Pepperl+Fuchs KFU8-FSSP-1.D-Y Signal Converter

Nome completo: Frequency/Voltage/Current (10 kHz Version) KFU8 series DIN rail signal conditioning module, designed for frequency/speed acquisition from encoders and pulse sensors, converting pulse signals into standard analog signals, with an optional frequency-divided pulse output. Distinção: KFU8-FSSP-1.D-Y = 10 kHz maximum input frequency KFU8-FSSP-1.D-Y322444 = 40 kHz high-speed version Many suppliers mix these two models; ...

  • Detalhes do produto

Nome completo: Frequency/Voltage/Current (10 kHz Version)

KFU8 series DIN rail signal conditioning module, designed for frequency/speed acquisition from encoders and pulse sensoré, converting pulse signals into standard analog signals, with an optional frequency-divided pulse output.

Distinção:

KFU8-FSSP-1.D-Y = 10 kHz maximum input frequency

KFU8-FSSP-1.D-Y322444 = 40 kHz high-speed version

Many suppliers mix these two models; confirm the frequency limit during selection.

✅ Funções principais

  1. Two measurement modes: Freqüência (Hz) / Velocidade rotacional (rpm)

Faixa de frequência: 0.001 Hz ~ 9999 Hz

Faixa de velocidade: 0.02 rpm ~ 9999 rpm

  1. Configurable analog output (selectable via menu):

0…10V / 2…10V

0…20 mA / 4…20 mA

  1. Frequency-divided pulse output: division ratio 1~9999, isolated pulse signal for PLC or secondary instruments
  2. Integrado 24 V DC auxiliary sensor power supply; compatible with 2/3/4-wire proximity switches and NPN/PNP incremental encoders
  3. 4-digit red LED display; shows input Hz/rpm or output V/mA. 4-button local programming with one-touch Teach-In calibration
  4. Period measurement method, optimized for low-speed pulse signals

📌 Electrical Specifications

Fonte de energia: 24 Em DC

Consumo de energia: <5 W

Max input frequency: 10 kHz (este modelo); minimum pulse width ≥40 μs

Precisão: ≤0.2% FS

Processing response: 5 ms internal update; display refresh adjustable from 0.01~2.5 s (no impact on signal conversion)

Isolamento: Galvanic isolation between input and analog output

Classe de proteção: IP20 (somente montagem em gabinete)

Montagem: Snap-on 35 mm trilho DIN

Terminais: Removable coded terminals, wire cross-section 0.2~2.5 mm²

Temperatura operacional: -25 ℃~ +40 ℃ (sem condensação)

Temperatura de armazenamento: -40 ℃~+85 ℃

📋 Terminal Assignment

terminalSinal
1Sensor GND
2Saída de pulso
5Saída Analógica +
6Saída Analógica – (Tensão)
4Saída Analógica – (Atual)
7Sensor 24 V+
11Power Supply L+ 24 Em DC
12Power Supply L- 0 V
14NPN/PNP Input – (Cathode)
15NPN/PNP Input + (Anode)
13Sensor GND
Remaining terminalsNC (Não conectado)

⚙️ Factory Default Parameters

Modo: rpm (Velocidade rotacional)

Pulse per revolution (PPR): 1

Full Scale Range: 9999

Saída Analógica: 0…10V

Display Refresh Time: 0.33 é

Division Ratio: 1

Salvar parâmetros: Long-press Enter + + to store into EEPROM (power-down retention)

🛠 Aplicações Típicas

Speed measurement for conveyors, fãs, pumps and roller tables

Converting pulse signals from flowmeters into 4–20 mA analog signals for DCS/PLC

Encoder signal division, local speed display + analog transmission

Stable measurement of low-frequency pulse signals (period measurement outperforms frequency counting at low speeds)

⚠️ Troubleshooting Guide

FaltaPossíveis causas & Remédios
Sem energia, sem exibição1. Verificar 24 V DC at terminals 11/12; 2. Terminais soltos; 3. Reverse polarity protection activated
Signal present but reading always zero1. NPN/PNP wiring reversed; 2. Pulse width ≥40 μs; 3. Não 24 V on sensor supply terminal 7; 4. Wrong measurement mode (rpm/Hz)
Leituras flutuantes1. Increase display refresh time; 2. Use cabo blindado com aterramento de extremidade única; 3. Check voltage drop on encoder supply; 4. Ensure high level ≥16 V DC, low level ≤6 V DC
Analog output stuck1. Match current/voltage output type with AI card; 2. Max load resistance ≤600 Ω for current output; 3. Re-run Teach-In calibration
Display overflow1. Actual speed exceeds set RANGE; 2. Incorrect PPR setting (value too large)
No pulse output on terminal 21. Division ratio ≠ 1; 2. Open-collector output requires external pull-up resistor on PLC side; 3. Input frequency below lower limit
Self-test error Err on power-upEEPROM checksum failure; power cycle first; repeated error means hardware failure, replace the module
Poor low-speed accuracyThis module uses period measurement; ensure pulse width ≥40 μs; avoid ultra-narrow pulses

📎 Cross-model & Opções de substituição

Mesma série: KFU8-FSSP-1.D-Y322444 (40 kHz, for high-speed encoders)

Alternativas domésticas: CZJ, UBE frequency/speed isolators (must support period measurement + frequency-divided pulse output)

  1. Instruções de fiação (KFU8-FSSP-1.D-Y)

Full Terminal List

terminalSignal DefinitionObservação
1Sensor GNDSpare sensor ground
2Frequency-divided Pulse OutputIsolated pulse for PLC high-speed counter
4Current Output I-Negative terminal for 4…20 mA
5Analog U+/I+Common positive for voltage & current output
6Voltage Output U-Negative terminal for 0…10 V
7Sensor 24 V+Encoder/proximity sensor supply, máx.. 30 mA
8NAMUR Input –NAMUR sensor channel
9NAMUR Input +NAMUR sensor channel
11Module Power L+ 24 Em DCMain power positive
12Module Power L- 0 VMain power negative
13Sensor GNDSensor power ground
14NPN/PNP Input – (Cathode)Pulse negative
15NPN/PNP Input + (Anode)Pulse positive
OutrosNCDo not connect

Standard Wiring Schemes

  1. 3-wire PNP Encoder (Mais Comum)

Brown wire → Terminal 7 (24 V+)

Blue wire → Terminal 13 (GND)

Black signal wire → Terminal 15; terminal 14 shorted to 13 (GND)

  1. 3-wire NPN Encoder

Marrom → 7; Azul → 13

Black signal → 14; terminal 15 shorted to 7 (24 V+)

  1. 4–20 mA analog to DCS AI card

terminal 5 → AI+; terminal 4 → AI-

  1. 0…10 V voltage output

terminal 5 → AI+; terminal 6 → AI-

  1. Frequency-divided pulse output

terminal 2 to PLC high-speed counter; fit external pull-up resistor on PLC side

Aviso importante: Max sensor supply current = 30 mA; do not drive multiple encoders. Use shielded cable for long-distance pulse wiring, ground the shield only at one end.

  1. Button Operation & Configuração de parâmetros

4 front-panel keys: Modo (Menu), ◀, +, Digitar

  1. Ligar; wait for self-test then enter measurement display (Hz/rpm)
  2. Short press Mode to switch menu items; ◀ = shift digit; + = change value
  3. Salvar parâmetros: Long press Enter + + together to write into EEPROM (retained after power loss)
  4. Exit menu: Long press Mode to return to measurement screen

Menu Items (English Original)

  1. MODO: Measurement Mode

rpm = Rotational Speed (Encoder application recommended)

Hz = Frequency (Pulse flowmeter)

  1. PULSE: Pulses Per Revolution (PPR)

Exemplo: 1000-line encoder → set PULSE=1000

  1. RANGE: Full Scale Value

Exemplo: 0~1500 rpm → set RANGE=1500

  1. FORA: Tipo de saída

0-10V / 2-10V / 0-20mA / 4-20mA

  1. DIV: Division Ratio (1~9999)

Output pulse = Input pulse ÷ DIV; set DIV=1 if no division required

  1. DISP: Display Refresh Time (0.01~2.5 s)

Increase to 0.5~1 s to stabilize low-speed readings; definir 0.1 s for high speed

  1. ENSINAR: One-touch Calibration (Teach-In)

Run equipment to full-scale speed, enter TEACH and press Enter; auto-set upper range (zero point fixed at 0)

Padrão de fábrica: MODE=rpm, PULSE=1, RANGE=9999, OUT=0…10V, DIV=1, DISP=0.33 s

Procedimento de redefinição de fábrica

Ligar, hold Mode + Enter for 5 seconds until FACT appears; confirm to restore all factory settings. All custom parameters will be erased.

  1. Tabela de solução de problemas de falhas
SintomaEtapas de solução de problemas
Nenhuma exibição após a inicialização1. Medir 24 V DC between terminals 11 & 12; 2. Check loose terminals; 3. Reverse polarity protection triggered
No reading, display stays zero1. Verify NPN/PNP wiring polarity; 2. Ensure pulse width ≥40 μs; 3. Verificar 24 V output on terminal 7; 4. Confirm correct MODE (rpm/Hz)
Instável, flickering readings1. Increase DISP refresh time; 2. Shield cable single-end grounded; 3. Check voltage drop on encoder supply; 4. High level ≥16 V DC, low level ≤6 V DC
Analog output locked and unchanged1. Match OUT type with AI card (current/voltage cannot be mixed); 2. Current output load resistance ≤600 Ω; 3. Re-run TEACH calibration
Display over-range overflow1. Actual speed exceeds RANGE setting; 2. PPR value set too high
No pulse output on terminal 21. DIV ratio not equal to 1; 2. Open-collector output requires external power/pull-up resistor on PLC; 3. Input frequency below lower limit
Err code on power-up self-testEEPROM data error; restart first; repeated error = hardware damage, replace module
Inaccurate low-speed measurementThis module uses period measurement (good for low speed); ensure pulse width ≥40 μs, avoid ultra-narrow pulses
  1. Parameter Table (Chinese ↔ English, Exportable)
Chinese ParameterEnglish TagFaixaObservações
测量模式MODOrpm / HzVelocidade / Freqüência
每转脉冲数PULSE1~9999Encoder PPR value
满量程RANGE1~9999Corresponds to full-scale analog output
输出类型FORA0-10V,2-10V,0-20mA,4-20mAAnalog signal selection
分频系数DIV1~9999Pulse output division
显示刷新时间DISP0.01~2.5 sOnly affects display, no impact on conversion speed
一键标定ENSINAR-Dynamic full-scale calibration
精度Precisão≤0.2%FSFull-scale accuracy
最大输入频率Fmax10 kHzFor model Y only (not Y322444)
  1. Procedimento de comissionamento (On-site Sequence)
  2. Wire with power disconnected; double-check power, encoder and analog terminals
  3. Ligar; verificar 24 V DC on sensor supply terminal 7
  4. Set MODE, PPR, RANGE and OUT type
  5. Rotate the encoder and confirm reading follows actual speed
  6. Measure analog output with multimeter, verify zero and full-scale values
  7. If pulse division is needed: connect PLC high-speed counter and test terminal 2 pulse signal
  8. Save parameters and record settings; commissioning complete

Pepperl+Fuchs KFU8 Series DIN Rail Signal Converter Order List

Descrição: KFU8 = K-System local-display programmable signal conditioners; divided into standard type and Ex intrinsically safe barrier type.

Suffix rules:

1.D = 1-channel; 2.D = 2-channel

Y = 10 kHz input; Y322444 = 40 kHz (only for FSSP models)

Ex = Intrinsically safe for hazardous area Zone 0/1/2

Order Part NumberNome do produtoBrief FunctionÀ prova de explosão
KFU8-FSSP-1.D-YFrequency/Speed Converter (10 kHz)Encoder pulse → analog 0-10V/4-20mA, with frequency-divided pulse output & local displayNão
KFU8-FSSP-1.D-Y322444Frequency/Speed Converter (40 kHz)Same as FSSP, máx. 40 kHz for high-speed encodersNão
KFU8-DW-1.DSpeed MonitorOverspeed/underspeed monitoring with relay alarm output; máx. 40 kHz, period measurementNão
KFU8-UFC-1.DFrequency Converter with Limit Alarms1 mHz~10 kHz; NAMUR/dry contact input; 4-20mA + relé + saída de transistor; SIL2Não
KFU8-UFC-1.D.FAConversor de frequência (Versão antiga)Modelo legado; phase-out, replace with UFC-1.DNão
KFU8-UFC-Ex1.DIntrinsically Safe Frequency BarrierA partir de agora, Zona 0/1/2, NAMUR input, SIL2Sim (A partir de agora)
KFU8-UFT-2.DDual-channel Frequency/Slip/Speed Direction MonitorDual NAMUR/dry contact input; detect rotation direction, slip and synchronous deviation; analógico + saída de reléNão
KFU8-UFT-Ex2.DExplosion-proof Dual-channel Direction/Slip BarrierHazardous area dual-channel rotation monitoringSim (A partir de agora)
KFU8-USC-1.DUniversal Voltage/Current Signal ConverterIsolamento & scaling for 0/4-20mA & 0-10V analog signals; with limit relay alarmNão
KFU8-GUT-Ex1.DIntrinsically Safe Universal Temperature TransmitterRTD/Thermocouple input, dual relay alarm, SIL2Sim (A partir de agora)

Regra de codificação do modelo

KFU8 [Código de Função] [Canal].[Versão] [-Sufixo]

FSSP: Frequency Speed → Speed transmission with divided pulse output

DW: Speed Watch → Speed monitoring & alarme

UFC: Universal Frequency Converter → Frequency conversion + limit alarm

UFT: Universal Frequency Twin → Dual-channel frequency, direção & slip monitoring

USC: Universal Signal Converter → Standard analog signal isolation

GUT: Universal Temperature → Temperature signal transmission

Ex: Intrinsically safe explosion-proof barrier

1.D = Single channel; 2.D = Dual channel

Y = 10 kHz; Y322444 = 40 kHz (FSSP exclusive suffix)

KFU8 Series Common Accessories

K-CJC-EX: Cold-junction compensation terminal (for GUT temperature modules)

KF-ST-5BU / KF-ST-5GN: Removable coded terminals (blue/grey)

Power Rail: K-series power bus for multi-module parallel power supply

Guia de seleção rápida

  1. Speed transmission + divided pulse output → FSSP (S / Y322444)
  2. Overspeed/underspeed alarm (no divided pulse) → DW-1.D
  3. NAMUR proximity switch frequency input + alarm → UFC / UFC-Ex
  4. Dual encoders, slip & rotation direction detection → UFT-2.D / UFT-Ex2.D
  5. Analog 4-20mA/0-10V isolation, scaling & alarm → USC-1.D
  6. RTD/TC temperature measurement in hazardous area → GUT-Ex1.D

Notas Suplementares

All KFU8 modules: 40 mm largura, 35 mm montagem em trilho DIN, 4-exibição de dígitos + 4-button programming; different from non-display KFD0 / KFA5 barriers.

Fonte de energia: Most models support 20~90 V DC / 48~253 V AC; FSSP model only supports 24 Em DC.

End-of-life notice: UFC-1.D.FA is obsolete; select UFC-1.D for new projects.