Schneider BMXDDI3202KH Digital Input Module - Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter

Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-Mail: kent@bestcontactor.com

Um Kontakt |

Schneider BMXDDI3202KH Digital Input Module - Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter

SPS/

Schneider BMXDDI3202KH Digital Input Module

Serie: Modicon X80 (M340 PLC) Modellerklärung: BMXDDI3202KH = BMXDDI3202K + H; H = Conformal Coating version for harsh environments. Electrical specifications are identical to BMXDDI3202K. Only the PCB is coated with conformal coating for moisture-proof, mould-proof and salt-spray resistance, suitable for ports, chemical plants, underground sites, high-humidity and dusty conditions. ✅ Basic Specifications Type: ...

  • Produktdetails

Serie: Modicon X80 (M340 PLC)

Modellerklärung: BMXDDI3202KH = BMXDDI3202K + H; H = Conformal Coating version for harsh environments. Electrical specifications are identical to BMXDDI3202K. Only the PCB is coated with conformal coating for moisture-proof, mould-proof and salt-spray resistance, suitable for ports, chemical plants, underground sites, high-humidity and dusty conditions.

✅ Grundlegende Spezifikationen

Typ: 32-channel isolated digital Eingabemodul, Waschbecken (positive Logik)

Eingangsspannung: 24VDC, sensor supply range 19~30VDC

Input current per channel: 2.5mA @24V

Logik 1: ≥11V / ≥2mA; Logik 0: ≤5V / ≤0.5mA

Eingangsimpedanz: 9600Oh

Ansprechzeit: Typical 4ms, maximum 7ms

Isolierung: Channel-to-channel isolation, Isolationswiderstand >10MΩ at 500VDC

Verdrahtung: Kompatibel mit 2-Draht / 3-wire proximity switches (IEC61131-2 Type3, IEC60947-5-2). Input parallel connection is not allowed

Stecker: Single 40-pin FCN interface, einzelner Steckplatz, hot-swap supported

Stromverbrauch: ≤3.9W; Typical backplane 3.3V consumption 121mA

Enclosure protection: IP20

📌 Matching Cables (40-pin FCN)

  1. BMXFCWxxx3: Pre-wired loose cables (3m/5m/10m: BMXFCW303 / BMXFCW503 / BMXFCW1003)
  2. BMXFCCxxx3: Pre-assembled HE10 terminal cables (0.5/1/2/3/5/10M)

🧩 Compatible CPUs

Full Modicon M340 series: BMXP34xx00, BMXP34xx20 (including H versions). General X80 rack, configured via Unity Pro software.

⚖️ Model Comparison

BMXDDI3202K: Standardversion, no conformal coating, for conventional control cabinets

BMXDDI3202KH: Conformal coated version for harsh environments. Fully interchangeable in program, pinout and cabling.

📎 Alternative Auswahlreferenz

Same-platform replacement: No drop-in equivalent. For fewer points, refer to BMXDDI1602K(H) (16-point Sink DI).

Inländischer Ersatz: Verify sink logic, isolation and filter time, suitable for domestic PLC remote IO modules.

⚠️ Troubleshooting Tips

  1. Kein Eingangssignal: Check 24V supply, sensor polarity (Waschbecken, signal connects to 0V), broken pins in prefabricated cables.
  2. Blinkt / Fehlauslösung: Check voltage drop and shielding. This module uses fixed hardware filter; filter parameters cannot be modified by software.
  3. Prefer KH version for humid and corrosive environments; standard K version is prone to PCB corrosion under long-term high humidity.

Schneider Digitaler Eingang (AUS) Module List by Platform

Notiz: Suffix H = Conformal coating for harsh environments. X80 platform compatible with M340 / M580; Sink = sinking input, Source = sourcing input; AC = AC input.

  1. Modicon X80 (BMX series, M340 / M580)

DC-Digitaleingang (BMXDDI)

ModellPunkteBeschreibung
BMXDDI1602K / BMXDDI1602KH1624VDC, Waschbecken
BMXDDI1603K / BMXDDI1603KH1648VDC, Waschbecken
BMXDDI1604T16125VDC, Waschbecken, breite Temperatur
BMXDDI3202K / BMXDDI3202KH3224VDC, Waschbecken (the model you enquired)
BMXDDI3203K / BMXDDI3203KH3248VDC, Waschbecken
BMXDDI3232K / BMXDDI3232KH3212/24VDC, Sink/Source configurable
BMXDDI6402K / BMXDDI6402KH6424VDC, Waschbecken

AC Digital Input (BMXDAI)

ModellPunkteBeschreibung
BMXDAI08058220VAC
BMXDAI08148100~120VAC
BMXDAI16021624VAC/24VDC, Quelle
BMXDAI16031648VAC
BMXDAI160416100~120VAC
BMXDAI161416220VAC

X80 Safety DI (Safety PLC dedicated)

ModellPunkteBeschreibung
BMXSDI160216Safety digital input, 24VDC
  1. TM3-Serie (Expansion for M221/M241/M251/M262 Compact PLC)
ModellPunkteBeschreibung
TM3DI8824VDC, Schraubklemmen
TM3DI8G824VDC, spring clamp terminals
TM3DI8A8120VAC
TM3DI161624VDC, Schraubklemmen
TM3DI16G1624VDC, spring clamp terminals
TM3DI16K1624VDC, HE10 connector
TM3DI32K3224VDC, HE10 connector
  1. Advantys STB Distributed Remote IO
ModellPunkteBeschreibung
STBDDI37251624VDC Sink
STBDDI3420824VDC Sink
STBDDI3610424VDC Sink
STBDAI02002100~240VAC
STBDAI04004100~240VAC
  1. Ergänzende Hinweise
  2. X80 naming rule: `BMXDDI` = DC DI; `BMXDAI` = AC DI; `K` standard, `KH` conformal coated.
  3. K and KH variants of the same model are fully interchangeable in pinout, programming and backplane interface, only differing in PCB protection.
  4. Mixed I/O modules (DI+DO) such as BMXDDM16022 are excluded from this table.

Application Scenarios of Schneider Digital Input (AUS) Module (X80/STB/TM3, usw.)

Core function of DI modules: Collect binary switch signals, transfer ON/OFF status from external dry contacts, Sensoren, Druckknöpfe, limit switches and auxiliary contacts of contactors to PLC. It only detects on/off status and does not process analog signals. The following is sorted by industry and signal type, applicable to BMXDDI3202KH and other X80 modules.

  1. General Signal Acquisition (Used across all industries)
  2. Druckknöpfe, Wahlschalter, Not-Aus-Taster

Local cabinet operation, remote control boxes, E-stop signals (general E-stop; safety E-stop should use dedicated safety DI module BMXSDI1602).

  1. Endschalter, Reiseschalter, Näherungsschalter, fotoelektrische Sensoren

Equipment position detection: cylinder confirmation, Türschalter, baffle limit for material level, Erkennung der Anwesenheit von Objekten.

BMXDDI3202KH is 24VDC Sink, compatible with mainstream NPN proximity switches.

  1. Auxiliary contacts of contactors / Relais, circuit breaker status feedback

Motor running feedback, VFD ready feedback, circuit breaker open/close status, thermal relay fault signals.

  1. Dry contact signals

Fire alarm systems, Zugangskontrolle, damper/valve position feedback in HVAC, float level switches.

  1. HVAC

Läuft / fault feedback of fans and water pumps

Differenzdruckschalter, frost protection switches, air damper / water valve end-position feedback

Filter differential pressure alarm, high/low float level switches

Feedback of smoke exhaust dampers and fire dampers

Conformal coated KH versions (BMXDDIxxxxKH) are preferred for humid and dusty machine rooms.

  1. Wasseraufbereitung, Wasserversorgung & Drainage, Abwasseranlagen

Level switches (hohes Niveau, niedriges Niveau, overflow)

Pump run, Fehler, hand-auto status

Limit signals for bar screens and sludge scrapers

Pulse signals from flow meters (high-speed pulses require dedicated high-speed counter modules; standard DI is not suitable for high-frequency pulses)

Ventil offen / Rückmeldung der geschlossenen Position

KH coated modules are widely used in corrosive, high-humidity wastewater sites.

  1. Verpackung, Montagelinien & Automatisierte Produktionslinien

Photoelectric detection for material presence / missing material

Cylinder and clamp confirmation signals

Conveyor belt jam and deviation switches

Barcode detection, silo level switches

Safety gate and guard door status signals

BMXDDI6402K (64-point DI) is commonly used for high-point-count lines to save slots.

  1. Crane Systems, Fördern & Warehouse Logistics

Crane travel limits, upper/lower hard limits, buffer switches

Palette in Position, bay detection

Roller conveyor deviation and E-stop loop feedback

Roller shutter and guard door status

  1. Power Distribution Rooms & Energy Monitoring

Circuit breaker and disconnector open/close position feedback for high-voltage cabinets

Cabinet door interlock, earthing switch status

Transformer thermostat switches, cooling fan feedback

DC panel fault alarm dry contacts

BMXDAI AC DI modules are often used for 220VAC cabinet signals.

  1. Öl & Gas, Chemische Industrie, Häfen (Raue Umgebungen)

Valve position feedback, pump status, dry contact output of combustible gas detectors

Limit switches and door interlocks for trestle and quay equipment

Salt spray, high humidity and condensation → select KH conformal coated versions (BMXDDI3202KH etc.). Standard K versions are vulnerable to corrosion.

  1. Gebäudeautomation, Fire Protection & Pumpstationen

Dry contact alarms from fire host, sprinkler pressure switches

Elevator interlock signals, smoke exhaust fan status

Rainwater pumps, sump tank level monitoring

✅ Quick Selection Guide by Scenario

Normal indoor control cabinet, trockene Umgebung: BMXDDIxxxK

Chemisch / Hafen / hohe Luftfeuchtigkeit & Salzsprühnebel: BMXDDIxxxKH (Schutzbeschichtung)

220VAC contact signals: BMXDAI AC DI

Sicherheitsschaltungen, Sicherheitstore, safety E-stop: BMXSDI safety DI

Kleine Maschinen, low I/O count: TM3DI series

Distributed remote IO with scattered field points: STB Advantys remote DI

⚠️ Scope Limitations (What DI modules cannot do)

  1. Cannot directly measure 4-20mA or temperature (AI analog modules required)
  2. Standard DI is not suitable for high-frequency pulse counting (high-speed counter module required)
  3. Safety functions shall not be implemented via ordinary DI; dedicated safety DI modules are mandatory.