Schneider EOCRSS-60NW7PQ

Informații de bază despre produs

Marca: SAMWHA EOCR (Schneider Korea)

Tip de produs: EOCR-SS Series Knob-type Electronic Motor Protector (Replaces traditional thermal overload relays)

  1. Model Code Breakdown of EOCRSS-60NW7PQ
SegmentCodDefiniţie
EOCRSSSerieSS Economy Integrated Through-Core Motor Protector
60Evaluare curentăBuilt-in CT, adjustable rated current: 5.0~60A, compatible with 1.5~30kW three-phase motors
NModul de protecțieType N Fail-Safe: Contacts open and contactor trips upon protector power loss or fault; Type R does not trip when power fails
W7Alimentare electricăW7 = Wide Voltage AC 180~480V (Suitable for 380/400/440V industrial three-phase power grids)
PConfigurare contactP = Standard changeover contacts: 95(NC)/97(NU) (1 Deschis normal + 1 În mod normal închis)
QFuncție suplimentarăQ = Built-in Modbus-RTU RS485 communication; supports PLC/DCS remote monitoring, real-time current reading and fault code retrieval
  1. EOCR-SS Series Knob-type Electronic Motor ProtectorSpecificații tehnice de bază

3.1 Actual & Time Adjustment

Interval de curent: 5~60A (10:1 wide adjustment ratio)

D-Time (Start Stall Delay): 0.2~30s adjustable to avoid false tripping caused by high motor starting current

O-Time (Overload Trip Delay): 0.2~30s adjustable to match motor thermal characteristic curves

3.2 Funcții de protecție

  1. Supraîncărcare & Protecție la supracurent (O-Time delayed trip)
  2. Three-Phase Phase Loss Protection (Instant trip)
  3. Stall Protection (D-Time + O-Time dual delay)
  4. Three-Phase Current Unbalance Protection

3.3 Specificații electrice

Operating Power Supply: AC 180~480V (W7 wide voltage)

Output Contacts: 5A/250VAC changeover contacts (95NC, 96COM, 97NU)

Comunicare: RS485 Modbus RTU (Exclusive to Q suffix models)

Tensiune de rezistență dielectrică: 2kV for 1 minut

Consumul de energie: ≤250mA

3.4 Mediu & Instalare

Temperatura de operare: -20℃~+60℃; Temperatura de depozitare: -30℃~+80℃

Umiditate: 30%~85%RH, necondens

Montare: Standard 35mm DIN rail or screw fixing

Circuitul principal: Two through-core CTs (Pass L1 and L2 through protector windows)

  1. Front Panel Knobs & Indicators
  2. LOAD(O): Motor rated current adjustment knob (5~60A)
  3. D-TIME: Start delay (Prevent false tripping during startup)
  4. O-TIME: Overload trip delay
  5. Green PWR LED: Power supply normal
  6. Red TRIP LED: Fault tripping (Number of flashes indicates fault type)
  7. RESET: Manual reset button; TEST: Unit self-test button
  8. Key Differences of PQ Suffix (vs Standard 60NW7)
  9. Built-in RS485 Modbus communication: Remotely read real-time operating current, fault logs and protector status; receive remote reset commands from upper computer
  10. PCB of Q model integrates communication terminals, supporting multi-protector bus networking
  11. Ideal for automated production lines, pump stations, central air conditioning and centralized monitoring control rooms
  12. Scenarii tipice de aplicare

380V three-phase fans, pompe de apa, compresoare de aer, belt conveyors and mixing motors

Motors with rated current 5~60A, no external current transformer required

Control cabinets requiring PLC remote motor data collection and remote fault reset

  1. Ghid de cablare
  2. Circuitul principal: Run motor phase wires L1 and L2 through the two CT windows of the protector; L3 does not need to pass through
  3. Power Terminals A1/A2: Connect to AC380V control power supply
  4. Circuit de control: 96COM as common terminal; wire 95NC normally closed contact in series with contactor coil (Type N opens on power loss); connect 97NO normally open contact to fault alarm indicator light
  5. Comunicare RS485: A/B differential bus, daisy-chain wiring for multiple devices
  6. Matricea de depanare
Fenomen de eroareCauza de bazăSoluții
TRIP LED stays lit and cannot be resetContinuous overload / motor stallReduceți sarcina, increase set current, check mechanical jamming
TRIP LED flashes twicePhase lossInspect main circuit fuses, contactor contacts and motor wiring
Niciun răspuns după pornire, PWR LED offAbnormal power supply to A1/A2Measure 380V power supply, replace the protector
No Modbus communication dataA/B wires reversed / duplicate device addressesSwap RS485 A/B polarity, set unique address for each device
  1. Alternative Models in the Same Series
  2. Non-communication version: EOCRSS-60NW7P (Nu RS485, cost mai mic)
  3. 24–240V power supply version: EOCRSS-60NS7PQ (S7 = 24~240V AC/DC)
  4. Higher current rating: For motors over 60A, select EOCRSS-100 series with external CT