Vollständiger Produktname: SITOP PSU100S 24V DC /5A Regulated Stromversorgung
Order Code Definition:
6EP = SITOP power supply family; 1333=24V 5A; 2BA20=PSU100S version, No Ex explosion-proof certification
✅ Grundlegende elektrische Spezifikationen
Eingang
Stromversorgung: Single-phase AC 120/230V, 50/60Hz
Spannungsbereich: AC 85–132V (120V range) / 170–264V (230V range), Not full wide automatic range
Nenneingangsstrom: 1.3A at 230V; 2.1A at 120V
Built-in input fuse; Recommended circuit breaker: B10A / C6A
Wartezeit: ≥20ms at rated load
Ausgabe
Bewertet: DC24V, 5A, 120W
Output adjustable range: 22.8 ~ 28V (via potentiometer on housing)
Static accuracy: ±3 %; Maximum ripple 150mV peak-to-peak
Überlastfähigkeit: 150% Nennstrom für 5 seconds per minute; Continuous operation at 120% laden
Statusanzeige: Grüne LED (24V OK) + Normally-open relay alarm contact (closed when power healthy)
📐 Mechanisch & Umweltfreundlich
Montage: DIN-35-mm-Schienenmontage, natural air cooling
Gewicht: 0.4kg
Betriebstemperatur: -10 ~ +70℃; Derating starts above 60℃ (3%/K); Upper limit drops to 50℃ if output >24V
Lagertemperatur: -25 ~ +85℃; Humidity class EN60721 3K3
Ursprungsland: Österreich; HS-Code: 85044083
🧩 Funktionen
- Isolated industrial switching power supply, standard 24V power source for PLC, sensors and valve islands
- Relay signal contact, can be connected to PLC for power fault diagnosis
- Parallel connection for current expansion (Max ambient temperature derate by 10℃ when paralleled)
- Schutzmaßnahmen: Überstrom, Überspannung, Übertemperaturschutz
- Zertifizierungen: UL508, CE, RoHS; This model no longer supports Ex certification
⚠️ Alternative Selections
Smaller model in same series: 6EP1332-2BA20 (24V/2,5A)
Larger model in same series: 6EP1334-2BA20 (24V/10A)
Referenz zu inländischen Alternativen: Meanwell DR-120-24, Phoenix QUINT-PS/1AC/24DC/5
🛠️ Häufige Fehlerbehebung
- No green LED: Check AC input voltage, Interne Sicherung durchgebrannt; Output short-circuit protection latch, zum Zurücksetzen aus- und wieder einschalten
- Spannungsabfall unter Last: Niedrige Eingangsspannung, overtemperature derating, continuous load exceeding 120% Bewertung
- Alarmrelais nicht geschlossen: Netzteil im Schutzzustand oder Ausgangsspannung zu niedrig
Anwendungsszenarien für 6EP1333-2BA20 (SITOP PSU100S 24V/5A)
Kernpositionierung: Einphasige AC- bis 24-VDC-SELV-Steuerstromversorgung in kleinen Schaltschränken, zur Stromversorgung der SPS, I/O-Module, Sensoren, Ventile, HMI und andere Industriekomponenten. Ausgestattet mit einem Power-Good-Relais-Alarmkontakt, Geeignet für den Stand-Alone-Betrieb / Kleinstationsautomatisierung, DIN-Schienenmontage.
- Maschinenbau / Eigenständige Automatisierung (Am häufigsten)
- Verpackungsmaschinen: Vertikale Verpackungsmaschinen, Etikettierer, Kofferpacker, Schrumpfmaschinen. Netzteil für S7-1200/1500, fotoelektrische Sensoren, Näherungssensoren, Magnetventile, Sicherheitsrelais und Touchscreens; 5Eine Kapazität entspricht den E/A-Schleifen mittelgroßer bis kleiner Standalone-Maschinen.
- Fördern & Sortierausrüstung: Kleine Förderbänder, Rollenlinien, Transfermaschinen. I/O-Module versorgen, Encoder, fotoelektrische Sensoren, pneumatische Ventilinseln; Unterstützt parallele Erweiterung.
- Spritzguss / Stanzhilfsgeräte: Manipulator-Schaltschrank, Materialzuführer, Schrank für Formentemperaturregler; Widerstehen Sie Netzschwankungen, geeignet für Lasten mit Anlaufstoßstrom.
- Hilfssteuerkasten für Werkzeugmaschinen: Kleine Spezialmaschinen, Schaltschrank für Vorrichtungen, Strom für Sensoren, Kontrollleuchten und Sicherheitsschaltungen.
- Prozessautomatisierung (Wasseraufbereitung, HVAC, Kommunal)
- Wasseraufbereitung: Kleine Wasseraufbereitungsgeräte, chemisches dosiersystem, Schaltschrank für die Wiederverwendung von aufbereitetem Wasser. SPS + analoge Sender, Niveauschalter, Magnetventile; Der Relaisalarmkontakt stellt eine Verbindung zur SPS her, um einen Fernalarm bei Stromausfall zu ermöglichen.
- HVAC: Bau von Lüftungsanlagen, Frischlufteinheiten, Schaltschrank für Abluftventilator; Power-DDC, Differenzdrucksensoren, elektrische Aktuatoren.
- Kommunale Kleinpumpstationen, Abwasserüberwachungsstationen: Feldsteuerkasten, Sensorerfassung + Fernkommunikationsmodul.
Notiz: Dieses Modell ohne Ex-Zertifizierung; Bei Verwendung in explosionsgefährdeten Bereichen, Das Netzteilgehäuse muss in einem explosionsgeschützten Schrank mit Schutzart IP54 oder höher installiert werden.
- Logistik, Lagerung, Hilfsstationen automatisierter Produktionslinien
Kleiner Arbeitsplatz-Schaltschrank aus Mini-AS/RS, AGV-Bodenstation, Scan-Inspektionsstation; Versorgen Sie die Remote-E/A des ET200SP mit Strom, fotoelektrische Sensoren, RFID-Lesegeräte, Kontrollleuchten.
Montagestationen für Automobilkomponenten, Prüfvorrichtungsschränke, eigenständige Prüfstände.
- Andere Branchen
- Essen & pharmazeutisch: Small filling and inspection equipment control cabinet; CE/UL compliant, suitable for standalone control in clean rooms.
- Laboratory test equipment, non-standard automatic test benches.
- PV / energy storage auxiliary control cabinet: Local signal acquisition cabinet (only for control circuit, not power circuit).
✅ Typical Load Combination Reference (5A Capacity)
S7-1200 CPU + 8~16 DI/DO points + HMI + several proximity/photoelectric sensors + 2~4 pcs 24V solenoid valves + Sicherheitsrelais.
Vorsicht: Solenoid valve has high inrush current, Reservemarge bei der Auswahl; High-power valves require separate power loop.
⚠️ Nicht empfohlene Anwendungen
- High-power 24V motors, heavy heating loads (This is control power supply, not power supply for high power loads)
- 3-phase input system (unless single-phase power is tapped from front end)
- Heavy corrosion environment, direct outdoor exposure (muss im Schaltschrank eingebaut werden)
- Direkte Installation im explosionsgefährdeten Bereich
- Hauptstromversorgung für große Anlagen (10A+-Modell oder redundantes Schema empfohlen)
✅ Wichtige Auswahlpunkte
Vorteile: Power-Good-Relaisausgang, 150% Kurzzeitüberlastfähigkeit, kompakte DIN-Schienenmontage, Selbstsicherheitsisolierung, Ideal für kleine Schaltschränke, die eine Überwachung des Stromstatus erfordern.
Kapazitätserweiterung: Mehrere Einheiten parallel geschaltet, um den Gesamtausgangsstrom zu erhöhen; Bei Parallelschaltung die maximale Umgebungstemperatur reduzieren.
Vollständige Modellliste der SITOP PSU100S-Serie (Einphasiger AC-Eingang, DIN-Schienen-Netzteil)
Alle Modelle: Eingang AC 120/230 V (85–132V /170–264V), Ausgestattet mit Power-Good-Relais-Alarmkontakt, natürliche Kühlung, DIN35-Schienenmontage.
24V DC-Ausgangsserie (Am häufigsten, Unterserie Ihres Modells)
| Bestell-Nr. | Spezifikation | Leistung |
| 6EP1332-2BA20 | DC24V / 2.5A | 60W |
| 6EP1333-2BA20 | DC24V / 5A | 120W |
| 6EP1334-2BA20 | DC24V / 10A | 240W |
| 6EP1336-2BA10 | DC24V / 20A | 480W |
12V DC-Ausgangsserie
| Bestell-Nr. | Spezifikation | Leistung |
| 6EP1322-2BA00 | DC12V / 7A | 84W |
| 6EP1323-2BA00 | DC12V /14A | 168W |
Abgeleitete SIPLUS Wide-Temperature-Version mit Beschichtung (Optional, kein Standard-PSU100S)
6AG1334-2BA20-4AA0: SIPLUS PS PSU100S 24V/10A, Schutzbeschichtung, Betriebstemperatur -25 ~ +70℃, for high humidity and corrosive environments (Eisenbahn, outdoor cabinet)
✅ Common Features of Series
- Relay alarm output (Power-good dry contact for PLC diagnosis)
- Kurzzeitige Überlastung: 150% laden für 5 Sekunden, handles solenoid valve impulse current
- Schutz: Überstrom, Überspannung, Übertemperaturschutz
- Multiple units can be paralleled to increase output current (Derate ambient temperature upper limit)
- Zertifizierungen: CE, UL508, RoHS; No Ex explosion-proof certification
⚠️ Distinction Reminder
PSU100S ≠ SITOP smart / PSU100C / PSU6200, nicht verwechseln:
PSU100S: With relay alarm contact, Liste oben;
SITOP smart: Without relay alarm, geringere Kosten;
PSU6200: Neue Generation, with communication diagnosis function.
Input Voltage Specifications of 6EP1333-2BA20
Single-phase AC, Automatic dual-range switching, not continuous 85~264V full wide range
Reichweite 1 (120V range): AC 85V ~ 132V
Reichweite 2 (230V range): AC 170V ~ 264V
Rated input: AC 120V / 230V
Input frequency: 47~63Hz (50/60Hz-kompatibel)
Wichtige Hinweise
- Voltage gap: Cannot operate stably when AC voltage between 132V ~170V. Power supply will not work reliably if grid voltage falls within this gap, must pay attention during selection.
- Power supply automatically identifies voltage range internally, no manual DIP switch required.
- Wartezeit: ≥20ms at rated load and rated input voltage.
- In domestic 3-phase cabinet, single-phase 220V tapped (170~264V range), falls into 230V range and works properly.
Housing Dimensions of 6EP1333-2BA20 (B × H × T)
50 mm × 125 mm × 120 mm
Breite (DIN rail direction): 50 mm
Höhe (Vertikale): 125 mm
Tiefe (into cabinet): 120 mm
Installation Clearance (Anforderung an die Wärmeableitung, critical for cabinet layout)
Top clearance: 50 mm
Bottom clearance: 50 mm
Links & Rechts: 0 mm, can be mounted side-by-side with other modules
Mount on EN 60715 standard 35mm DIN rail, wall mounting not supported.
Gewicht
Nettogewicht: Ca. 0.4 kg
Dimension comparison of PSU100S series (für die Schrankaufteilung)
| Bestell-Nr. | W×H×D mm |
| 6EP1332-2BA20 | 32.5 × 125 × 120 |
| 6EP1333-2BA20 | 50 × 125 × 120 |
| 6EP1334-2BA20 | 70 × 125 × 120 |
| 6EP1336-2BA10 | 115 × 145 × 150 |
Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter



















NH42-63-318x560.png)