TENSO DGK-04F Voltage Monitoring Relay

Marca: TENSO (Peru) Produto: 3-Phase Digital Adjustable Overvoltage / Subtensão & Relé de proteção de sequência de fase (Voltage Monitoring Relay) Model Code Explanation DGK: Series of 3-phase digital voltage control relays 04: Function code → Overvoltage + Subtensão + Phase Sequence Monitoring F: Versão com display digital (enhanced model) Sibling model: DGK-04PF with extra phase loss protection Protection ...

  • Detalhes do produto

Marca: TENSO (Peru)

Produto: 3-Phase Digital Adjustable Overvoltage / Subtensão & Proteção de sequência de fase Relé (Voltage Monitoring Relay)

  1. Explicação do código do modelo

DGK: Series of 3-phase digital voltage control relays

04: Function code → Overvoltage + Subtensão + Phase Sequence Monitoring

F: Versão com display digital (enhanced model)

Sibling model: DGK-04PF with extra phase loss protection

  1. Funções de proteção
  2. 3-proteção contra sobretensão de fase (Você>)
  3. 3-proteção de subtensão de fase (Você<)
  4. Sequência de fase / reverse phase protection (phase sequence detection cannot be turned off on DGK-04F)
  5. Real-time digital display of 3-phase line voltages + fault LED indication
  6. Especificações Técnicas

Fonte de energia & medição: 3-phase AC380V, no neutral required, L1/L2/L3 only

Freqüência: 50/60Hz auto-adaptive

Undervoltage setting range: 230~360V AC

Overvoltage setting range: 400~460V AC

Tempo de atraso de falha: 0.1~10s adjustable

Output contact: 1NÃO+1NC (SPDT), 5UM / 250V AC resistive load

Montagem: Montagem em trilho DIN padrão

Temperatura operacional: -10℃ ~ +55℃

Medindo precisão: ±1V

  1. Definição de terminal

L1, L2, L3: 3-phase voltage input

1, 2, 3: Relay changeover contacts

terminal 1: NC (Normalmente fechado)

terminal 2: COM (Comum)

terminal 3: NÃO (Normalmente aberto)

Fiação Padrão (Motor / Compressor de ar / Bomba de água)

Contactor coil circuit: Wire in series with 2-3 (NÃO)

Alarm lamp / Buzzer: Connect to 1-2 (NC)

Safety note: L1/L2/L3 must be from the same 3-phase power source; do not mix phases from different circuits.

  1. Fiação & Manual de Comissionamento

Panel Buttons & Indicadores

Você: Overvoltage setting key

Você< : Undervoltage setting key

t : Time delay setting key

Visor digital: Cyclically shows L1-L2 / L2-L3 / L3-L1 line voltages

FORA: Relay output indicator (LIGADO em condições normais)

Você: Overvoltage fault LED

Você< : Undervoltage fault LED

PHASE: Phase sequence error LED

Power-on logic: The unit shows parameter settings for 2 seconds first, then automatically cycles through 3-phase voltage readings.

Pre-power Check (Obrigatório)

  1. Perform all wiring with power disconnected; confirm no short circuit on L1/L2/L3.
  2. Contact load limit: Max 5A/250VAC; only interlock the control circuit, do not switch main power of large contactors directly.
  3. Keep away from inverters and large contactors to avoid strong electromagnetic interference.

Step-by-step Commissioning

Etapa 1: Ligar

Switch on 3-phase supply, digital display lights up:

OUT ON: Tensão & phase sequence normal, relay energized, 2-3 fechado.

PHASE ON: Phase sequence reversed → Power off and swap any two incoming phases (L1↔L2 or L2↔L3).

U/ U< SOBRE: Voltage exceeds threshold, protection activated.

Etapa 2: Set Undervoltage U< (Recomendado: 340V for 380V systems)

  1. Short press the U< key to enter undervoltage setup.
  2. Press U< to increase value; press t to decrease value.
  3. Espere 4 seconds without operation to auto-save and return to voltage monitoring screen.

Setting range: 230~360V

Etapa 3: Set Overvoltage U(Recomendado: 420V for 380V systems)

  1. Short press the Ukey to enter overvoltage setup.
  2. Press Uto increase value; press t to decrease value.
  3. Auto-save after 4 seconds idle.

Setting range: 400~460V

Etapa 4: Set Fault Time Delay t (Recommended 1~3s to avoid false tripping from momentary voltage dips)

  1. Short press the t key to enter delay setup.
  2. U= increase time; Você< = reduce time.
  3. Settings take effect after auto-save.

Faixa: 0.1~10s; same delay applies for fault trip AND automatic reset after voltage recovers.

Etapa 5: Phase Sequence Function Note

DGK-04F: Phase sequence detection cannot be disabled. Reverse phase will trigger protection, PHASE LED lights up, OUT turns off, and contact 2-3 abre.

If phase sequence monitoring is not required (fans without rotation direction requirement), you need to select another model. Only DGK-04PF adds phase loss protection.

Etapa 6: Teste Funcional

  1. Estado normal: OUT stays ON, 2-3 fechado, contactor can energize.
  2. Simulate overvoltage: Raise supply voltage or lower the Uthreshold; ULED lights up, OUT cuts off, 2-3 abre.
  3. Simulate undervoltage: Lower supply voltage or raise the U< limite; Você< LED lights up, relé desenergiza.
  4. Swap two phases: PHASE fault triggers, relay drops out.

Histerese: Relay only restores after voltage returns within the set window (+5V tolerance) plus the programmed time delay.

Parâmetros recomendados (AC380V 3-phase Equipment)

Undervoltage U<: 340V

Overvoltage U>: 420V

Time delay t: 2é

Troubleshooting List

  1. PHASE LED always ON after power-up: Phase sequence reversed; swap any two incoming phases.
  2. OUT OFF with no fault indication: One phase is missing; measure line voltages on L1/L2/L3.
  3. Falsos disparos frequentes: Increase time delay t; check for grid voltage flicker or loose terminal connections.
  4. Flashing reading on one phase: Abnormal voltage on that phase.
  5. Voltage reading normal but relay will not energize: Check continuity of terminals 2-3 and the contactor control circuit.

Proibições estritas

❌ Never connect L1/L2/L3 to the output terminals of an inverter (distorted sine wave will cause false fault alarms).

❌ Do not feed single-phase 220V power into L1/L2/L3.

❌ Do not use the relay contacts to drive high-power loads directly; only use them for control circuit interlock.

Atraso de tempo (t) Setting for TENSE DGK-04F

Faixa de atraso: 0.1~10 seconds. This single setting covers both fault confirmation delay AND voltage recovery reset delay. The relay will only re-energize after the voltage returns to normal and the set time elapses.

Etapas da operação

  1. While the display is cycling through line voltages, short press the t key to enter delay setup; the digital tube shows the current time value.
  2. Press U= increase time value
  3. Press U< = decrease time value
  4. Stop pressing any key; wait approx. 4 seconds for auto-save, then the unit returns to voltage monitoring mode automatically.

✅ Factory recommended setting: 1~2s to filter short grid transients and prevent false tripping.

Compressores de ar & bombas de água: 2s preferred

Fast cut-off protection requirement: set to 0.5s

Key Logic

When overvoltage / subtensão / reverse phase occurs: O relé começa a cronometrar; contacts only open after the delay expires.

When the fault clears and voltage recovers (with +5V hysteresis): The relay waits the same t seconds before closing contacts again.

Phase sequence faults also follow this same time delay setting.

Problemas comuns

New setting not saved: Do not press any confirm key; just wait for automatic return. Avoid long key presses.

Unwanted frequent tripping: Increase the t value.

Slow recovery after fault: Reduce the t value appropriately.

Full Model List of TENSE (Peru) DGK Digital Voltage Monitoring Relays

DGK series: Digital readout, adjustable over/undervoltage, Montagem em trilho DIN, no neutral required (L1/L2/L3 line voltage detection).

Suffix definition: F = digital display; P = phase loss protection added

ModeloFaseFunções principaisObservações
DGK-01MonofásicoAdjustable overvoltage + subtensão, display digitalAC220V single-phase monitoring
DGK-033-faseSobre/subtensão ajustável, no phase sequence check, display digitalFor loads with no rotation direction requirement
DGK-043-faseSobre/subtensão ajustável, no phase sequence, analog knob (sem exibição)Analog version without digital readout
DGK-04F3-faseSobretensão + Subtensão + Sequência de fases, display digitalSeu modelo atual; no phase loss protection, phase sequence check cannot be disabled
DGK-04PF3-faseSobretensão + Subtensão + Sequência de fases + Perda de Fase, display digitalUpgraded model of DGK-04F, widely used on air compressors & refrigeradores

Analog Knob Series (Série GK, No Digital Display)

ModeloFunção
Guarda Geral-033-phase over/undervoltage adjustable, no phase sequence
Guarda Geral-043-phase over/undervoltage adjustable, no phase sequence
Guarda Geral-04F3-phase over/undervoltage + sequência de fase

Sequência de fases / Perda de Fase / Unbalance Protection Series (Futebol / FKV Series, without continuous voltage adjustment window)

These models focus on phase loss, 3-phase unbalance and phase sequence; some support PTC motor temperature protection, not the DGK over/undervoltage main series.

Futebol-04: Perda de fase + sequência de fase, fixo 30% unbalance threshold

Futebol-05 / Futebol-05F: Perda de fase + sequência de fase, unbalance adjustable 5~25% (F = digital display)

FK-14 / FK-14P: Sequência de fase + perda de fase; P model with PTC motor thermal protection

FKM-05 / FKM-05F: Adjustable unbalance, sequência de fase, perda de fase

FKT-06 / FKT-06PF: 3-desequilíbrio de fase + perda de fase + sequência de fase; PF with PTC input

FKV-03 / FKV-03F / FKV-03DF / FKV-03AF: Perda de fase, sequência de fase, desequilíbrio; some versions require neutral N

FKV-14 / FKV-14P: Economy phase sequence & relé de perda de fase; P with PTC protection

Suffix Quick Reference

F: Digital display type

P: Phase loss protection function

T: Built-in PTC motor temperature protection

DF/HF: Adjustable unbalance ratio

N: Requires neutral wire (3P+N)

Guia de seleção rápida (Most Popular Engineering Models)

  1. Only over/undervoltage monitoring, no rotation check: DGK-03
  2. Sobre/subtensão + anti-reverse phase (motor rotation control): DGK-04F
  3. Sobre/subtensão + anti-reverse phase + proteção contra perda de fase: DGK-04PF (first choice for air compressors & refrigeradores de água)
  4. Only phase loss & unbalance monitoring without voltage threshold adjustment: Futebol-05F / FKV-14

Common Specifications for All DGK 3-phase Models

Saída: 1NO+1NC SPDT contact, 5A/250 VCA

Time delay: 0.1~10s ajustável (shared trip & reset delay)

Faixa de tensão: Undervoltage 230~360V; Overvoltage 400~460V (for 380V line voltage systems)

Poder & measurement input: L1/L2/L3 only, no neutral wire needed