Schneider LV429413

(MN Type 125VDC Undervoltage Release)

Schneider LV429413 is an MN series undervoltage release specially designed for molded case circuit breakers of the Compact NSX, PowerPact Multistandard, and EasyPact CVS series. It has a rated voltage of 125VDC and uses screwless spring terminals. It is used for emergency stop or remote tripping control. When the control voltage drops below 35% of the rated value, it automatically trips the circuit breaker to ensure system safety.

  1. Interpretarea Codului Modelului
Segment de codSens
LVPrefix for Schneider low-voltage power distribution products
4294Product category identifier for undervoltage releases
13Specific specification code corresponding to 125VDC rating, MN type, screwless terminals
MNProduct type code: Undervoltage Release; MX denotes Shunt Trip

Caracteristici de bază: 125VDC operating voltage, suitable for 100-630A molded case circuit breakers, non-delay type, tripping threshold at 35% a tensiunii nominale.

  1. Parametrii tehnici de bază
ArticolCaietul de sarcini
Tip de produsMN Type Undervoltage Release
Tensiune nominală de control125VDC (not for AC systems)
Tripping Threshold 35% a tensiunii nominale (aproximativ. 43.75VDC)
Reset Voltage≥ 85% a tensiunii nominale (aproximativ. 106.25VDC)
Tip terminalScrewless Spring Terminal
Compatible Breaker SeriesCompact NSX 100–630A, PowerPact Multistandard, EasyPact CVS
Mounting LocationAccessory slot on front of circuit breaker
Wire Capacity1.5–2.5mm² cable
Ingress ProtectionIP20 (when installed)
Temperatura de operare-25°C ~ +70°C
GreutateAproximativ. 50g
CertificariIEC 60947-2, UL 489, CSA C22.2 No. 5
  1. Mediul de aplicare
  2. System Types

Industrial automation control systems, data center UPS systems

DC power supply systems, emergency stop circuits

Remote monitoring and tripping applications

  1. Condiții de funcționare

Control voltage fluctuation: 85%-110% of rated value for stable operation

EMC performance: Conform IEC 61000-4

Compatible frame sizes: 100O, 160O, 250O, 400O, 630O (NSX series)

  1. Cerințe de instalare

Must be installed in dedicated front accessory slot with reliable mechanical interlock

Control circuit to be protected by 1A fuse to prevent coil damage from short circuit

Observe polarity: “+” for positive, “-” for negative

  1. Cross-Reference & Replacement Models
Replacement TypeModelMarcaDescriere
Înlocuire directăLV429414Schneider220VAC version for AC control circuits
Equivalent FunctionS29413Schneider (Square D)125VDC undervoltage release for PowerPact series
Cross鈥態rand AlternativeABB TA250-125DCABB125VDC undervoltage release for Tmax MCCBs
Domestic AlternativeCHINT NXB-MN/125DCCHINTFor NXB series MCCBs
  1. Official Ordering Information
ArticolDetalii
Official ModelLV429413 (global part number)
Product NameUndervoltage Release MN, Compact NSX, 125VDC, Screwless Terminal
Order NoteMust match corresponding breaker model, de ex., NSX100N, NSX250F
PackingIndividual package including release body, manual, mounting screws
EAN Code3606480019029
MOQ1 piece
  1. Engineering Implementation
  2. Compatibility Check

Confirm breaker model: only for Compact NSX (100-630O), PowerPact Multistandard, EasyPact CVS

Verify control voltage: strictly 125VDC, not for AC or other DC voltages

Ensure front slot available for MN/MX accessories

  1. Etape de instalare
  2. Disconnect main and control power to the breaker
  3. Remove front accessory cover
  4. Insert undervoltage release into slot and engage mechanical interlock
  5. Secure with supplied screws
  6. Wire 125VDC with correct polarity
  7. Refit cover and perform functional test
  8. Commissioning

Trip test: reduce voltage below 43VDC; breaker must trip automatically

Reset test: restore voltage above 106VDC; breaker should close normally

Interlock check: breaker cannot be manually closed when release is activated until voltage recovers

  1. Lista completă de modele (MN Series Undervoltage Releases)
ModelTensiune nominalăTip terminalCompatible SeriesObservații
LV42940024VAC/DCScrew TerminalNSX/CVSStandard
LV42940148VAC/DCScrew TerminalNSX/CVSStandard
LV429402110VAC/DCScrew TerminalNSX/CVSStandard
LV429403220VAC/DCScrew TerminalNSX/CVSStandard
LV42941024VDCScrewless TerminalNSX/CVSSpring Terminal
LV42941148VDCScrewless TerminalNSX/CVSSpring Terminal
LV429412110VDCScrewless TerminalNSX/CVSSpring Terminal
LV429413125VDCScrewless TerminalNSX/CVSSpring Terminal
LV429414220VACScrewless TerminalNSX/CVSSpring Terminal
LV429415230VACScrewless TerminalNSX/CVSSpring Terminal
  1. Risks & Warnings
  2. Potrivirea tensiunii: This model is only for 125VDC control circuits. Applying AC or incorrect DC voltage will burn the coil and damage the unit.
  3. Polarity: DC polarity must be observed; reversed connection causes failure or circuit damage.
  4. Overcurrent Protection: Install 1A fast-acting fuse in control circuit to protect coil.
  5. Mechanical Interlock: Ensure reliable engagement; altfel, false tripping or failure to trip may occur.
  6. Ambient Limits: Do not use above +70°C or below -25°C to avoid performance degradation.
  7. Întreţinere: Regularly check control voltage stability (85%-110% of rated) to prevent excessive mechanical wear from frequent undervoltage tripping.