Marke: ZEITFORM (Truthahn)
Produkt: 3-Phase Digital Adjustable Overvoltage / Unterspannung & Phasenfolgeschutz Relais (Spannungsüberwachungsrelais)
- Erklärung des Modellcodes
DGK: Series of 3-phase digital voltage control relays
04: Function code → Overvoltage + Unterspannung + Phase Sequence Monitoring
F: Version mit digitaler Anzeige (enhanced model)
Sibling model: DGK-04PF with extra phase loss protection
- Schutzfunktionen
- 3-Phasenüberspannungsschutz (U>)
- 3-Phasenunterspannungsschutz (U<)
- Phasenfolge / reverse phase protection (phase sequence detection cannot be turned off on DGK-04F)
- Real-time digital display of 3-phase line voltages + fault LED indication
- Technische Spezifikationen
Stromversorgung & Messung: 3-phase AC380V, no neutral required, L1/L2/L3 only
Frequenz: 50/60Hz auto-adaptive
Undervoltage setting range: 230~360V AC
Overvoltage setting range: 400~460V AC
Fehlerverzögerungszeit: 0.1~10s adjustable
Ausgangskontakt: 1NO+1NC (SPDT), 5A / 250V AC resistive load
Montage: Standard-DIN-Schienenmontage
Betriebstemperatur: -10℃ ~ +55℃
Messgenauigkeit: ±1V
- Terminaldefinition
L1, L2, L3: 3-phase voltage input
1, 2, 3: Relay changeover contacts
Terminal 1: NC (Normalerweise geschlossen)
Terminal 2: COM (Gemeinsam)
Terminal 3: NEIN (Normalerweise geöffnet)
Standardverkabelung (Motor / Air Compressor / Wasserpumpe)
Contactor coil circuit: Wire in series with 2-3 (NEIN)
Alarm lamp / Buzzer: Verbinden mit 1-2 (NC)
Safety note: L1/L2/L3 must be from the same 3-phase power source; do not mix phases from different circuits.
- Verdrahtung & Inbetriebnahmehandbuch
Panel Buttons & Indikatoren
U: Overvoltage setting key
U< : Undervoltage setting key
T : Time delay setting key
Digitale Anzeige: Cyclically shows L1-L2 / L2-L3 / L3-L1 line voltages
AUS: Relay output indicator (Im Normalzustand EIN)
U: Overvoltage fault LED
U< : Undervoltage fault LED
PHASE: Phase sequence error LED
Power-on logic: The unit shows parameter settings for 2 seconds first, then automatically cycles through 3-phase voltage readings.
Pre-power Check (Obligatorisch)
- Perform all wiring with power disconnected; confirm no short circuit on L1/L2/L3.
- Contact load limit: Max 5A/250VAC; only interlock the control circuit, do not switch main power of large contactors directly.
- Keep away from inverters and large contactors to avoid strong electromagnetic interference.
Step-by-step Commissioning
Schritt 1: Einschalten
Switch on 3-phase supply, digital display lights up:
OUT ON: Stromspannung & phase sequence normal, relay energized, 2-3 geschlossen.
PHASE ON: Phase sequence reversed → Power off and swap any two incoming phases (L1↔L2 or L2↔L3).
U/ U< AN: Voltage exceeds threshold, protection activated.
Schritt 2: Set Undervoltage U< (Empfohlen: 340V for 380V systems)
- Short press the U< key to enter undervoltage setup.
- Press U< to increase value; press t to decrease value.
- Warten 4 seconds without operation to auto-save and return to voltage monitoring screen.
Setting range: 230~360V
Schritt 3: Set Overvoltage U(Empfohlen: 420V for 380V systems)
- Short press the Ukey to enter overvoltage setup.
- Press Uto increase value; press t to decrease value.
- Auto-save after 4 seconds idle.
Setting range: 400~460V
Schritt 4: Set Fault Time Delay t (Recommended 1~3s to avoid false tripping from momentary voltage dips)
- Short press the t key to enter delay setup.
- U= increase time; U< = reduce time.
- Settings take effect after auto-save.
Reichweite: 0.1~10s; same delay applies for fault trip AND automatic reset after voltage recovers.
Schritt 5: Phase Sequence Function Note
DGK-04F: Die Phasenfolgeerkennung kann nicht deaktiviert werden. Reverse phase will trigger protection, PHASE LED lights up, OUT turns off, and contact 2-3 öffnet sich.
If phase sequence monitoring is not required (fans without rotation direction requirement), you need to select another model. Only DGK-04PF adds phase loss protection.
Schritt 6: Functional Test
- Normaler Zustand: OUT stays ON, 2-3 geschlossen, contactor can energize.
- Simulate overvoltage: Raise supply voltage or lower the Uthreshold; ULED lights up, OUT cuts off, 2-3 öffnet sich.
- Simulate undervoltage: Lower supply voltage or raise the U< Schwelle; U< LED lights up, Relais fällt ab.
- Swap two phases: PHASE fault triggers, relay drops out.
Hysterese: Relay only restores after voltage returns within the set window (+5V tolerance) plus the programmed time delay.
Recommended Parameters (AC380V 3-phase Equipment)
Undervoltage U<: 340V
Overvoltage U>: 420V
Time delay t: 2S
Troubleshooting List
- PHASE LED always ON after power-up: Phase sequence reversed; swap any two incoming phases.
- OUT OFF with no fault indication: One phase is missing; measure line voltages on L1/L2/L3.
- Häufige Fehlauslösungen: Increase time delay t; check for grid voltage flicker or loose terminal connections.
- Flashing reading on one phase: Abnormal voltage on that phase.
- Voltage reading normal but relay will not energize: Check continuity of terminals 2-3 and the contactor control circuit.
Strenge Verbote
❌ Never connect L1/L2/L3 to the output terminals of an inverter (distorted sine wave will cause false fault alarms).
❌ Do not feed single-phase 220V power into L1/L2/L3.
❌ Do not use the relay contacts to drive high-power loads directly; only use them for control circuit interlock.
Time Delay (T) Setting for TENSE DGK-04F
Verzögerungsbereich: 0.1~10 seconds. This single setting covers both fault confirmation delay AND voltage recovery reset delay. The relay will only re-energize after the voltage returns to normal and the set time elapses.
Bedienungsschritte
- While the display is cycling through line voltages, short press the t key to enter delay setup; the digital tube shows the current time value.
- Press U= increase time value
- Press U< = decrease time value
- Stop pressing any key; wait approx. 4 seconds for auto-save, then the unit returns to voltage monitoring mode automatically.
✅ Factory recommended setting: 1~2s to filter short grid transients and prevent false tripping.
Luftkompressoren & Wasserpumpen: 2s preferred
Fast cut-off protection requirement: set to 0.5s
Key Logic
When overvoltage / Unterspannung / reverse phase occurs: Das Relais beginnt mit der Zeitmessung; contacts only open after the delay expires.
When the fault clears and voltage recovers (with +5V hysteresis): The relay waits the same t seconds before closing contacts again.
Phase sequence faults also follow this same time delay setting.
Häufige Probleme
New setting not saved: Do not press any confirm key; just wait for automatic return. Avoid long key presses.
Unwanted frequent tripping: Increase the t value.
Slow recovery after fault: Reduce the t value appropriately.
Full Model List of TENSE (Truthahn) DGK Digital Voltage Monitoring Relays
DGK series: Digital readout, adjustable over/undervoltage, DIN-Schienenmontage, no neutral required (L1/L2/L3 line voltage detection).
Suffixdefinition: F = digital display; P = phase loss protection added
| Modell | Phase | Kernfunktionen | Bemerkungen |
| DGK-01 | Einphasig | Adjustable overvoltage + Unterspannung, Digitalanzeige | AC220V single-phase monitoring |
| DGK-03 | 3-Phase | Einstellbare Über-/Unterspannung, no phase sequence check, Digitalanzeige | For loads with no rotation direction requirement |
| DGK-04 | 3-Phase | Einstellbare Über-/Unterspannung, no phase sequence, analog knob (no display) | Analog version without digital readout |
| DGK-04F | 3-Phase | Überspannung + Unterspannung + Phasenfolge, Digitalanzeige | Your current model; no phase loss protection, phase sequence check cannot be disabled |
| DGK-04PF | 3-Phase | Überspannung + Unterspannung + Phasenfolge + Phasenverlust, Digitalanzeige | Upgraded model of DGK-04F, widely used on air compressors & Kältemaschinen |
Analog Knob Series (GK-Serie, No Digital Display)
| Modell | Funktion |
| GK-03 | 3-phase over/undervoltage adjustable, no phase sequence |
| GK-04 | 3-phase over/undervoltage adjustable, no phase sequence |
| GK-04F | 3-Phase Über-/Unterspannung + Phasenfolge |
Phasenfolge / Phasenverlust / Unbalance Protection Series (FK / FKV Series, without continuous voltage adjustment window)
These models focus on phase loss, 3-phase unbalance and phase sequence; some support PTC motor temperature protection, not the DGK over/undervoltage main series.
FK-04: Phasenverlust + Phasenfolge, behoben 30% unbalance threshold
FK-05 / FK-05F: Phasenverlust + Phasenfolge, unbalance adjustable 5~25% (F = digital display)
FK-14 / FK-14P: Phasenfolge + Phasenverlust; P model with PTC motor thermal protection
FKM-05 / FKM-05F: Adjustable unbalance, Phasenfolge, Phasenverlust
FKT-06 / FKT-06PF: 3-Phasenunsymmetrie + Phasenverlust + Phasenfolge; PF with PTC input
FKV-03 / FKV-03F / FKV-03DF / FKV-03HF: Phasenverlust, Phasenfolge, Ungleichgewicht; some versions require neutral N
FKV-14 / FKV-14P: Economy phase sequence & Phasenausfallrelais; P with PTC protection
Suffix Quick Reference
F: Digital display type
P: Phase loss protection function
T: Built-in PTC motor temperature protection
DF/HF: Adjustable unbalance ratio
N: Requires neutral wire (3P+N)
Kurzanleitung zur Auswahl (Most Popular Engineering Models)
- Only over/undervoltage monitoring, no rotation check: DGK-03
- Über-/Unterspannung + anti-reverse phase (motor rotation control): DGK-04F
- Über-/Unterspannung + anti-reverse phase + Phasenausfallschutz: DGK-04PF (first choice for air compressors & Wasserkühler)
- Only phase loss & unbalance monitoring without voltage threshold adjustment: FK-05F / FKV-14
Common Specifications for All DGK 3-phase Models
Ausgabe: 1NO+1NC SPDT contact, 5A/250VAC
Time delay: 0.1~10s adjustable (shared trip & reset delay)
Spannungsbereich: Undervoltage 230~360V; Overvoltage 400~460V (for 380V line voltage systems)
Leistung & measurement input: L1/L2/L3 only, no neutral wire needed