Schneider Acti9 C120N 125A Miniature Circuit Breaker

The C120N belongs to the Acti9 series high-current miniature circuit breaker (MCB). It is an upgraded high-current variant of the standard C65N, with a maximum rated current of 125A and isolation function. Widely used for power distribution in industrial and building terminals, as well as outgoing circuits in power cabinets. Model Definition C120: Produktserie, ...

  • Produktdetails

The C120N belongs to the Acti9 series high-current Miniatur-Leistungsschalter (MCB). It is an upgraded high-current variant of the standard C65N, with a maximum rated current of 125A and isolation function. Widely used for power distribution in industrial and building terminals, as well as outgoing circuits in power cabinets.

  1. Modelldefinition

C120: Produktserie, high-current MCB (63~125A)

N: Schaltleistungsklasse, Icn=10kA @ 400V AC

125A: Rated working current In=125A (reference temperature: 30℃)

Full model requires additional [Polzahl + Auslösekurve]

C-Kurve: Instantaneous tripping at 5~10In, für die allgemeine Energieverteilung, lighting and resistive loads (Teile-Nr. A9N18359 / A9N18363 / A9N18369)

D-Kurve: Instantaneous tripping at 10~14In, for loads with inrush current such as motors and transformers (Teile-Nr. A9N18389)

  1. Grundlegende elektrische Spezifikationen
ArtikelParameter
Nennstrom In125A (bei 30℃)
Operating voltage UeAC 230/400V
Bemessungsisolationsspannung Ui500V
Rated short-circuit breaking capacity Icn10Die (IEC60898-1)
Bewertetes maximales Kurzschlussausschaltvermögen Icu10kA @400V (IEC60947-2)
Tripping typeC / D optional
SchutzfunktionThermal overload trip + magnetic short-circuit trip, with isolation function (green contact indicator)
Mechanische Ausdauer20,000 Operationen
Elektrische Ausdauer5,000 Operationen (range 80~125A)
Montagemethode35mm DIN-Schienenmontage
SchutzklasseIP20 (Klemmenseite)
Betriebsumgebungstemperatur-25℃ ~ +70℃
  1. Verkabelungsspezifikationen

Solid copper cable: Max. 50mm²

Flexible copper cable: Max. 35mm²

Optional aluminum terminal: For 16~50mm² aluminum cables

  1. Anwendungsszenarien
  2. High-current outgoing circuits in factory buildings, computer rooms and building distribution cabinets
  3. Main power incoming, fan and water pump circuits (D-curve recommended)
  4. Alternative to small-frame moulded case circuit breakers to save cabinet space

Optionales Zubehör: Vigi C120 residual current module, Hilfskontakt, fault alarm contact, Arbeitsstromauslöser

  1. Auswahlrichtlinien & Alternative Produkte

Auswahlnotizen

  1. Derating is required when ambient temperature exceeds 30℃;
  2. D-curve is preferred for motor loads; C-curve for general distribution;
  3. C120N with 10kA breaking capacity; select C120H (15Die) / C120L (25Die) for circuits with higher short-circuit current.

Inländische Alternativen

Chint: NM1-125 compact MCCB / NB1-125 MCB

Lecker: CDB2 125 series miniature circuit breaker

  1. Allgemeine Fehlerbehebung
  2. Fahrten sofort nach Schließung: Short circuit on downstream side, check cable insulation and load earth fault;
  3. Trips after period of loaded operation: Überlast, actual load exceeds 125A, or high ambient temperature causes derating;
  4. Kann nicht geschlossen werden, handle stuck: Damaged internal mechanism, or Vigi residual current module triggered;
  5. Green indicator does not appear: Main contacts are not fully disconnected. Maintenance on downstream circuits is prohibited.
  6. HS Code Reference

85362000 Low-voltage circuit breaker (for customs declaration reference only, subject to customs verification)

Schneider Acti9 C120N 125A Product Manual (Compiled from Original Datasheet)

Serie: Acti9 C120N High-current Miniature Circuit Breaker (MCB)

Nennstrom: 125A (reference at 30℃)

Bruchkapazität: Icn=10kA @400V AC

Reference part numbers:

2P C-curve: A9N18363

3P C-curve: A9N18369

4P C-curve: A9N18376

3P D-curve: A9N18389

The C120N is part of Schneider Acti9 high-current MCB family covering 63~125A. It features isolation function. The green contact indicator provides direct visual confirmation that main contacts are open, meeting maintenance safety requirements. It provides thermal-magnetic protection against overload and short-circuit for high-current power distribution in industrial and building distribution cabinets. Compatible with add-on accessories including Vigi C120 residual current module, Hilfskontakte, alarm contacts and shunt releases.

Standards: GB10963.1, IEC/EN60898-1, IEC/EN60947-2; CCC, CE-zertifiziert

  1. Elektrische Spezifikationen
ArtikelParameter
Nennstrom In125A (reference ambient temperature:30℃)
Rated operating voltage UeAC 230/400V; max. 440V und
Bemessungsisolationsspannung Ui500V
Bemessungsstoßspannungsfestigkeit Uimp6kV
Bewertetes maximales Kurzschlussausschaltvermögen Icu10kA @400V AC
Rated service short-circuit breaking capacity Ics75% of Icu =7.5kA
Rated short-circuit breaking capacity Icn10Die (IEC60898-1)
Tripping typeC-Kurve: 5~10In instantaneous magnetic trip; D-Kurve:10~14In instantaneous magnetic trip
Protection principleThermalreise (Überlast) + magnetischer Auslöser (Kurzschluss)
Mechanische Ausdauer20,000 Operationen
Elektrische Ausdauer5,000 Operationen (range 80~125A)
Current limiting classKlasse 3
Isolationsfunktion✅ Verfügbar, green indicator for contact open status
  1. Mechanisch & Verkabelungsspezifikationen
  2. Montage: 35mm Standard-DIN-Schiene, Snap-in-Typ, mountable in any orientation
  3. Schutzklasse: IP20 (front terminals)
  4. Verkabelungskapazität

Solid copper cable: Max.50mm²

Flexible copper cable (with cable lug): Max.35mm²

Optional aluminum terminals: For 16~50mm² aluminum cables

  1. Anzugsdrehmoment: 3.5 N·m
  2. Gesamtabmessungen (18mm pro Pol)

2P: 36mm Breite; 3P: 54mm Breite; 4P:72mm Breite

  1. Betriebsumgebung

Umgebungstemperatur: -25℃ ~ +70℃; derating required above 30℃

Lagertemperatur: -40℃ ~ +85℃

Höhe: No derating ≤2000m; Über 2000 m ist eine Leistungsreduzierung erforderlich

Relative Luftfeuchtigkeit: 5~95 %, nicht kondensierend

  1. Auslöseeigenschaften
  2. Thermal overload trip (Umkehrzeit)

1.13In: No tripping within 1h (kalter Zustand)

1.45In: Tripping within 1h

  1. Magnetic instantaneous trip

C-Kurve:5~10 Zoll, Stromverteilung, Beleuchtung, ohmsche Lasten

D-Kurve:10~14In, Motoren, Transformatoren, capacitor loads with inrush current

  1. Optionales Zubehör
  2. Vigi C120: Add-on residual current protection module, forms RCD+MCB combination
  3. OF Auxiliary contact: Circuit ON/OFF status signal
  4. SD Fault alarm contact: Tripping signal for short-circuit / Überlast
  5. MX Shunt release: Remote electrical trip
  6. MN Undervoltage release: Loss-of-voltage protection
  7. Sammelschiene: Comb-type busbar for multi-pole parallel incoming connection
  8. Installation & Betriebshinweise
  9. Derating: Derate rated current when ambient temperature >30℃. Derating also required for multiple devices installed side by side inside enclosed cabinets.
  10. Isolation verification: When handle is set to OFF position, the green indicator visible confirms main contacts are fully open before downstream maintenance. Handle position alone cannot be used as isolation confirmation.
  11. Verdrahtung: Top-in or bottom-in wiring is acceptable. Cable lugs are recommended. Tightening torque 3.5N·m to prevent overheating.
  12. Modelldifferenzierung

C120N:10Die; C120H:15Die; C120L:25Die. Select H/L version for circuits with high short-circuit current.

  1. Fehlerbehebung
  2. Fahrten sofort nach Schließung: Short circuit or earth fault on downstream side. Test breaker separately after disconnecting load to verify breaker integrity.
  3. Trips after loaded operation: Actual load exceeds rated current, or high ambient temperature causes derating.
  4. Kann nicht geschlossen werden, handle stuck: Damaged mechanism or locked residual current module.
  5. Overheating when closed: Insufficient terminal torque, Unterdimensioniertes Kabel, oxidized terminals.
  6. Model Selection Table (C120N 125A)
PoleAuslösekurveTeilenummer
2PCA9N18363
3PCA9N18369
4PCA9N18376
3PDA9N18389

Schneider Acti9 C120N 125A Overall & Montagemaße (Originaldatenblatt)

Referenz: Height H=81mm, Depth D=73mm, height and depth are consistent for all pole types; width varies with pole count

Montageschiene: 35mm standard symmetrical DIN rail, snap-in installation

PoleB × H × TDIN module (9mm/unit)Nettogewicht
1P27 × 81 × 73 mm3 Einheiten0.205 kg
2P54 × 81 × 73 mm6 Einheiten0.410 kg
3P81 × 81 × 73 mm9 Einheiten0.615 kg
4P108 × 81 × 73 mm12 Einheiten0.820 kg

Common model: 3P C120N 125A (A9N18369): 81(W) × 81(H) ×73(D) mm

Related Mounting Dimensions

  1. Abisolierlänge des Kabels: 15 mm
  2. Anzugsdrehmoment der Klemmen: 3.5 N·m
  3. Max terminal wiring: Solid wire 50mm² / Flexible wire 35mm²
  4. Cabinet clearance: ≥20mm wiring space reserved at top and bottom terminals; keep heat dissipation gap for side-by-side installation at high temperature (Derating)

Ergänzende Hinweise

Depth 73mm: Total depth from DIN rail backplate to front handle of breaker body; cabinet door cutout needs clearance allowance

Height 81mm: Overall vertical height of device body, excluding cable bending allowance

If Vigi C120 residual current module is fitted, overall depth increases, refer to separate accessory datasheet for dimension