Nome completo do produto: SITOP PSU100S 24V DC /5A Regulated Fonte de energia
Order Code Definition:
6EP = SITOP power supply family; 1333=24V 5A; 2BA20=PSU100S version, No Ex explosion-proof certification
✅ Core Electrical Specifications
Entrada
Fonte de energia: Single-phase AC 120/230V, 50/60Hz
Faixa de tensão: AC 85–132V (120V range) / 170–264V (230V range), Not full wide automatic range
Corrente de entrada nominal: 1.3A at 230V; 2.1A at 120V
Built-in input fuse; Recommended circuit breaker: B10A / C6A
Tempo de espera: ≥20ms at rated load
Saída
Avaliado: CC24V, 5UM, 120C
Output adjustable range: 22.8 ~ 28V (via potentiometer on housing)
Static accuracy: ±3%; Maximum ripple 150mV peak-to-peak
Capacidade de sobrecarga: 150% corrente nominal para 5 seconds per minute; Continuous operation at 120% carregar
Indicação de status: LED verde (24V OK) + Normally-open relay alarm contact (closed when power healthy)
📐 Mecânico & Ambiental
Montagem: Montagem em trilho DIN 35mm, natural air cooling
Peso: 0.4kg
Temperatura operacional: -10 ~ +70℃; Derating starts above 60℃ (3%/K); Upper limit drops to 50℃ if output >24V
Temperatura de armazenamento: -25 ~ +85℃; Humidity class EN60721 3K3
País de origem: Áustria; HS code: 85044083
🧩 Recursos
- Isolated industrial switching power supply, standard 24V power source for PLC, sensors and valve islands
- Relay signal contact, can be connected to PLC for power fault diagnosis
- Parallel connection for current expansion (Max ambient temperature derate by 10℃ when paralleled)
- Proteções: Sobrecorrente, sobretensão, overtemperature protection
- Certificações: UL508, CE, RoHS; This model no longer supports Ex certification
⚠️ Alternative Selections
Smaller model in same series: 6EP1332-2BA20 (24V/2,5A)
Larger model in same series: 6EP1334-2BA20 (24V/10A)
Referência de alternativas nacionais: Meanwell DR-120-24, Phoenix QUINT-PS/1AC/24DC/5
🛠️ Solução de problemas comuns
- No green LED: Check AC input voltage, fusível interno queimado; Trava de proteção contra curto-circuito de saída, ciclo de energia para redefinir
- Queda de tensão sob carga: Baixa tensão de entrada, redução de temperatura excessiva, carga contínua excedendo 120% avaliação
- Relé de alarme não fechado: Fonte de alimentação em estado de proteção ou tensão de saída muito baixa
Cenários de aplicação para 6EP1333-2BA20 (SITOP PSU100S 24V/5A)
Posicionamento central: Fonte de alimentação de controle SELV monofásica CA para 24 VCC dentro de pequenos gabinetes de controle, para alimentar o CLP, Módulos de E/S, sensores, válvulas, IHM e outros componentes industriais. Equipado com contato de alarme de relé de boa potência, adequado para autônomo / automação de pequenas estações, Montagem em trilho DIN.
- Fabricação de máquinas / Automação autônoma (Mais Comum)
- Máquinas de embalagem: Máquinas de embalagem vertical, rotuladores, embaladores de caixas, máquinas termorretráteis. Fonte de alimentação para S7-1200/1500, sensores fotoelétricos, sensores de proximidade, válvulas solenóides, relés de segurança e telas sensíveis ao toque; 5A capacidade corresponde aos loops de E/S de máquinas autônomas de médio e pequeno porte.
- Transporte & equipamento de classificação: Transportadores de correia pequenos, linhas de rolo, máquinas de transferência. Fornecimento de módulos de E/S, codificadores, sensores fotoelétricos, ilhas de válvulas pneumáticas; Suporta expansão paralela.
- Moldagem por injeção / equipamento auxiliar de estampagem: Gabinete de controle do manipulador, alimentador de materiais, gabinete controlador de temperatura do molde; Resistir à flutuação da rede, adequado para cargas com corrente de impulso de partida.
- Caixa de controle auxiliar de máquina-ferramenta: Pequenas máquinas especiais, gabinete de controle de fixação, energia para sensores, luzes indicadoras e circuitos de segurança.
- Automação de Processos (Tratamento de Água, AVAC, Municipal)
- Tratamento de água: Equipamento pequeno de purificação de água, sistema de dosagem química, gabinete de controle de reutilização de água recuperada. CLP + transmissores analógicos, interruptores de nível, válvulas solenóides; O contato de alarme do relé se conecta ao PLC para alarme remoto de falha de energia.
- AVAC: Construindo unidades de tratamento de ar, unidades de ar fresco, gabinete de controle do exaustor; Potência DDC, sensores de pressão diferencial, atuadores elétricos.
- Pequenas estações municipais de bombeamento, estações de monitoramento de esgoto: Caixa de controle de campo, aquisição de sensores + módulo de comunicação remota.
Observação: Este modelo sem certificação Ex; Se usado em área perigosa explosiva, o corpo da fonte de alimentação deve ser instalado dentro de um gabinete à prova de explosão IP54 ou superior.
- Logística, Armazenagem, Estações Auxiliares de Linhas de Produção Automatizadas
Gabinete de controle de estação de trabalho pequena de mini AS/RS, Estação terrestre AGV, scanning inspection station; Power ET200SP remote I/O, sensores fotoelétricos, RFID readers, luzes indicadoras.
Automotive component assembly stations, test fixture cabinets, standalone test benches.
- Outras indústrias
- Comida & farmacêutico: Small filling and inspection equipment control cabinet; CE/UL compliant, suitable for standalone control in clean rooms.
- Laboratory test equipment, non-standard automatic test benches.
- VP / energy storage auxiliary control cabinet: Local signal acquisition cabinet (only for control circuit, not power circuit).
✅ Typical Load Combination Reference (5A Capacity)
S7-1200 CPU + 8~16 DI/DO points + IHM + several proximity/photoelectric sensors + 2~4 pcs 24V solenoid valves + relé de segurança.
Cuidado: Solenoid valve has high inrush current, reserve margin during selection; High-power valves require separate power loop.
⚠️ Not Recommended Applications
- High-power 24V motors, heavy heating loads (This is control power supply, não é fonte de alimentação para cargas de alta potência)
- 3-sistema de entrada de fase (a menos que a energia monofásica seja derivada do front-end)
- Ambiente de corrosão pesada, exposição direta ao ar livre (deve ser instalado dentro do gabinete de controle)
- Instalação direta em área explosiva perigosa
- Fonte de alimentação principal para grandes sistemas (10Modelo A+ ou esquema redundante recomendado)
✅ Pontos-chave da seleção
Vantagens: Saída de relé com boa potência, 150% capacidade de sobrecarga de curto prazo, montagem compacta em trilho DIN, Isolamento de auto-segurança, ideal para pequenos gabinetes de controle que exigem monitoramento do status de energia.
Expansão de capacidade: Várias unidades em paralelo para aumentar a corrente de saída total; Reduza a temperatura ambiente máxima durante o paralelo.
Lista completa de modelos da série SITOP PSU100S (Entrada CA monofásica, Fonte de alimentação em trilho DIN)
Todos os modelos: Entrada CA 120/230V (85–132V/170–264V), equipado com contato de alarme de relé Power-good, resfriamento natural, Montagem em trilho DIN35.
24Série de saída V DC (Mais comum, subsérie do seu modelo)
| Número do pedido. | Especificação | Poder |
| 6EP1332-2BA20 | CC24V / 2.5UM | 60C |
| 6EP1333-2BA20 | CC24V / 5UM | 120C |
| 6EP1334-2BA20 | CC24V / 10UM | 240C |
| 6EP1336-2BA10 | CC24V / 20UM | 480C |
12Série de saída V DC
| Número do pedido. | Especificação | Poder |
| 6EP1322-2BA00 | DC12V / 7UM | 84C |
| 6EP1323-2BA00 | DC12V/14A | 168C |
Derived SIPLUS Wide-temperature Coated Version (Opcional, not standard PSU100S)
6AG1334-2BA20-4AA0: SIPLUS PS PSU100S 24V/10A, revestimento isolante, temperatura operacional -25 ~ +70℃, for high humidity and corrosive environments (ferrovia, outdoor cabinet)
✅ Common Features of Series
- Relay alarm output (Power-good dry contact for PLC diagnosis)
- Sobrecarga de curto prazo: 150% carregar para 5 segundos, handles solenoid valve impulse current
- Proteção: Sobrecorrente, sobretensão, overtemperature protection
- Multiple units can be paralleled to increase output current (Derate ambient temperature upper limit)
- Certificações: CE, UL508, RoHS; No Ex explosion-proof certification
⚠️ Distinction Reminder
PSU100S ≠ SITOP smart / PSU100C / PSU6200, não confunda:
PSU100S: With relay alarm contact, list above;
SITOP smart: Without relay alarm, menor custo;
PSU6200: Nova geração, with communication diagnosis function.
Input Voltage Specifications of 6EP1333-2BA20
Single-phase AC, Automatic dual-range switching, not continuous 85~264V full wide range
Faixa 1 (120V range): AC 85V ~ 132V
Faixa 2 (230V range): AC 170V ~ 264V
Rated input: AC 120V / 230V
Frequência de entrada: 47~63Hz (50/60Hz compatível)
Notas importantes
- Voltage gap: Cannot operate stably when AC voltage between 132V ~170V. Power supply will not work reliably if grid voltage falls within this gap, must pay attention during selection.
- Power supply automatically identifies voltage range internally, no manual DIP switch required.
- Tempo de espera: ≥20ms at rated load and rated input voltage.
- In domestic 3-phase cabinet, single-phase 220V tapped (170~264V range), falls into 230V range and works properly.
Housing Dimensions of 6EP1333-2BA20 (L × A × P)
50 milímetros × 125 milímetros × 120 milímetros
Largura (DIN rail direction): 50 milímetros
Altura (vertical): 125 milímetros
Profundidade (into cabinet): 120 milímetros
Installation Clearance (Heat dissipation requirement, critical for cabinet layout)
Folga superior: 50 milímetros
Folga inferior: 50 milímetros
Esquerda & certo: 0 milímetros, can be mounted side-by-side with other modules
Mount on EN 60715 standard 35mm DIN rail, wall mounting not supported.
Peso
Peso líquido: Aprox.. 0.4 kg
Dimension comparison of PSU100S series (for cabinet layout)
| Número do pedido. | W×H×D mm |
| 6EP1332-2BA20 | 32.5 × 125 × 120 |
| 6EP1333-2BA20 | 50 × 125 × 120 |
| 6EP1334-2BA20 | 70 × 125 × 120 |
| 6EP1336-2BA10 | 115 × 145 × 150 |
Contator,disjuntor,sensor,Codificador,CLP,Conversor