW (select LTMR100 series instead)
- Equipment with frequent forward/reverse rotation and heavy impulse jogging operation (thermal model parameters require special evaluation)
- Explosion-proof enclosures without sufficient heat dissipation (ambient temperature must remain ≤60℃)
Selection Advantages Matched to Operating Conditions
Integrated current transformers, no external CT required, simplifies cabinet wiring;
Modbus RS485 interface, seamless connection with Schneider PLC (Modicon M241/M251/M340 etc.);
Comprehensive protection suite: sobrecarga, rotor bloqueado, perda de fase, current unbalance, underload, falha de terra, PTC temperature monitoring;
Fault history recording & running hour statistics, compliant with smart factory and energy management projects.
Operating Principle of Locked Rotor Protection on Schneider TeSys T LTMR27MFM
The LTMR27MFM implements locked rotor protection via real-time 3-phase current sampling + time threshold judgment, split into two independent configurable modes: Locked Rotor Protection during Start-up and Locked Rotor Protection in Running State.
- Hardware Foundation
The LTMR27MFM integrates built-in 3-phase current transformers to continuously sample stator current at high speed. The internal MCU calculates in real time:
- RMS value of three-phase currents
- Ratio between instantaneous current and rated operating current
- Duration of over-limit condition
No additional external sensors required; diagnosis relies purely on current signature analysis.
- Two Locked Rotor Protection Modes (Independently configured in SoMove)
Mode 1: Locked Rotor Protection during Motor Start-up
Application scenario: Motor cannot accelerate due to mechanical jamming at startup
- Judgment window: Controller identifies startup sequence (current surge, motor at standstill before acceleration)
- Lógica:
If start-up current > Locked Rotor Start Threshold, and duration ≥ Locked Rotor Start Delay → Trip command triggered
- Adjustable parameters (SoMove):
Locked rotor start current: typical range 1.5~8× motor rated current Ie (default 5Ie)
Locked rotor start delay: typical range 0.5~10 s
Propósito: Prevent winding burnout caused by prolonged high current when motor is blocked on startup; distinguish permanent stall from normal short-duration starting inrush current.
Mode 2: Locked Rotor Protection during Steady-State Operation
Application scenario: Mechanical blockage occurs after motor reaches rated speed (belt jamming, pump impeller stuck, foreign object entrapment)
- Judgment window: Controller confirms motor completes acceleration and enters stable operation
- Lógica:
If operating current > Running Locked Rotor Threshold, and duration ≥ Running Locked Rotor Delay → Trip command triggered
- Parameter characteristics:
Running locked rotor threshold is generally set lower than start-up threshold (typically 1.8~4 Ie), with shorter delay for rapid fault isolation.
- Full Internal Decision Workflow
- LTMR continuously samples three-phase currents and monitors current variation trends;
- Automatically distinguishes three operating states: Standstill → Start-up → Steady Run;
- Activates corresponding locked rotor threshold rules according to operating state;
- Starts timing once current exceeds set threshold continuously;
- When timing reaches configured delay:
✅ Internal protection sequence activated;
✅ Fault relay contact changes state;
✅ Disconnects contactor control circuit;
✅ Stores fault code BLR (Blocked Rotor) locally;
✅ Uploads locked rotor fault information to upper-level PLC via Modbus.
⚠️ Critical Distinction: Locked Rotor Protection ≠ Thermal Overload Protection
Proteção contra sobrecarga térmica: Based on motor thermal accumulation model, trips for sustained mild overload; slow response characteristic.
Proteção de Rotor Bloqueado: Fast acting definite-time protection against severe instantaneous overcurrent caused by mechanical stall, compensating the slow response of thermal protection.
- Key Commissioning Guidelines
- Motor rated current Ie must be entered accurately
All locked rotor thresholds are calculated as multiples of Ie. Incorrect setting leads to protection failure.
- Tuning principles for delay
Fãs & centrifugal pumps: Longer natural startup time → extend start-up locked rotor delay to avoid nuisance tripping.
Transportadores & trituradores: High risk of mechanical jamming → minimize running locked rotor delay for fast protection.
- Coordenação de proteção
Locked rotor protection can be enabled together with phase loss, desequilíbrio, underload and PTC temperature protection for multi-layer safety.
- Common setting pitfall
Do not set locked rotor threshold higher than the actual motor starting inrush current; otherwise protection will fail to respond during blocked startup.
- Fault Identification After Trip
With local display panel LTMCU: Fault code BLR shown on screen
SoMove fault log: Recorded as Blocked rotor
Corresponding dedicated Modbus fault register bit for HMI/PLC alarming.
- Limitações Funcionais
Locked rotor protection relies solely on stator current signature. Rare edge case limitation:
If mechanical jamming occurs with light load and current does not rise above threshold, stall cannot be detected. For such conditions, implement redundant monitoring via underload protection or vibration sensors.
Contator,disjuntor,inversor solar,medidor elétrico,baterias solares