EOCRSSD-30DF7 Schneider Digital Motor Protector

EOCRSSD-30DF7 is a digital motor protector manufactured by Schneider Electric (formerly Samwha, Coreea de Sud) with current range 3-30A and 110VAC control power supply. It provides triple protection against overload, phase loss and locked rotor. It is applicable for precise protection of three-phase low-power motors, capable of replacing traditional thermal relays to improve protection accuracy and fault diagnosis efficiency.

  1. Definiția codului modelului
Segment de codDescriere
EOCRElectronic Over Current Relay, core product positioning
SSDSolid State Digital, adopting solid-state electronic components and digital control technology
30Current protection range: 3~30A (direct connection, no external CT required)
DAfișaj digital, equipped with digital tube to display real-time 3-phase average current and fault status
F7Control power specification: 110VAC±15% (50/60Hz); other options: M7(220VAC), B(24VAC/DC)
  1. Specificatii tehnice principale
CategorieParametriiObservații
Informații de bază
MarcaSchneider Electric (Former Samwha Korea)Produced in Iksan, Korea; Authorized agent in China: Shanghai Hanshi Electric
Tip de produsDigital Overcurrent Relay / Motor ProtectorPrecizie mai mare (±5%) than traditional thermal relay
Parametrii electrici
Tensiune nominală de operare600V și (UL) / 690V și (CSA, IEC 60947-4-1)Suitable for low-voltage motor circuits
Tensiune nominală de rezistență la impuls6kVConform IEC 60947-4-1
Puterea de control110VAC±15%, 50/60HzMatched with F7 code
Consumul de energie≤3WLow power consumption for long-term operation
Protection Parameters
Interval de curent reglabil3~30A continuously adjustableAdjustment ratio: 10:1
Funcții de protecție1. Supracurent (O-Time: 0.5~10s adjustable)Independent adjustable start delay D-Time
2. Phase loss (fast protection within 3s)
3. Locked rotor (combined D-Time+O-Time protection)
Modul de resetareManual / Electric (opțional)Reset required after fault for restart
Ieșire & Afişa
Contact de ieșire1 NC + 1 NU (2-SPST)Evaluarea contactului: 3A/250VAC
Display ModeDigital tube displayReal-time 3-phase average current, flashing fault code indication
Fizic & Environmental
Dimensiune45×75×110mm, standard DIN rail mountingCompact size saves cabinet space
Grad de protecțieIP20 (front panel)Suitable for installation inside control cabinets
Temperatura de operare-20℃ ~ +60℃Adaptable to industrial temperature variation
Temperatura de depozitare-40℃ ~ +85℃Meet transportation and storage requirements
Certificare
Certificari internationaleCE, UL, CSARespectați IEC 60947-4-1, global applicable
Conformitatea transportului aerianNo built-in lithium battery, conform to UN38.3Shippable as general cargo without special packaging
  1. Cross-brand Comparison
ModelInterval de curentPuterea de controlAfişaProtecţieGama de prețuriAplicație
Schneider EOCRSSD-30DF73~30A110VACDigital displaySupraîncărcare / Phase loss / Locked rotor350~450CNY3-phase low-power motors with fault diagnosis demand
ABB CM-MSS.31P3~30A24~240VAC/DCIndicator lightSupraîncărcare / Phase loss / Locked rotor400~500CNYGeneral industrial motors, unified brand matching
Siemens 3RB2026-1SB02.5~32A24~240VAC/DCIndicator lightSupraîncărcare / Phase loss300~400CNYSupporting Siemens PLC, basic protection
Omron K8DS-PH13~30A100~240VACDigital displaySupraîncărcare / Phase loss / Locked rotor380~480CNYAutomated production lines, high-precision protection
Chint NR2-322.5~32ANo control powerNo displaySupraîncărcare / Phase loss50~80CNYEconomy application, low precision requirement

Puncte cheie ale selecției

  1. Display function: EOCRSSD-30DF7 supports real-time current monitoring and fault diagnosis, superior to indicator-light-only models
  2. Protection accuracy: Electronic protector (±5%) far exceeds thermal relay (±15%), extending motor service life
  3. Control power: 110VAC F7 version fits specific regional power grids, confirm on-site power supply first
  4. Lista completă a modelelor din seria

EOCR-SSD Series Classification

Interval de curentBase ModelPower OptionsComplete Model Examples
0.5~6AEOCRSSD-05SS:24~240VAC/DCEOCRSSD-05DF7, EOCRSSD-05DM7, EOCRSSD-05DB
F7:110VAC
M7:220VAC
W:380~440VAC
3~30AEOCRSSD-30SLa fel ca mai susEOCRSSD-30DF7, EOCRSSD-30DM7, EOCRSSD-30DW
5~60AEOCRSSD-60SLa fel ca mai susEOCRSSD-60DF7, EOCRSSD-60DM7, EOCRSSD-60DS

Cod de comandă & Accesorii

Număr de comandă standard: EOCRSSD-30DF7

Mounting bracket: EOCR-MNT-01 (DIN rail type)

Extension cable: EOCR-CAB-05 (5m) / EOCR-CAB-10 (10m)

Test kit: EOCR-TEST-KIT (including analog load & calibrator)

  1. Defecte comune & Maintenance Solutions
Fenomen de eroareCauze posibilePași de depanareSoluțiiPreventive Measures
No digital display1. Control power disconnected1. Measure terminal voltage1. Connect 110VAC correctlyCheck power spec before installation
2. Wrong wiring polarity2. Verificați cablajul2. Adjust connection (AC non-polar)
3. Internal fuse blown3. Inspect internal fuse3. Replace 0.5A fuse
False tripping1. Low current setting1. Confirm motor rated current1. Set current to 1.1 ori valoarea nominalăSet parameters per motor nameplate
2. Short start delay2. Extend D-Time2. D-Time = motor start time +1s
3. Power harmonic interference3. Test power THD3. Install power filter
Failure to trip1. Excessively high current setting1. Check current setting1. Set current to 0.9 ori valoarea nominalăRegular contact inspection, avoid overload
2. Damaged output contacts2. Test contact continuity2. Replace contact module
3. Internal circuit failure3. Inspect internal components3. Contact after-sales service
Garbled display1. Voltage fluctuation1. Test power stability1. Install voltage stabilizerKeep away from inverters, ensure good grounding
2. Electromagnetic interference2. Check grounding2. Optimize grounding
3. Program error3. Power cycle restart3. Restore factory settings

Ciclul de întreținere

  1. Daily inspection: Check display status and alarm indicator
  2. Monthly maintenance: Dust cleaning, tighten wiring terminals
  3. Quarterly calibration: Verify protection parameter accuracy
  4. Annual overhaul: Inspect internal components, replace aging parts
  5. Scenarii de aplicare & Cases

Scenarii aplicabile

Automatizare industrială: Mașini-unelte CNC, transportoare, echipamente de imprimare

Tratarea apei: Water pumps, fans with frequent startup and variable load

HVAC: Compresoare de aer, cooling tower fans

Building materials industry: Mixere, transportoare grele

Power system: Standby generators, small transformer protection

Non-recommended Scenarios

High voltage motors (>690V): Adopt dedicated high-voltage protectors

Explosion-proof environment: Extra explosion-proof housing required with higher cost

Ultra-low current (<0.5O): Choose EOCRSSD-05S or match external CT

Typical Cases

Caz 1: Water Pump Motor Protection in Steel Plant

Problemă: Frequent false tripping of old thermal relays causing unplanned shutdowns without fault identification

Soluţie: Install EOCRSSD-30DF7, set current 15A (motor rated 13.5A), start delay 5s

Efect: False shutdown rate reduced by 62%, fault diagnosis time shortened from 2h to 5min, annual maintenance cost saved about 80,000 CNY

Caz 2: Mixer System in Pharmaceutical Factory

Problemă: Motor burnout caused by mixer locked rotor leading to heavy losses

Soluţie: Adopt EOCRSSD-30DF7, set locked rotor protection (D-Time=3s, O-Time=1s)

Efect: Power cut within 3s once locked rotor occurs, 100% motor intact rate, avoid production stop losses

  1. Reguli de selecție

Quick Selection Rules

  1. Potrivire curentă: Set protection current within 0.9~1.1 times motor rated current
  2. Delay setting: Start delay (D-Time) = actual motor startup time + 1 doilea
  3. Alimentare electrică: Prioritize matching on-site control power to avoid extra transformer cost
  4. Display demand: Choose D-type for fault diagnosis, non-D-type for basic protection only
  5. Conformitatea transportului aerian & Certificari
  6. Air Freight Regulation

No built-in lithium batteries or supercapacitors, fully compliant with UN38.3 air transport standards

Can be delivered as general goods, no MSDS or special shipping documents needed

Packaging suggestion: Anti-static bag + hard carton to prevent vibration damage

  1. Qualification Certificates

CE: Comply with EU LVD & EMC directives

UL: Meet US safety standards for North America market

CSA: Certified for Canadian market

IEC: Conform to international electrical standards for global use