Allen-Bradley 2711-T5A2L1 Touchscreen

Rockwell Automation no longer supplies new units. Items available on the market are second-hand, refurbished or spare stock. It is a classic legacy monochrome HMI of the PanelView Standard 550 ряд. ✅ Model Breakdown 2711-T5A2L1 2711: PanelView Standard series T: Touchscreen only (no membrane keypad) 5: 5.5-inch display A: Monochrome LCD (черный & белый) 2: ...

  • Подробная информация о продукте

Роквелл Автоматизация no longer supplies new units. Items available on the market are second-hand, refurbished or spare stock. It is a classic legacy monochrome ЧМИ of the PanelView Standard 550 ряд.

✅ Разбивка модели

2711-T5A2L1

2711: PanelView Standard series

Т: Touchscreen only (no membrane keypad)

5: 5.5-inch display

А: Monochrome LCD (черный & белый)

2: DH-485 communication port, no print port

Л1: 24V DC power supply version

📋 Основные технические характеристики

ЭлементТехнические характеристики
Отображать5.5-inch monochrome LCD, resistive touchscreen
Источник питания18~30 В постоянного тока, rated 24VDC; Max 12W, 0.5A@24V
КоммуникацияDH‑485 (for connection with legacy AB SLC500, MicroLogix PLCs)
ПамятьNon-volatile memory 240KB / RAM 170KB
МонтажPanel cutout mounting, front panel IP65
Программное обеспечениеPanelBuilder32 (legacy software, 32-bit OS only)
Firmware VersionsCommon A series, прошивка 3.30/4.41 и т. д..
Рабочая температура0~55℃
Unavailable PortsNo print port, нет Ethernet

📌 Typical Applications

Legacy production line retrofits, упаковочное оборудование, обработка материалов, очистка воды, and older SLC500/MicroLogix projects. DH485 bus only, no EtherNet/IP support.

⚠️ Распространенные неисправности & Запчасти

  1. Backlight degradation: Most typical fault. Spare part 2711-NL1 (CCFL backlight tube; LED backlight modification is also feasible)
  2. Повреждена сенсорная панель: PV550 touch membrane can be replaced separately
  3. Program loss: On-board coin cell battery preserves screen programs; program loss occurs once battery fails
  4. Сбой связи: DH485 bus termination resistor, wiring polarity, RSLinx driver issues

🔁 Replacement Options for Engineering Retrofit

Original project cannot be migrated directly, screen reconfiguration is mandatory

  1. Preferred direct replacement: 2711R-T4T / 2711R-T7T (ПанельВью 800). Supports RS485 and connects to legacy PLCs;
  2. Modern alternative: ПанельВью Плюс 7 / ПанельВью 5000 series with Ethernet port;
  3. 3rd-party domestic HMI: Weintek / Kunlun MT, connecting legacy AB controllers via DH485/Modbus with lower cost.

📎 Supporting Documentation

Руководство: 2711-UM014 (PanelView Standard Terminal User Manual)

Datasheet: 2711-TD007

Ссылка на код ТН ВЭД

85287110 (Industrial touchscreen, ЧМИ, applicable for customs declaration)

2711-T5A2L1 (ПанельВью 550) Old-to-New HMI Program Migration Assessment Checklist

Применимый: Migration from legacy AB PanelView Standard 550 to PanelView 800 / ПанельВью Плюс / 3rd-party domestic HMI

Key point: PanelBuilder32 project cannot be imported into new HMI software; full reconfiguration required. This checklist is used for pre-migration risk assessment and workload estimation.

  1. Аппаратное обеспечение & Communication Assessment
Assessment ItemInspection ContentRisk Notes
Original Controller ModelSLC500 / MicroLogix 1000/1100/1200/1500?Legacy PLC only supports DH485; verify whether new HMI has native DH485, otherwise protocol converter required
Протокол связиОригинал: DH485New HMI options: DH485 / DF1 / Модбус РТУ (PLC side must support)
Address MappingOriginal PV550 tags: Н, Б, Т, С, Р, F and other PLC registers⚠️ Register addresses must be checked line by line, do not copy by experience; distinguish bits / words / floats
Коммуникационная проводкаExisting DH485 bus, termination resistors, wiring polarityNew HMI communication interface differs, evaluate rewiring and additional converter workload
Источник питания24В постоянного токаMost old & new units compatible; verify terminal definition and fuse rating
Panel Cutout Dimension2711-T5A2L1 cutout: 216 × 152mmNew HMI dimension differs; evaluate: прямая замена / adapter plate / cabinet cutout modification
Среда установкиТемпература, пыль, вибрацияVerify new HMI environmental rating and IP protection match site conditions
  1. Original HMI Project Inventory (Export from PanelBuilder32)
Assessment ItemInspection ContentПримечания
Total Screen CountMain screen, manual mode, тревога, parameter, trendCount screens to estimate configuration man-hours
Screen Element ListКнопки, индикаторы, numeric displays, input boxes, selector switchesDistinguish bit read/write, word read/write, multi-state indicators
Alarm InformationAlarm text, trigger bit, acknowledge bit, alarm log⚠️ PV550 uses simple bit-triggered alarms; new HMI alarm storage capacity varies
Recipe FunctionRecipe used or not?PV550 recipes stored locally in HMI; re-plan recipe storage location (ЧМИ / ПЛК) for new HMI
Trend CurvesReal-time / historical trend, sampling cycleLegacy PV550 only supports simple real-time trend without large-capacity history logging; evaluate history storage for new HMI
Security AccessPassword, user level, screen access permissionСтарый & new permission models differ; recreate user accounts
Macro / Script LogicPanelBuilder32 built-in macrosHigh risk: Macros cannot be migrated. All logic must be rewritten using new software scripts / функции
Screen Switch LogicScreen jump buttons, conditional jumpReplicate conditional jump logic line by line
Print FunctionThis 2711-T5A2L1 model has no print port, skip this itemEvaluate printing if other models in the series are used
Hardcopy / ScreenshotScreen capture function required?Configure on demand for new HMI

III. Tag / Variable Mapping Assessment (Core Workload Item)

  1. Export full variable list of original project (print variable table in PB32)
  2. Классификация & statistics:

Boolean (Кусочек: Бегать, Вина, Auto/Manual, Alarms)

Integer (Word: Setpoints, Счетчики)

Float (Температура, Давление)

  1. Verify PLC data file types: N files, B files, T/C preset values, registers
  2. Mark special variables:

Arrays

Indirect addressing (High risk: many new HMIs do not support legacy AB indirect addressing syntax)

Только чтение / Read-write attributes

Risk note: DH485 address notation differs between HMI software packages, prone to address offset errors.

  1. Function Equivalence Assessment (Item-by-item comparison, mark missing functions)
Original PV550 FunctionПримечания
Bit buttons, momentary / latching buttonsDistinguish momentary pushbuttons (most common error source)
Multi-state indicators (3-состояние / multi-state)
Numeric input, limit validationPV550 local limit check; new HMI can validate on HMI side or PLC side
Screen jump, conditional jumpTest conditional jump logic
Alarm trigger, alarm acknowledgeAlarm text encoding (китайский / Английский; legacy units mostly English)
Recipe read/writeVerify recipe quantity and data length
Real-time trendЦикл выборки, channel quantity
User password permissionPassword hierarchy, lock function
Macro logicDecompose macro logic and implement via PLC logic or new HMI scripts
  1. PLC Side Change Assessment

Whether PLC program modification is required to adapt new HMI communication

Whether spare PLC register space is available for new HMI functions (recipes, history logging)

Whether PLC firmware supports new protocols (например. DF1)

Downtime window assessment for PLC program download

  1. Test Plan Assessment
  2. Оффлайн моделирование: Simulate screens and variables in HMI software, verify addresses
  3. Bench test: New HMI + identical site PLC bench commissioning (recommended to reduce on-site downtime)
  4. Step-by-step on-site power-up test:

Communication connectivity test

All screen switching

Full button operation & indicator feedback

Parameter write / read verification

Alarm trigger & acknowledge test

Recipe read/write test

  1. Long-term aging test (необязательный)
  2. Rollback plan: Keep old HMI, mark wiring for fast fallback in case of failure

VII. Документация & Delivery Assessment

Backup of new HMI project source file

Variable cross-reference table (old tags ↔ new HMI variables)

Screen function specification document

Updated wiring diagram (HMI terminals, communication bus)

Updated site operation manual

Spare parts list (new HMI spare parts, модули связи)

VIII. Risk Summary & Man-hour Estimation

Fill directly into assessment form

  1. High-risk items: Macro logic, indirect addressing, address misalignment
  2. Medium-risk items: Alarm logic, recipes, communication parameter mismatch
  3. Low-risk items: Screen layout, static text

Man-hour reference:

10 basic screens without complex macros/recipes: estimated 1~2 working days for configuration + testing; projects with heavy macros, recipes, indirect addressing require double the man-hours.

  1. Downtime Plan Assessment

Planned downtime window duration

Wiring modification time

Commissioning time

Emergency plan & rollback scheme

Rockwell Allen-Bradley PanelView HMI Full Series List

Grouped by generation, marked【Active / Discontinued】, with supporting software and key features. Optimized for your 2711-T5A2L1 legacy screen retrofit selection

Catalog rule: 2711 = legacy classic; 2711R=PanelView800; 2711P=PanelView Plus; 2715=PanelView5000; 2800=OptixPanel

  1. Legacy Classic Series (All discontinued, second-hand/spare market; your 2711-T5A2L1 belongs here)

1.1 PanelView Standard (2711 ряд, monochrome / early color, PanelBuilder32 software)

ПанельВью 300: 2711-Т3А / 2711-K3A, 3-inch monochrome, DH485

ПанельВью 550: 2711-T5A2L1 / 2711-K5A2L1, 5.5-inch monochrome (твоя модель)

ПанельВью 600: 2711-T6C / 2711-K6C, 6-inch color

ПанельВью 900: 2711-T9C / 2711-K9C, 9-inch color

ПанельВью 1000: 2711-T10C / 2711-K10C, 10-inch color

Коммуникация: DH485, DF1; Нет Ethernet; Программное обеспечение для программирования: PanelBuilder32 (32-bit Windows only)

Typical faults: CCFL backlight aging, on-board coin cell causing program loss

1.2 PanelView Component (2711С, Снято с производства)

2711C-C200, miniature modular HMI, paired with Micro800 compact PLC, simple screens

1.3 Early Generation PanelView Plus (First-gen 2711P, Снято с производства)

Original PV Plus, WinCE, FactoryTalk View ME, 600/700/1000/1250/1500

  1. Previous Generation: ПанельВью Плюс 6 (2711П, EOL Discontinued, existing installed base)

Программное обеспечение: FactoryTalk View Machine Edition (FTView ME), WinCE6.0

PV Plus6 400: 2711P-T4C / K4C, 4-дюйм

PV Plus6 600: 2711P-T6C / K6C, 6.5-дюйм

PV Plus6 700: 2711P-T7C / K7C, 7-дюйм

PV Plus6 1000: 2711P-T10C / K10C, 10.4-дюйм

PV Plus6 1250: 2711P-T12C / K12C, 12.1-дюйм

PV Plus6 1500: 2711P-T15C / K15C, 15-дюйм

Suffix explanation: T=Touch; K=Membrane Keypad; C=Color; D=DC power; A=AC power

  1. Active Classic: ПанельВью Плюс 7 (2711П, Active for Sale), Стандартный / Performance versions

Программное обеспечение: FactoryTalk View ME; Performance version runs Win10 IoT Core, supports video, VNC, DLR ring

Стандартная версия: 4”,7”,10”,12”,15”

Примеры: 2711P-T4W21D8S, 2711P-T7C21D8S, 2711P-T10C21D8S, 2711P-T12W21D8S, 2711P-T15C21D8S

Performance high-performance version: 7~19” wide screen, stainless steel enclosure, conformal coated ArmorView machine-mount type

Примеры: 2711P-T7C22D9P, 2711P-T10W22D9P, 2711P-T15C22D9P, 2711P-T19C22D9P

  1. Economy Small Size: ПанельВью 800 (2711Р, Active for Sale), Preferred replacement for legacy DH485 projects

Программное обеспечение: FactoryTalk View 800 (lightweight standalone software); Ethernet + RS485/DF1 native support, perfect for SLC500/MicroLogix, recommended replacement for your 2711-T5A2L1

2711R-T4T: 4.3-inch touch

2711R-T7T: 7-inch touch

2711R-T10T: 10.4-inch touch

Touch-only models, экономически эффективный, popular for legacy line retrofit

  1. New High-End Platform PanelView 5000 (2715 ряд, Active for Sale), for Logix5000: ControlLogix/CompactLogix

Программное обеспечение: Studio5000 View Designer (integrated into Studio5000, FTView ME incompatible), native EtherNet/IP for large automation projects

  1. ПанельВью 5310 (2713П, базовый): 4”,7”,10”,12”,15”

Пример: 2713P-T10CD

  1. ПанельВью 5510 (2715П, high-performance):7/10/12/15/19”, трогать / keypad hybrid

Пример: 2715P-T7CD, 2715P-T10CD, 2715P-T15CD

⚠️Critical reminder: PV5000 project is fully incompatible with PanelView Plus projects, screen migration impossible

  1. Новое поколение: OptixPanel (2800 ряд, Rockwell new HMI, Active for Sale)

Successor to PanelView 800 линия, Compact and Standard models, FactoryTalk Optix software, native IoT & edge visualization

OptixPanel Compact (2800С): 2800С-070AS-1S (7-дюйм)

OptixPanel Standard (2800С):7/10/12/15-дюйм

Designed for new projects, weak native DH485 serial support, not recommended for direct replacement of legacy 2711 screens

  1. Mobile Handheld HMI: MobileView (2711Т)

Cabled pendant handheld operator terminal for machine-side operation, 2711T series, partial models available.

  1. Industrial Panel PC (Not pure touchscreen, industrial all-in-one PC, ASEM series)

6300П, 6300M series industrial panel PCs, ОС Windows, for local advanced SCADA operation

Series Selection Comparison Table (Quick reference for retrofit projects)

РядНомер по каталогуЖизненный циклКонфигурационное программное обеспечениеСценарии применения
PanelView Standard2711Снято с производстваPanelBuilder32Legacy spare part maintenance (2711-T5A2L1)
PanelView Plus62711ПСнято с производстваFTView MESpare parts for existing installed base
PanelView Plus72711ПАктивныйFTView MEСередина & large production lines, compatible with legacy FT projects
ПанельВью 8002711РАктивныйFTView800✅Legacy DH485 line retrofit, replace 2711-T5A2L1
PanelView50002713P/2715PАктивныйStudio5000 View DesignerLarge Logix5000 projects
OptixPanel2800АктивныйFactoryTalk OptixНовые проекты, IoT visualization

General Suffix Definition (Rapid model decoding)

T = Touch only; K = Keypad membrane; B = Touch + Keypad combined

C = Color LCD; A=Monochrome

D = 24VDC supply; A=AC100-240V

W = Wide screen; P = Performance high grade

S = Standard grade

Key Project Migration Tips (Continued from your 2711-T5A2L1 migration assessment)

  1. 2711 (PV Standard) → 2711R PanelView800: Рекомендуется, supports RS485/DF1 for SLC500/MicroLogix, умеренная стоимость; screens must be reconfigured, PB32 project cannot be imported
  2. 2711 → PanelView Plus7: Also feasible, requires DF1 / serial communication module
  3. 2711 → PanelView5000: Not recommended for legacy DH485 retrofit. Software fully different, extra gateway required for serial port, heavy engineering workload

 