comprehensive protection relay Schneider Electric P243-311A2MCD28M
P243-311A2MCD28M is a comprehensive protection relay for rotating machines (motors/generators) from Schneider Electric’s MiCOM P243 series. It is a high-end digital protection device mainly used for the full protection, control and monitoring of large motors and synchronous motors.
- Interpretarea Codului Modelului (P243-311A2MCD28M)
P243: Base series, motor differential protection and integrated management relay.
3: Hardware configuration/version (corresponding to I/O, power supply and interface combination).
11: Protection function configuration (including complete motor protection such as differential, supracurent, supraîncălzire, stall, unbalance protection, etc.).
A2: Auxiliary power supply rating (typically 220–240V AC/DC or 110V DC, subject to nameplate).
M: CT input type (1O / 5O).
C: Communication interface (including Modbus RTU, optional IEC 61850, Profibus DP).
D28: I/O configuration (de ex.: 16 intrări digitale / 16 ieșiri releu).
M: RTD temperature monitoring (supports 6–10 platinum resistance thermometers for winding/bearing temperature measurement).
- Funcții de bază & Protection Features
- Main Protection
87 Motor differential protection (phase-to-phase/turn-to-turn faults)
50/51 Overcurrent/instantaneous overcurrent, 49 Stator overheating, 48 Stall/locked rotor
51N/50N Earth-fault overcurrent, 37 Underpower/overpower, 24 Speed supervision
- Measurement & Monitoring
Three-phase current, Voltaj, power, frecvenţă, power factor
RTD temperature monitoring (windings, bearings, cooling medium)
Motor operating hours, start count statistics, event recording (1000+ înregistrări)
- Comunicare & Controla
Standard: Modbus RTU
Opțional: IEC 61850, Profibus DP, DNP3.0
Programmable logic (PLC), remote switching, fault recording
- Aplicații tipice
High-voltage induction/synchronous motors (pompe de apa, fani, compresoare, rolling mills)
Protection of generators and large rotating machinery
Critical motor circuits in industry, power, metallurgy, petrochemical, municipal engineering, etc.
- Parametrii tehnici (Reference)
Operating power supply: 24-240V AC/DC (wide range)
CT input: 1A or 5A
I/O: 16 DIN / 16 DO (ieșiri releu)
RTD: 6–10 channels Pt100/Pt1000
Precizie: Current ±0.2%, Voltage ±0.5%
Ambient: -25°C ~ +70°C, front panel IP54
- Differences Within the Same Series
P241: Standard motor protection (without differential)
P242: Enhanced motor protection
P243: Top configuration with differential protection (corresponding to model P243-xxxx)