ABB CC-U-STDR-1SVR040010R0000 - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

chatear: +86-13184948252 Whatsapp: 0086-13811255435 Correo electrónico: kent@bestcontactor.com

Acerca de Contacto |

ABB CC-U-STDR-1SVR040010R0000 - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

eléctrico/

ABB CC-U-STDR-1SVR040010R0000

Model Code Explanation Model Segment Description CC Series code for analog signal converters (Conversion Controller) U Universal type, compatible with conversion of various standard signals STD Standard signal input. Supports 0-20mA/4-20mA/0-1V/1-5V/0-10V/±10V, etc.. R Equipped with relay output, differentiated from STD models without relay output 1SVR040010R0000 Official order number, unique identification code ABB Brand logo ABB ...

  • Detalles del producto

Explicación del código del modelo

Segmento de modeloDescripción
CCSeries code for analog signal converters (Conversion Controller)
Ud.Universal type, compatible with conversion of various standard signals
STDStandard signal input. Supports 0-20mA/4-20mA/0-1V/1-5V/0-10V/±10V, etc..
REquipped with relay output, differentiated from STD models without relay output
1SVR040010R0000Official order number, unique identification code
TEJIDOBrand logo

ABB CC-U-STDR-1SVR040010R0000-ABB Technical Manual The CC-U/STDR is a universal analog signal converter of ABB CC series. It features 2-channel threshold relay outputs and triple electrical isolation, designed for industrial signal conversion and control.

  1. Especificaciones técnicas principales
CategoríaPresupuesto
Información general• Product Type: Universal Signal Converter (with relay output)
• Status: Interrumpido, no direct replacement model
• Origin: Alemania
• Peso: 0.142kilos
Fuente de alimentación• Rated Voltage: 24-48VCC / 24VCA 50/60 Hz
• Power Consumption: ≤5W
Input Signal 7 standard signal ranges: 0-20mA/4-20mA/0-1V/1-5V/0-10V/±10V
• Input Impedance: ≤250Ω for current input; ≥1MΩ for voltage input
Señal de salida• 2-channel SPDT relay contacts
• Independently adjustable threshold and hysteresis for each channel
• Contact Rating: AC 250V/5A, DC 30V/5A
Exactitud & Actuación• Repeat Accuracy: ±0,5 % escala completa (Full Scale)
• Response Time: 10EM
• Temperature Drift: ≤0.05%/°C
Aislamiento eléctrico• Triple isolation: Isolation between input, output and power supply
• Isolation Voltage: ≥2.5kV
Parámetros ambientales• Operating Temperature: -20°C ~ +60°C (Temperatura de almacenamiento: -40°C ~ +80°C)
• Protection Class: IP20 (Front panel)
• Mounting: 35mm montaje en carril DIN
Dimensiones• L × W × H: 120mm × 22.5mm × 105mm
• Mounting Depth: 120milímetros
  1. Full Model List (CC-U Series)
ModeloNúmero de pedido.Tipo de entradaTipo de salidaFuente de alimentaciónObservaciones
CC-U/STD1SVR040000R1700Standard SignalAnalog Signal24-48VDC/24VACtipo básico, no relay output
CC-U/STD1SVR040001R0400Standard SignalAnalog Signal110-240VAC/100-300VDCHigh voltage power supply type
CC-U/STDR1SVR040010R0000Standard Signal2-channel Relay24-48VDC/24VACThis model with relay output
CC-U/STDR1SVR040011R2500Standard Signal2-channel Relay110-240VAC/100-300VDCHigh voltage power supply type
CC-U/RTD1SVR040002R0000RTD Temperature SensorAnalog Signal24-48VDC/24VACRTD input type
CC-U/RTDR1SVR040003R0000RTD Temperature Sensor2-channel Relay24-48VDC/24VACRTD input + salida de relé
CC-U/TC1SVR040005R0000ThermocoupleAnalog Signal110-240VAC/100-300VDCThermocouple input type
CC-U/TC1SVR040006R0000ThermocoupleAnalog Signal24-48VDC/24VACThermocouple input type
CC-U/I1SVR040007R0000Current SignalAnalog Signal24-48VDC/24VACCurrent signal conversion type
CC-U/V1SVR040008R0000Voltage SignalAnalog Signal24-48VDC/24VACVoltage signal conversion type
  1. Cross-Model & Referencia de reemplazo

4.1 Replacement for Discontinued Products

Modelo OriginalEstadoRecomendación de reemplazoReason for Replacement
CC-U/STDR-1SVR040010R0000Interrumpido, no direct equivalent1. Upgrade to new ABB model: TTH300 Series• TTH300: New-generation ABB signal converter with enhanced functions
2. Third-party replacement: Phoenix Contact MACX MCR-UI-UI-NC• MACX MCR: Standard industrial replacement with wide compatibility
3. Functional replacement: WAGO 750-455• WAGO 750: Modular design with strong expandability

4.2 Compatibilidad entre marcas

ABB ModelContacto FénixWAGOsiemensFunction Comparison
CC-U/STDRMACX MCR-UI-REL-NC750-4553RK1300• Support standard signal input
• 2-channel relay output
• Triple electrical isolation
• Response time ≤10ms
  1. Entornos de aplicación & Casos de la industria

5.1 Escenarios aplicables

Automatización Industrial: Monitoring and control of analog signals on production lines, including conversion of pressure, temperature and flow signals

Control de procesos: Standard signal processing for chemical, pharmaceutical and food industries

Gestión Energética: Conversion of sensor signals in power systems for equipment monitoring and control

Automatización de edificios: Signal processing for HVAC systems to ensure reliable signal management

Tratamiento de agua: Conversion of liquid level and flow signals for pump control and alarm systems

Metalurgia: Signal isolation and conversion in high-temperature environments to eliminate interference

5.2 Non-Recommended Scenarios

Intrinsically Safe Areas: No explosion-proof certification, not suitable for Zone 0/Zone 1 hazardous locations

High-Speed Signal Processing: 10ms response time, not applicable for microsecond-level control

Outdoor Installation: Clase de protección IP20, additional protective measures are required for outdoor use

5.3 Casos de aplicación típicos

Caso 1: Temperature Control of Chemical Reactor

Solicitud: Convert millivolt thermocouple signals to standard 4-20mA signals; set dual thresholds for high temperature alarm (85°C) and over-temperature shutdown (95°C)

Configuración: CC-U/STDR + Type K thermocouple adapter, 24Fuente de alimentación VCC

Ventajas: Triple isolation eliminates ground loop interference; dual relay outputs realize hierarchical control and improve operational safety

Caso 2: Pressure Monitoring for Building HVAC System

Solicitud: Convert 0-10V signals from pressure sensors to standard 4-20mA signals; set low pressure alarm (0.5bar) and high pressure alarm (3bar)

Configuración: CC-U/STDR, 24fuente de alimentación VCA

Ventajas: Standardized signals facilitate centralized PLC monitoring; relay outputs directly control fan start/stop and reduce system costs

  1. Consejos de selección & Quick Reference Rules

Selection Rhythm

The CC series includes U (Universal) y E (Economía);

STD for standard signals, R for relay output, check power supply carefully;

24/48V for low voltage, 110/240V for high voltage;

Triple isolation against interference, 10-millisecond response;

This series is discontinued, plan upgrade in advance.

Quick Reference Rules

  1. Identificación del modelo: CC-U/STDR = Universal type + Standard signal + Salida de relé
  2. Order Number Distinction: 1SVR040010R0000 = 24-48V power supply; 1SVR040011R2500 = 110-240V power supply
  3. Ventajas principales: Triple isolation, independently adjustable dual relays, 7 selectable input signals
  4. Status Reminder: All legacy CC-U series products are discontinued. Select ABB TTH300 series or third-party alternatives for new projects.
  5. Solución de problemas & Mantenimiento
Fenómeno de fallaPosibles causasSoluciones
Sin señal de salida1. Power supply disconnected or abnormal voltage1. Check 24-48VDC/24VAC power supply
2. Incorrect DIP switch settings2. Reconfigure DIP switches (input type, output mode)
3. Input signal out of range3. Measure input signal and ensure it is within 0-20mA/0-10V range
Relay Fails to Actuate1. Threshold set too high/low1. Readjust threshold potentiometer
2. Excessively large hysteresis value2. Reduce hysteresis value
3. Damaged relay contacts3. Measure contact resistance; replace unit if contacts are damaged
Fluctuating Output Signal1. Interference on input signal1. Check shield wiring and add filter
2. Ondulación excesiva de la fuente de alimentación2. Connect a 100渭F capacitor in parallel to power terminals
3. Poor contact of potentiometer3. Clean or replace the potentiometer
Loss of Isolation1. Wrong wiring across isolation zones1. Rewire strictly to separate input, output and power circuits
2. Equipment aging2. Replace with new device (select replacement model due to discontinuation)