Schneider TM2DDO8TT Output Module

Modicon TM2 Discrete Output Expansion Module, for M238 / M241 PLC, End of Life Full designation: TM2DDO8TT, 8-point 24VDC Source (PNP) transistor output module, removable screw terminal block Model Code Definition TM2: TM2 series expansion I/O (Compatible with M218 / M238 / M241) D: Digital DO: Digitaler Ausgang 8: 8 channels T: Transistor T: Quelle ...

  • Produktdetails

Modicon TM2 Discrete Output Expansion Module, for M238 / M241 PLC, Lebensende

Full designation: TM2DDO8TT, 8-point 24VDC Source (PNP) transistor output module, removable screw terminal block

  1. Modellcode-Definition

TM2: TM2 series expansion I/O (Compatible with M218 / M238 / M241)

D: Digital

TUN: Digitaler Ausgang

8: 8 Kanäle

T: Transistor

T: Source output (PNP); UT = Sink output (NPN)

  1. Wichtige elektrische Spezifikationen
ArtikelSpezifikation
Ausgabetyp24VDC PNP Source Transistor
Kanäle8 Punkte, shared 1 gemeinsames Terminal
Rated current per channel0.5A/Punkt; Max total current of common terminal: 4A
Betriebsspannungsbereich20.4 ~ 28.8 VDC
Ansprechzeit450µs (rise / fall)
SpannungsabfallMax 0.4V
Leckstrom≤0.1mA
Max inductive load10mH; Tungsten lamp load:12W
SchutzPer-channel short-circuit & Überlastschutz, Automatische Wiederherstellung
IsolierungChannel ↔ PLC internal bus: 500Vac for 1min; No isolation between channels
TerminalRemovable screw terminal block
Montage35mm DIN-Schiene
Gewicht0.085kg
AbmessungenW27.3 × H90 × D84.6 mm
  1. Kompatibilität & End-of-Life Information
  2. Kompatible CPU: Modicon M218 / M238 / M241 PLC (TM2 local expansion); Not applicable for M221/M251
  3. EOL Status: Officially discontinued by Schneider An 27 Sept 2024. No new original units available, nur Lagerbestand / second-hand modules on market.
  4. Empfohlener Ersatz: TM3DQ8T (TM3 series, 8-point Source transistor output, compatible with M221/M241/M251)

⚠️ Hinweis: TM2 and TM3 bus hardware are not interchangeable. Direct replacement requires PLC backplane / expansion architecture modification.

  1. Auswahlreferenz für die gleiche Serie

TM2DDO8TT: 8TUN, PNP Source, 0.5A, Schraubklemme (EOL)

TM2DDO8UT: 8TUN, NPN Sink, 0.3A, Schraubklemme (EOL)

  1. Anwendung & Hinweise zur Verkabelung
  2. PNP Source Output: Output terminal provides +24V; negative side of load connects to 0V. Suitable for solenoid valves, Kontrollleuchten, load connected to 0V.
  3. Für induktive Lasten (Magnetventile), freewheeling diode is recommended to protect transistors.
  4. TM2 expansion modules must be installed at the end of local expansion bus, cannot be placed before TM3 expansion modules.
  5. Onboard LED channel status indicators for commissioning and troubleshooting.
  6. Fehlerbehebung (Second-hand Module Inspection)
  7. Power on and check module power LED and bus communication LED.
  8. Test each output channel sequentially: When PLC output = ON, measure 24V at terminal; voltage drops when OFF.
  9. Short-circuit protection test: Short output to 0V, channel should cut off output automatically; output recovers once short circuit removed.
  10. Measure off-state leakage current to judge transistor aging.
  11. Inspect removable terminals for burn marks and deformed copper contacts.
  12. HS Code Reference

8537101100 (Programmable Controller I/O Expansion Module)

Replacement Options for TM2DDO8TT (8-point 24VDC PNP Source, TM2 Bus)

Original module: TM2DDO8TT, TM2 bus, only for M218/M238/M241, EOL; TM2 bus and TM3 bus hardware cannot be swapped directly. 3 categories for selection:

Fall 1: Keep existing M218/M238/M241 CPU, only replace expansion module

TM3 modules cannot be used. Although M241 supports both TM2+TM3 bus, TM2 modules must be installed after TM3 modules. Mixed installation is not recommended for long-term engineering use. If you need direct plug-in on TM2 expansion bus: only surplus / used TM2DDO8TT available. Schneider has no new equivalent module on TM2 bus.

Alternative spare within same EOL series: No other TM2 8-point Source DO. Only TM2DDO8UT (NPN Sink) verfügbar, cannot directly swap, opposite output logic.

Fall 2: Full PLC Upgrade (Recommended for new project / major overhaul, official replacement: TM3 series)

✅ TM3DQ8T [Top-Empfehlung]

Spez: 8-point 24VDC PNP Source transistor, 0.5A pro Kanal, removable screw terminal

Compare with TM2DDO8TT: Same channel count, output type and per-channel current; Bus type is TM3, not TM2

Kompatible CPU: M221 / M241 / M251 / M262

Modification effort:

  1. Original M241: TM3 expansion bus supported, but IO address must be reconfigured in EcoStruxure Machine Expert, IO mapping modification required in program.
  2. Original M218/M238: Does not support TM3 modules, CPU must be upgraded to M241/M251 together.

Other TM3 Alternatives (Same TM3 Bus)

  1. TM3DQ8TG: 8-point PNP Source, Federklemme, electrical parameters same as TM3DQ8T, only wiring terminal difference
  2. TM3DQ16T: 16-point PNP Source, 0.5A; spare IO channels, suitable for projects with IO reservation

Fall3: Distributed Remote IO Replacement (Keep original CPU, no local bus modification, ideal for legacy retrofit)

Advantys OTB remote IO, communicate via Modbus RTU to original PLC, independent IO station, does not occupy TM2 local expansion port

  1. OTB1C08T: 8-point 24V PNP Source transistor output, Modbus RTU, Schraubklemme

Pros: No modification to original local expansion bus, only add Modbus read/write logic, independent installation inside cabinet. Suitable for limited cabinet space, no change to existing expansion chain.

Cons: Modbus communication program required, response speed slightly slower than local expansion module.

Fall4: Domestic Compatible Replacement (Cost-saving option, Modbus Remote IO)

Domestic Modbus RTU remote 8-channel PNP transistor output modules (Innovation, Xinje, Lansen etc.), functionally equivalent, connect to M218/M238/M241 via Modbus. For projects with tight budget.

Selection Comparison Table

ErsatzmodellAusgabetypCurrent per ChannelBustypKompatible SPSModification Workload
TM2DDO8TT (Original)PNP Source0.5ATM2 Local BusM218/M238/M241EOL, nur Lagerbestand / gebraucht
TM3DQ8T (Offiziell empfohlen)PNP Source0.5ATM3 Local BusM241/M251/M221/M262★★★☆ Reconfigure IO address & PLC program
OTB1C08TPNP Source0.5AModbus RTU Remote IOM218/M238/M241 (No CPU change)★★☆ Add Modbus communication program

⚠️ Critical Retrofit Notes

  1. TM2 bus and TM3 bus have different hardware connectors, cannot hot-swap directly. When mixing TM2+TM3 on M241, TM2 modules must be placed after TM3 modules; long-term mixed configuration is not recommended in engineering.
  2. TM2DDO8TT is PNP Source. Never select NPN Sink model (TM3DQ8U / TM2DDO8UT), opposite output logic, load will not operate after wiring.
  3. TM3DQ8T has different common terminal and pin assignment from TM2DDO8TT, field secondary wiring cannot reuse the original terminal plug directly; Neuverkabelung erforderlich.

Schneider TM3DQ8T (Common miswriting: TM3DO8T)

Modicon TM3 discrete expansion output module, 8-point 24VDC PNP Source transistor output, removable screw terminal, official recommended replacement for TM2DDO8TT

  1. Modellcode-Definition

TM3: TM3 series local expansion I/O module

DQ: Discrete Output

8: 8 Kanäle

T: Transistor PNP Source output (Schraubklemme)

TM3DQ8TG = identical electrical parameters, spring cage terminal version

  1. Grundlegende elektrische Spezifikationen
ArtikelSpezifikation
Ausgabetyp24VDC PNP Source (positive Logik) Transistor
Kanalmenge8 Punkte, shared one common terminal
Rated current per channel0.5A/channel
Max total current of common terminal4A (Total limit for 8 Kanäle)
Output supply voltage20.4 ~ 28.8 VDC (nominal 24 VDC)
Spannungsabfall≤0.4V
Leckstrom im ausgeschalteten Zustand≤0.1mA
AnsprechzeitMax 450µs (rise / fall)
Maximale Schaltfrequenz (ohmsche Last)100Hz
Max incandescent lamp load12W
Induktive LastExternal freewheeling diode recommended; typical clamping voltage 50VDC
KurzschlussschutzPer-channel independent short-circuit / Überlastschutz; auto-recovery after fault removal
Isolation ratingModule bus ↔ output channel: 500Vac, 1min withstand; No isolation between channels
Bus power supply5V supplied by TM3 expansion bus; 24V for output loop must be wired separately
5V bus consumptionAUS:5mA; AN:10mA; 24V field circuit: OFF=0mA, ON max 20mA
  1. Mechanisch & Umweltspezifikationen
ArtikelSpezifikation
Montage35mm DIN rail TH35-7.5 / TH35-15, or panel screw mounting
GesamtdimensionW27.4 × H90 × D84.6 mm
NettogewichtCa. 0.076kg
SchutzklasseIP20 (Nur für den Schrankeinbau)
TerminalRemovable screw terminal block, 5.08mm pitch; Draht:0.2~2,5mm² (24~14AWG)
BetriebstemperaturHorizontale Montage: -10 ~ +55℃; Vertikale Montage: -10 ~ +35℃
Lagertemperatur-25 ~ +70℃
Relative Luftfeuchtigkeit10~95 %, nicht kondensierend
Max working altitude2000M
Verschmutzungsgrad2
Vibrationsfestigkeit5~8.4Hz:3.5mm; 8.4~150Hz:3G
Stoßfestigkeit15G,11MS
Anzeige-LED1 green LED per channel to display ON/OFF state
ZertifizierungenCE, cULus, UKCA, RCM, CCC
  1. PLC Compatibility

Works with Modicon M221 / M241 / M251 / M262

❗ M218, M238 do NOT support TM3 modules, cannot extend TM3DQ8T directly.

  1. Comparison vs Original TM2DDO8TT (Schlüssel)
ParameterTM2DDO8TTTM3DQ8T
AusgabePNP Source 0.5A, 8-point common terminalPNP Source 0.5A, 8-point common terminal
Max total common current4A4A
Ansprechzeit450碌s450碌s
Withstand isolation500Vac500Vac
BusTM2 Bus (M218/M238/M241)TM3 Bus (M221/M241/M251/M262)
AbmessungenW27.3 脳 H90 脳 D84.6mmW27.4 脳 H90 脳 D84.6mm
TerminallayoutDifferent pin assignment, secondary wiring cannot reuse terminal plug directlyDifferent pin assignment, secondary wiring cannot reuse terminal plug directly
  1. Hinweise zur Verkabelung
  2. PNP Source: Output terminal provides +24V, load other end connects to 0V; suitable for solenoid valves and indicator lamps.
  3. 8 channels share one common power terminal, external +24V connects to common terminal.
  4. Für induktive Lasten (Magnetventile), freewheeling diode must be paralleled to absorb back EMF and protect transistors.
  5. Module 5V bus power supplied by PLC backplane; 24V power for output circuit must be external.
  6. Fault Detection (Bench Test)
  7. Power on: Check module bus LED and channel LED status.
  8. Activate each point sequentially: 24V measured at terminal when ON; voltage drops at OFF state.
  9. Short-circuit test: Short output to 0V, module triggers protection, output restores automatically after short removed.
  10. Measure off-state leakage current to evaluate transistor aging.
  11. HS Code Reference

8537101100 (PLC discrete I/O expansion module)

  1. Alternatives within TM3 family

TM3DQ8TG: Same specs, spring cage terminal

TM3DQ8U: 8-point NPN Sink output, opposite logic, do not select by mistake