 Schneider NT06H2 Air Circuit Breaker - Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter

Leistungsschalter/

Schneider NT06H2 Air Circuit Breaker

NT: MasterPact NT series air circuit breaker (ACB, legacy model, eingestellt; replacement model MTZ1 06H2) 06: Rahmengröße 06, frame rated current 630A H2: Breaking capacity class H2; Icu=50kA@440VAC, short-time withstand current Icw=50kA (1S), Class B selective protection Core Electrical Parameters Item Specification Frame rated current In 630A (bei 40℃) Rated operational voltage Ue AC ...

  • Produktdetails

NT: MasterPact NT series Luftleistungsschalter (ACB, legacy model, eingestellt; replacement model MTZ1 06H2)

06: Rahmengröße 06, frame rated current 630A

H2: Breaking capacity class H2; Icu=50kA@440VAC, short-time withstand current Icw=50kA (1S), Class B selective protection

Elektrische Kernparameter

ArtikelSpezifikation
Frame rated current In630A (bei 40℃)
Bemessungsbetriebsspannung UeWechselstrom 690 V, 50/60Hz
Bemessungsisolationsspannung UiWechselstrom 1000 V
Bemessungsstoßspannungsfestigkeit Uimp12kV (1.2/50μs lightning impulse)
Höchstes Kurzschlussausschaltvermögen Icu50kA@440V; 42kA@690V
Anzahl der Pole3P / 4P optional
Construction typeBehoben / Ausziehbar
AuslöseeinheitFrame supplied without trip unit, MicroLogic trip unit to be ordered separately
StandardsIEC 60947-2, with isolating function

Wichtige Anmerkungen

  1. Auslaufstatus: NT series scheduled for end-of-sale by the end of 2025. Replacement model MTZ1 06H2, part number LV947203 (draw-out version)
  2. Parameter Clarification

Ue=690V: Maximum normal operating voltage

Ui=1000V: Spannungsfestigkeit der Netzfrequenz

Uimp=12kV: Blitzimpulse halten der Spannung stand. NOT applicable for 12kV high-voltage switchgear, this is an insulation index for low-voltage ACB

  1. Anwendung: Incoming feeder, bus tie and heavy-load outgoing feeder in low-voltage distribution systems, for industrial plants, data centers and marine power distribution; supports selective protection and coordination with upstream/downstream devices
  2. Reference Frame Part Numbers

NT06H2 3P Fixed: 47113

NT06H2 3P Draw-out: 47203

NT06H2 4P Fixed: 47119

Zubehör & Ersatzteile

Trip Units: MicroLogic 2.0 / 5.0 / 6.0 / 7.0 (Überlast, kurze Zeitverzögerung, instantaneous and earth-fault protection)

Zubehör: Motor operating mechanism, Hilfskontakte, fault alarm contacts, closing coil, shunt trip coil, Türverriegelung, phase barriers

Draw-out base: Mandatory independent cradle for draw-out version

Richtlinien zur Fehlerbehebung

  1. Fehler beim Schließen: Undervoltage coil de-energized, incomplete spring charging, cradle not in connected position, interlock blocking
  2. Unintended tripping: Check trip unit protection curve, Erdschluss, harmonic distortion and temperature rise
  3. Isolationstest: Power frequency withstand test at Ui=1000V level; 12kV impulse withstand is type-test only, no on-site 12kV impulse test

Inländische alternative Referenz

Domestic MT06H2 (Schneider domestic MT series). Compatible breaking capacity and mounting dimensions for direct replacement.

Schneider MasterPact NT06H2 Air Circuit Breaker Technical Manual (Full Engineering Version, per original datasheet 0613CT0001)

Bemerkungen: NT series is legacy discontinued ACB, frame size NT06, In=630A; breaking class H2; frame supplied without trip unit, MicroLogic trip unit to be ordered separately; standard IEC 60947-2, isolating function, Class B selective protection

Inhaltsverzeichnis

  1. Produktübersicht & Erklärung des Modellcodes
  2. Bewertete elektrische Parameter
  3. Mechanische Parameter, Gesamtabmessungen & Gewicht
  4. MicroLogic Trip Unit Selection
  5. Zubehörliste & Secondary Terminal Definition
  6. Installation & Verkabelungsanforderungen
  7. Betrieb, Handling & Interlock Description
  8. Wartung, Inspektion & Fehlerbehebung
  9. Umgebungsbedingungen
  10. Replacement Model Information
  11. Original Document Index
  12. Produktübersicht & Erklärung des Modellcodes

1.1 Überblick

MasterPact NT series low-voltage air circuit breakers for incoming feeders, bus ties and high-current outgoing feeders in 400/690V low-voltage distribution systems. NT06H2 maximum frame rating 630A, available in draw-out or fixed construction, spring charged operation, configurable with intelligent MicroLogic protection unit, supports remote signalling, metering and communication.

Wichtige Erinnerung: Ui=1000V (Bemessungsisolationsspannung), Uimp=12kV (lightning impulse withstand voltage). NOT 12kV high voltage circuit breaker, only for AC ≤690V low-voltage distribution.

1.2 Modellaufschlüsselung

NT: MasterPact NT series air circuit breaker

06: Rahmengröße 06, frame rated current 630A

H2: Breaking class H2; Icu=50kA@440VAC, Icw=50kA 1s, Class B selective

Teilenummern:

NT06H2 3P Fixed: 47113

NT06H2 3P Draw-out: 47203

NT06H2 4P Fixed: 47119

1.3 Produktstatus

NT series scheduled end-of-sale by end of 2025; replacement model MTZ1 06H2, part number LV947203 (Auszug). Mounting dimensions and secondary interfaces fully compatible for direct replacement.

  1. Bewertete elektrische Parameter
ArtikelWert
Frame rated current In630A (at 40℃ ambient)
Bemessungsbetriebsspannung UeWechselstrom 50/60 Hz, max 690V
Bemessungsisolationsspannung Ui1000V
Bemessungsstoßspannungsfestigkeit Uimp12kV (1.2/50μs lightning impulse)
Höchstes Kurzschlussausschaltvermögen Icu50kA@440V; 42kA@690V
Rated short-time withstand current Icw50Die, 1S
Bewertetes Betriebsschaltvermögen Ics100% von Icu
Selectivity classKlasse B (with short-time delay selective protection)
Isolating functionComplies with IEC60947-2 isolation requirement
Anzahl der Pole3P / 4P optional
  1. Mechanische Parameter, Gesamtabmessungen & Gewicht

3.1 Mechanische Ausdauer

Mechanisches Leben: 20,000 Operationen (no-load make/break)

Elektrisches Leben (400V, In): 10,000 Operationen

Spring charging: Manual charging / motor charging MCH optional

3.2 Gesamtabmessungen (3P, Einheit: mm)

Fester Typ: W300 × H415 × D266

Ausziehbarer Typ (with cradle): W300 × H415 × D376

4P version width 360mm, height and depth unchanged

3.3 Gewicht

Fixed frame only: ≈32kg

Draw-out frame + cradle: ≈52kg

3.4 Three positions for draw-out version

  1. Verbundene Position: Main circuit and secondary circuit fully connected, normaler Betrieb
  2. Test Position: Main circuit disconnected, secondary circuit remains connected for protection test
  3. Disconnected Position: Main and secondary circuits fully disconnected, breaker can be withdrawn for maintenance
  4. MicroLogic Trip Unit Selection (Must be ordered separately, not included with frame)
AuslösermodellSchutzfunktionenTypische Anwendung
MicroLogic 2.0Long-time overload protection onlyIsolator, overload-only protection
MicroLogic 5.0ALong-time Ir, short-time delay Isd, instantaneous IiIncoming feeder, Buskrawatte (am häufigsten)
MicroLogic 6.0AAll functions of 5.0A + ErdschlussschutzCritical incoming feeder requiring earth fault protection
MicroLogic 7.0A6.0A + Fehlerstromschutz + OberwellenüberwachungRechenzentren, sensitive loads

Protection setting range: Und (lange Zeit) 0.4~1×In; Isd short-time delay 0.5~10×In, delay 0.1/0.2/0.4s; Ii instantaneous 1~15×In.

  1. Zubehörliste & Secondary Terminal Definition

5.1 Optionales Zubehör

  1. MCH: Charging motor AC220V / DC24V
  2. XF: Closing solenoid AC220V / DC24V
  3. MX: Shunt-Auslösespule (remote opening)
  4. MN: Unterspannungsauslöser (MNu time-delayed undervoltage for auto-transfer application)
  5. OF: Hilfskontakte (CB on/off status feedback)
  6. SDE: Fault trip contacts (signal for overload/short-circuit/earth fault trip)
  7. PF: Cradle position contacts (verbunden / prüfen / disconnected position)
  8. Phase barriers, Schranktürverriegelung, mechanical interlock cables, padlock device
  9. ULP communication module: Modbus-RTU, remote signalling & Dosierung

5.2 Secondary Terminal Definition

CodeNameTerminalsBeschreibung
MCHCharging motorB1, B2Auto charging upon power-up; B1-B3 charged ready CH contact
XFClosing coilA1, A2Schließbetätigung
MXRangierfahrtC1, C2Remote opening
MNUnterspannungsauslöserD1, D2Trip on loss of voltage, core component for auto-transfer
OFAuxiliary position contact11-12 NC /11-13 NEINOn/off status feedback
SDEFault trip contact81,82Protection action signal
PFCradle position contact251/252/254Draw-out position signal
  1. Installation & Verkabelungsanforderungen
  2. Montage: Vertikale, aufrechte Installation, ±5° tilt allowed; inverted mounting prohibited
  3. Hauptstromkreisanschluss: Frontanschluss / rear horizontal / rear vertical connection; apply specified tightening torque for copper busbars to avoid overheating
  4. Secondary control wiring: 0.75~1.5mm² multi-core shielded cable; independent AC220V/DC24V control power supply for secondary circuit
  5. Isolationstest: Power frequency withstand test at Ui=1000V level; 12kV impulse withstand is type test only, no on-site 12kV impulse test
  6. Draw-out operation: Use dedicated crank for rack-in / rack-out; prohibit racking out breaker from connected position under live condition
  7. Betrieb, Handling & Interlock Description

7.1 Operation Procedure

  1. Aufladen: Manual charging handle or MCH motor auto charging; charging complete, charged indicator lights on
  2. Schließen: Local front panel close pushbutton / XF remote close; verify interlock conditions before closing
  3. Öffnung: Local open pushbutton / MX remote opening / automatic protection tripping; after fault trip, fault reset button must be manually reset before re-closing

7.2 Verriegelung (Two-incoming one bus tie scheme)

Mechanische Verriegelung: Steel cable mechanical interlock, physically prevents simultaneous closing of three ACBs

Electrical interlock: Close circuit wired in series with normally closed contacts of other breakers for double protection

Cradle position interlock: Closing circuit blocked when not in connected position, closing prohibited

Fault trip interlock: Auto-transfer closing logic blocked upon SDE contact activation

  1. Wartung, Inspektion & Fehlerbehebung

8.1 Regelmäßige Wartung

Semi-annual: Check charging status, on/off indication, contact temperature rise, tightness of secondary wiring

Jährlich: Dust cleaning, insulation inspection, trip unit test (using MicroLogic test cable)

Überholung (jeder 5 Jahre): Disassemble to inspect main contacts and arc chamber, mechanical lubrication, mechanical life verification

8.2 Typische Fehlerbehebung

  1. Fehler beim Schließen

Incomplete charging; undervoltage MN coil de-energized; cradle not in connected position; interlock blocked; fault trip not reset

  1. Unintended tripping

Verify protection curve; Erdschluss; harmonic overload; loose wiring with overheating; voltage dip triggering MN undervoltage trip

  1. Ladefehler

No power supply to MCH motor; jammed charging mechanism; damaged charged-ready contact

  1. No fault signal output

Wrong SDE auxiliary contact wiring, verbrannte Kontakte

  1. Umgebungsbedingungen

Betriebsumgebungstemperatur: -5℃ ~ +70℃; Über 40℃ ist eine Leistungsreduzierung erforderlich

Lagertemperatur: -40℃ ~ +85℃

Relative Luftfeuchtigkeit: ≤95 % (nicht kondensierend)

Höhe: ≤2000m; derating and insulation correction required above 2000m

Schutzart: Device IP30; IP40 with cabinet door closed

Verschmutzungsgrad: 3

  1. Replacement Model Information

NT06H2 → MTZ1 06H2

Rahmen 630A, Icu=50kA, compatible MicroLogic trip unit

Montagemaße, primary busbar and secondary terminals fully compatible, no cabinet modification required for in-panel retrofit

Supports ECOSTRUXURE Power software commissioning, upgraded communication interface

Schneider MasterPact NT Full Series Model List (IEC Version, Discontinued ACB, Frame 630~1600A)

Benennungsregel: NT + Frame Code + Klasse brechen

Frame Code: 06=630A; 08=800A; 10=1000A; 12=1250A; 16=1600A

Klasse brechen: N1 / H1 / H2 / L1; Konstruktion: Behoben / Ausziehbar; Poles 3P/4P; Frame without trip unit, MicroLogic to be ordered separately

Common Base Parameters: Ui=1000V, Uimp=12kV, Ue max AC690V, Class B selective protection

Breaking Class Definition (440V, Icu ultimate breaking capacity)

N1: 35Die

H1: 42Die

H2: 50Die (same class as NT06H2)

L1: 130Die (strombegrenzender Typ, application for high short-circuit capacity)

NT Full Model List

RahmenFrame InKlasse brechenVollständiges ModellIcu@440VIcw(1S)Typical 3P Fixed Part No.
NT06630AN1NT06N135Die35Die47111
NT06630AH1NT06H142Die42Die47112
NT06630AH2NT06H250Die50Die47113
NT06630AL1NT06L1130Die50Die47114
NT08800AN1NT08N135Die35Die47121
NT08800AH1NT08H142Die42Die47122
NT08800AH2NT08H250Die50Die47123
NT08800AL1NT08L1130Die50Die47124
NT101000AN1NT10N135Die35Die47131
NT101000AH1NT10H142Die42Die47132
NT101000AH2NT10H250Die50Die47133
NT101000AL1NT10L1130Die50Die47134
NT121250AN1NT12N135Die35Die47141
NT121250AH1NT12H142Die42Die47142
NT121250AH2NT12H250Die50Die47143
NT121250AL1NT12L1130Die50Die47144
NT161600AN1NT16N135Die35Die47151
NT161600AH1NT16H142Die42Die47152
NT161600AH2NT16H250Die50Die47153
NT161600AL1NT16L1130Die50Die47154

Draw-out part number: add 10 to the last digit. Example NT06H2 3P Draw-out:47203; 4P fixed part number +6 (NT06H2 4P Fixed 47119)

Derivative Isolator Models (HA version)

NTxxHA: Isolator (without trip unit, IEC60947-3)

NT06HA / NT08HA / NT10HA / NT12HA / NT16HA

Compatible Trip Unit List (Universal for full NT series)

MicroLogic 2.0: Long-time overload only

MicroLogic 5.0A: Long-time + kurze Zeitverzögerung + augenblicklich (preferred for incoming / Buskrawatte)

MicroLogic 6.0A: 5.0A + Erdschlussschutz

MicroLogic 7.0A: 6.0A + Fehlerstromschutz + harmonic measurement

Replacement Cross Reference Table (NT → MTZ1)

Legacy NT ModelReplacement MTZ1 Model
NT06N1MTZ1 06N1
NT06H1MTZ1 06H1
NT06H2MTZ1 06H2
NT06L1MTZ1 06L1
NT08~NT16 follow same ruleMTZ1 08 /10 /12 /16 + Klasse brechen

Selection Remarks

  1. NT series fully discontinued, not recommended for new projects; MTZ1 can be used for spare parts replacement for existing projects with compatible primary and secondary interfaces.