Marca: TENSO (Peru)
Produto: 3-Phase Digital Adjustable Overvoltage / Subtensão & Proteção de sequência de fase Relé (Voltage Monitoring Relay)
- Explicação do código do modelo
DGK: Series of 3-phase digital voltage control relays
04: Function code → Overvoltage + Subtensão + Phase Sequence Monitoring
F: Versão com display digital (enhanced model)
Sibling model: DGK-04PF with extra phase loss protection
- Funções de proteção
- 3-proteção contra sobretensão de fase (Você>)
- 3-proteção de subtensão de fase (Você<)
- Sequência de fase / reverse phase protection (phase sequence detection cannot be turned off on DGK-04F)
- Real-time digital display of 3-phase line voltages + fault LED indication
- Especificações Técnicas
Fonte de energia & medição: 3-phase AC380V, no neutral required, L1/L2/L3 only
Freqüência: 50/60Hz auto-adaptive
Undervoltage setting range: 230~360V AC
Overvoltage setting range: 400~460V AC
Tempo de atraso de falha: 0.1~10s adjustable
Output contact: 1NÃO+1NC (SPDT), 5UM / 250V AC resistive load
Montagem: Montagem em trilho DIN padrão
Temperatura operacional: -10℃ ~ +55℃
Medindo precisão: ±1V
- Definição de terminal
L1, L2, L3: 3-phase voltage input
1, 2, 3: Relay changeover contacts
terminal 1: NC (Normalmente fechado)
terminal 2: COM (Comum)
terminal 3: NÃO (Normalmente aberto)
Fiação Padrão (Motor / Compressor de ar / Bomba de água)
Contactor coil circuit: Wire in series with 2-3 (NÃO)
Alarm lamp / Buzzer: Connect to 1-2 (NC)
Safety note: L1/L2/L3 must be from the same 3-phase power source; do not mix phases from different circuits.
- Fiação & Manual de Comissionamento
Panel Buttons & Indicadores
Você: Overvoltage setting key
Você< : Undervoltage setting key
t : Time delay setting key
Visor digital: Cyclically shows L1-L2 / L2-L3 / L3-L1 line voltages
FORA: Relay output indicator (LIGADO em condições normais)
Você: Overvoltage fault LED
Você< : Undervoltage fault LED
PHASE: Phase sequence error LED
Power-on logic: The unit shows parameter settings for 2 seconds first, then automatically cycles through 3-phase voltage readings.
Pre-power Check (Obrigatório)
- Perform all wiring with power disconnected; confirm no short circuit on L1/L2/L3.
- Contact load limit: Max 5A/250VAC; only interlock the control circuit, do not switch main power of large contactors directly.
- Keep away from inverters and large contactors to avoid strong electromagnetic interference.
Step-by-step Commissioning
Etapa 1: Ligar
Switch on 3-phase supply, digital display lights up:
OUT ON: Tensão & phase sequence normal, relay energized, 2-3 fechado.
PHASE ON: Phase sequence reversed → Power off and swap any two incoming phases (L1↔L2 or L2↔L3).
U/ U< SOBRE: Voltage exceeds threshold, protection activated.
Etapa 2: Set Undervoltage U< (Recomendado: 340V for 380V systems)
- Short press the U< key to enter undervoltage setup.
- Press U< to increase value; press t to decrease value.
- Espere 4 seconds without operation to auto-save and return to voltage monitoring screen.
Setting range: 230~360V
Etapa 3: Set Overvoltage U(Recomendado: 420V for 380V systems)
- Short press the Ukey to enter overvoltage setup.
- Press Uto increase value; press t to decrease value.
- Auto-save after 4 seconds idle.
Setting range: 400~460V
Etapa 4: Set Fault Time Delay t (Recommended 1~3s to avoid false tripping from momentary voltage dips)
- Short press the t key to enter delay setup.
- U= increase time; Você< = reduce time.
- Settings take effect after auto-save.
Faixa: 0.1~10s; same delay applies for fault trip AND automatic reset after voltage recovers.
Etapa 5: Phase Sequence Function Note
DGK-04F: Phase sequence detection cannot be disabled. Reverse phase will trigger protection, PHASE LED lights up, OUT turns off, and contact 2-3 abre.
If phase sequence monitoring is not required (fans without rotation direction requirement), you need to select another model. Only DGK-04PF adds phase loss protection.
Etapa 6: Teste Funcional
- Estado normal: OUT stays ON, 2-3 fechado, contactor can energize.
- Simulate overvoltage: Raise supply voltage or lower the Uthreshold; ULED lights up, OUT cuts off, 2-3 abre.
- Simulate undervoltage: Lower supply voltage or raise the U< limite; Você< LED lights up, relé desenergiza.
- Swap two phases: PHASE fault triggers, relay drops out.
Histerese: Relay only restores after voltage returns within the set window (+5V tolerance) plus the programmed time delay.
Parâmetros recomendados (AC380V 3-phase Equipment)
Undervoltage U<: 340V
Overvoltage U>: 420V
Time delay t: 2é
Troubleshooting List
- PHASE LED always ON after power-up: Phase sequence reversed; swap any two incoming phases.
- OUT OFF with no fault indication: One phase is missing; measure line voltages on L1/L2/L3.
- Falsos disparos frequentes: Increase time delay t; check for grid voltage flicker or loose terminal connections.
- Flashing reading on one phase: Abnormal voltage on that phase.
- Voltage reading normal but relay will not energize: Check continuity of terminals 2-3 and the contactor control circuit.
Proibições estritas
❌ Never connect L1/L2/L3 to the output terminals of an inverter (distorted sine wave will cause false fault alarms).
❌ Do not feed single-phase 220V power into L1/L2/L3.
❌ Do not use the relay contacts to drive high-power loads directly; only use them for control circuit interlock.
Atraso de tempo (t) Setting for TENSE DGK-04F
Faixa de atraso: 0.1~10 seconds. This single setting covers both fault confirmation delay AND voltage recovery reset delay. The relay will only re-energize after the voltage returns to normal and the set time elapses.
Etapas da operação
- While the display is cycling through line voltages, short press the t key to enter delay setup; the digital tube shows the current time value.
- Press U= increase time value
- Press U< = decrease time value
- Stop pressing any key; wait approx. 4 seconds for auto-save, then the unit returns to voltage monitoring mode automatically.
✅ Factory recommended setting: 1~2s to filter short grid transients and prevent false tripping.
Compressores de ar & bombas de água: 2s preferred
Fast cut-off protection requirement: set to 0.5s
Key Logic
When overvoltage / subtensão / reverse phase occurs: O relé começa a cronometrar; contacts only open after the delay expires.
When the fault clears and voltage recovers (with +5V hysteresis): The relay waits the same t seconds before closing contacts again.
Phase sequence faults also follow this same time delay setting.
Problemas comuns
New setting not saved: Do not press any confirm key; just wait for automatic return. Avoid long key presses.
Unwanted frequent tripping: Increase the t value.
Slow recovery after fault: Reduce the t value appropriately.
Full Model List of TENSE (Peru) DGK Digital Voltage Monitoring Relays
DGK series: Digital readout, adjustable over/undervoltage, Montagem em trilho DIN, no neutral required (L1/L2/L3 line voltage detection).
Suffix definition: F = digital display; P = phase loss protection added
| Modelo | Fase | Funções principais | Observações |
| DGK-01 | Monofásico | Adjustable overvoltage + subtensão, display digital | AC220V single-phase monitoring |
| DGK-03 | 3-fase | Sobre/subtensão ajustável, no phase sequence check, display digital | For loads with no rotation direction requirement |
| DGK-04 | 3-fase | Sobre/subtensão ajustável, no phase sequence, analog knob (sem exibição) | Analog version without digital readout |
| DGK-04F | 3-fase | Sobretensão + Subtensão + Sequência de fases, display digital | Seu modelo atual; no phase loss protection, phase sequence check cannot be disabled |
| DGK-04PF | 3-fase | Sobretensão + Subtensão + Sequência de fases + Perda de Fase, display digital | Upgraded model of DGK-04F, widely used on air compressors & refrigeradores |
Analog Knob Series (Série GK, No Digital Display)
| Modelo | Função |
| Guarda Geral-03 | 3-phase over/undervoltage adjustable, no phase sequence |
| Guarda Geral-04 | 3-phase over/undervoltage adjustable, no phase sequence |
| Guarda Geral-04F | 3-phase over/undervoltage + sequência de fase |
Sequência de fases / Perda de Fase / Unbalance Protection Series (Futebol / FKV Series, without continuous voltage adjustment window)
These models focus on phase loss, 3-phase unbalance and phase sequence; some support PTC motor temperature protection, not the DGK over/undervoltage main series.
Futebol-04: Perda de fase + sequência de fase, fixo 30% unbalance threshold
Futebol-05 / Futebol-05F: Perda de fase + sequência de fase, unbalance adjustable 5~25% (F = digital display)
FK-14 / FK-14P: Sequência de fase + perda de fase; P model with PTC motor thermal protection
FKM-05 / FKM-05F: Adjustable unbalance, sequência de fase, perda de fase
FKT-06 / FKT-06PF: 3-desequilíbrio de fase + perda de fase + sequência de fase; PF with PTC input
FKV-03 / FKV-03F / FKV-03DF / FKV-03AF: Perda de fase, sequência de fase, desequilíbrio; some versions require neutral N
FKV-14 / FKV-14P: Economy phase sequence & relé de perda de fase; P with PTC protection
Suffix Quick Reference
F: Digital display type
P: Phase loss protection function
T: Built-in PTC motor temperature protection
DF/HF: Adjustable unbalance ratio
N: Requires neutral wire (3P+N)
Guia de seleção rápida (Most Popular Engineering Models)
- Only over/undervoltage monitoring, no rotation check: DGK-03
- Sobre/subtensão + anti-reverse phase (motor rotation control): DGK-04F
- Sobre/subtensão + anti-reverse phase + proteção contra perda de fase: DGK-04PF (first choice for air compressors & refrigeradores de água)
- Only phase loss & unbalance monitoring without voltage threshold adjustment: Futebol-05F / FKV-14
Common Specifications for All DGK 3-phase Models
Saída: 1NO+1NC SPDT contact, 5A/250 VCA
Time delay: 0.1~10s ajustável (shared trip & reset delay)
Faixa de tensão: Undervoltage 230~360V; Overvoltage 400~460V (for 380V line voltage systems)
Poder & measurement input: L1/L2/L3 only, no neutral wire needed