The Schneider GV3P50 motor circuit breaker is an ideal choice for protecting 22kW three-phase motors. Featuring thermal-magnetic tripping, an adjustable current range of 37–50A, a breaking capacity of 100kA and IP20 ingress protection rating, it is widely deployed in industrial automation, fluid conveyance, building facilities and other sectors. Key points: match breaker rating to motor ...

  • Detalles del producto

The Schneider GV3P50 motor circuit breaker is an ideal choice for protecting 22kW three-phase motors. Featuring thermal-magnetic tripping, an adjustable current range of 37–50A, a breaking capacity of 100kA and IP20 ingress protection rating, it is widely deployed in industrial automation, fluid conveyance, building facilities and other sectors. Key points: match breaker rating to motor power and operating conditions; avoid non-recommended applications including DC circuits, high-frequency starting and high-altitude environments. Combined with contactors and auxiliary contacts, it forms a complete motor protection and control system.

Segmento de códigoDefiniciónDescripción detallada
GV3Serie de productosTeSys GV3 range motor circuit breakers for three-phase motor protection
PAGTipo de productoStandard thermal-magnetic trip unit with rotary knob operation
50Corriente nominalMax adjustable trip current 50A; thermal trip setting range: 37–50A
Modelo completoGV3P503-pole thermal-magnetic motor breaker, 37–50A, EverLink BTR screw terminals, IP20
Código de pedidoFD6887Schneider official standard part number
  1. Core Technical Specification Table
Categoría de parámetroDatos técnicosObservaciones
Parámetros básicos
Configuración de polos3PAG (3-polo)For three-phase AC circuits
Tipo de viajeThermal-MagneticCombines thermal overload protection & magnetic short-circuit protection
Modo de operaciónRotary Knob ControlManual switching with ON/OFF marking
TerminationEverLink BTR screw-clamp terminalsFast wiring to reduce loose connection risks
Parámetros eléctricos
Thermal Trip Adjustment37–50ACompatible with motors of different rated powers
Tensión operativa nominal (interfaz de usuario)690V y50/60Hz
Tensión nominal de aislamiento (ue)690V yCumple con IEC 60947-2
Corriente operativa nominal (Es decir)50ACorriente máxima de funcionamiento continuo
Corriente de disparo magnético700AShort-circuit instantaneous tripping value
Máxima capacidad de rotura (uci)100elA 400V
Matched Motor Rating22kilovatios @ 400VPara motores asíncronos trifásicos
Mecánico & Ambient Parameters
Protección de ingresoIP20Finger-touch safe against live components
MontajeMontaje en carril DINStandard 35mm top-hat rail
PesoAprox.. 0.45kilosFácil instalación & transportation
Temperatura de funcionamiento-25°C ~ +60°CSuitable for most industrial environments
Temperatura de almacenamiento-40°C ~ +85°CWide storage temperature range
Certificaciones
Main ApprovalsCE, UL, CSA, CCC, CAOGlobally certified per international standards
Eco CertificationsRoHS, ALCANZAREU-compliant environmentally friendly design

III. Full GV3P Series Model List

ModeloThermal Trip RangeMatched Motor Power @400VCorriente de disparo magnéticoCódigo de pedido
GV3P4025–40A18.5kilovatios600AFD6886
GV3P5037–50A22kilovatios700AFD6887
GV3P6548–65A30kilovatios800AFD6888
GV3ME5037–50A22kilovatios700AFD6890
GV3ME6548–65A30kilovatios800AFD6891
GV3ME8056–80A37kilovatios1000AFD6892
GV3ME10070–100A45kilovatios1200AFD6893
  1. Alternative Cross Reference (Modelos de reemplazo)
  2. In-house Schneider Replacement
Modelo OriginalReemplazoDescripción
GV3P50GV3ME50Identical performance; ME is enhanced version with better accessory compatibility
GV3P50New production GV3P50No functional change, only production batch update
  1. Equivalentes entre marcas
MarcaModelo equivalenteMatching GradeVentajas
TEJIDOMS132-50★★★★★Misma calificación actual, interchangeable mounting dimension
siemens3RV2031-4KA10★★★★☆Viaje termomagnético, fits 22kW motors
EatonPKZM0-50★★★★☆3-diseño de poste, 100kA capacidad de corte
chintNDM2-63M/3300★★★☆☆Cost-effective for bulk replacement
DeliciosoCDM1-63M/3300★★★☆☆Well-known domestic brand with high cost-performance
  1. Entornos de aplicación & Field Cases
  2. Aplicaciones recomendadas

Automatización Industrial: Sobrecarga & short-circuit protection for 3-phase asynchronous pumps, fans and compressors

Fabricación: Production line motor control & machine tool protection

Electricidad del edificio: Central air-conditioning & fire-fighting pump control

Energy Sector: Front-end protection for small generator sets and inverters

Infraestructura: Wastewater treatment equipment & bulk material conveying systems

  1. Non-Recommended Applications

DC Circuits: Designed exclusively for AC; abnormal tripping characteristics under DC supply

Ultra-Frequent Cycling: Not applicable for >30 starts per hour (accelerates trip unit aging)

High Altitude: Derating mandatory above 2000m elevation

Corrosive Atmosphere: No anti-corrosion coating; unsuitable for strong acid/alkali surroundings

  1. Casos de aplicación típicos

Caso 1: Fan System Protection for Food Processing Plant

Equipo: 3×22kW centrifugal fans, 380V/50Hz

Solución: GV3P50 + LC1D65 contactor combination

Outcome: Triple protección contra sobrecarga, cortocircuito & pérdida de fase; equipment failure rate reduced by 40%

Caso 2: Submersible Sewage Pump Control at Wastewater Plant

Equipo: 4×22kW submersible sewage pumps, 380V/50Hz

Solución: GV3P50 + contactos auxiliares + PLC interlock control

Outcome: Full motor protection plus remote monitoring, lower maintenance expense

  1. Cumplimiento de envíos aéreos & Certificación CE
  2. Cumplimiento del transporte aéreo

UN38.3: No requerido; no built-in lithium battery or supercapacitor inside

Shipping Class: General commodity without special transport restriction

Packing: Standard industrial carton to avoid transit damage

Documento de envío: Copy of CE certificate + RoHS compliance declaration available

  1. CE Certification Details

Normas aplicables: CEI 60947-2 (LV switchgear) & CEI 60947-4-1 (motor control equipment)

Valid Region: European Economic Area (EEA) & global territories accepting CE marking

Validity: Permanently valid complying with current normative requirements

Consulta: Check Schneider official website product page or certification database

VII. Solución de problemas de fallas comunes

Fault SymptomProbable CausesRemedial Actions
Frequent thermal tripping1. Sobrecarga del motor1. Inspect motor load
2. Underset trip current2. Adjust rotary knob to correct setting
3. Excess ambient temperature3. Improve ventilation or derate operating current
Unable to close1. Tripping latch not reset1. Toggle knob OFF then ON to reset
2. Short circuit in wiring2. Troubleshoot short-circuit faults
3. Atasco mecánico3. Clean or replace breaker
No protection upon phase loss1. Cableado incorrecto1. Recheck three-phase cabling
2. Damaged trip unit2. Replace trip component
3. Severe 3-phase unbalance3. Balance connected loads
Overheated terminals1. Terminales sueltos1. Retighten terminal screws
2. Undersized cable2. Upgrade to proper wire gauge
3. Terminal oxidation3. Clean terminals or replace unit

VIII. Sizing Guidelines & Reglas de selección rápida

Quick Selection Formula Summary

> GV3P series 3-pole thermal-magnetic breakers;

> Suffix number denotes upper current limit;

> 40 = 25–40A, 50 =37–50A, 65 max at 65A;

> Power matching rule: 40 for 18.5kW, 50 for 22kW, 65 for 30kW.

Quick Rules

  1. Coincidencia actual: Motor rated current ×1.1 ≤ breaker setting ≤ motor rated current ×1.3
  2. Power Reference: A 400V, GV3P50 matches 22kW motor (~44A nominal)
  3. Accessory Option: Contacto auxiliar: GV3AE11 (1NO+1NC) / GV3AE20 (2NO)
  4. Mounting Spacing: DIN rail install; ≥10mm clearance for heat dissipation, away from heat-generating devices
  5. Instalación & Wiring Instruction
  6. Pasos de instalación

Confirm standard 35mm DIN rail

Snap breaker firmly onto rail

Incoming power: top-feed or bottom-feed acceptable

Motor cable connection: terminal tightening torque 2.5Nm recommended

  1. Especificación de cableado

Wire cross-section range: 1.5mm² min ~35mm² max

Terminal: EverLink BTR screw terminal compatible with copper/aluminum conductors

Phase marking: R/S/T corresponds to L1/L2/L3; no neutral connection (3P without N pole)

  1. EMC Protection

Maintain ≥50mm clearance between breaker and contactors

Separate control wiring from power cables to avoid cross-interference

Install EMC filter if needed for EMI suppression

Full Application Overview for Schneider GV3P50 Motor Circuit Breaker

  1. Resumen de la aplicación principal

Schneider GV3P50 is a 3-pole thermal-magnetic motor circuit breaker with adjustable trip 37–50A, rated for 22kW three-phase asynchronous motors @400V. Its core functions: sobrecarga del motor, cortocircuito & phase-loss protection plus manual switching, widely used in below industries:

  1. Detailed Application Classification
  2. Automatización Industrial & Fabricación
SolicitudEquipoRequisito de protecciónApplication Benefit
Production Line ControlTransportadores, sorters, máquinas de embalajeContinuous running protection against overload shutdownImprove line stability & reduce breakdown loss
Máquinas herramientaMilling, lathe & grinder spindle motorsProtection for frequent start-stop & instant short-circuit breakingProtect costly equipment and extend service life
Bulk HandlingBucket elevators, transportadores de tornilloStall & phase-loss protectionPrevent burnout & cut maintenance cost
Maquinaria generalImpresión, textil & plastic processing machinesProtección contra sobrecarga + emergency manual cut-offSimplify control circuit & enhance operational safety
  1. Fluid Conveyance Systems
SolicitudEquipoProtection FeatureTypical Parameter
Pump SetIndustrial pump, fire pump, sewage pumpDual overload + phase-loss protection, moisture-resistant22kW/380V,50Hz, setting 37–50A
Fan UnitCentrifugal/axial/induced draft fansLight-load startup protection against impeller jammingAdapt to current fluctuation from variable duct resistance
CompresorAire & compresores de refrigeraciónHeavy-start & protección contra sobrecalentamientoTolerate frequent loading/unloading cycles
Vacuum PumpIndustrial & water-ring vacuum pumpsLow-current idle-running damage preventionAdjustable setting for light-load operation
  1. Edificio & Municipal Infrastructure
SectorSistemaKey DemandMétodo de montaje
climatizaciónCentral air-con, air handler, cooling towerStable continuous-duty protectionDIN rail mounted with contactor interlock
Automatización de edificiosFire control, security & elevator room equipmentEmergency cut-off safetyRemote monitoring via PLC
WastewaterAerator & sludge processing unitsPolvo & moisture resistanceCabinet installation with IP20 protection
Nueva energíaSmall gen-set & PV invertersobrecorriente & grid-fault isolationRated up to 690V high-voltage system
  1. Other Industrial Sectors
IndustriaEquipoSpecial RequirementMatching Advantage
AgriculturaIrrigation pump & feed processorOutdoor installation against grid voltage swingWide operating temp: -25°C~+60°C
MineríaSmall conveyor & mine ventilation fanHeavy startup + high short-circuit withstand100kA alto poder de corte
Alimento & BebidaMixer & sterilization equipmentSanitario & easy-clean layoutNo exposed live parts for hygiene compliance
PharmaFarmacéutico & cleanroom machineryPrecise control & low failure rateHigh accuracy thermal-magnetic trip characteristic

III. Non-Recommended Applications (Avoidance Guide)

Unsuitable ConditionRazónAlternative Solution
DC CircuitAbnormal tripping characteristic under DC (rated only AC 50/60Hz)Dedicated DC-rated Schneider circuit breakers
>30 Starts/HourAccelerated trip unit ageing & shortened service lifeGV3ME enhanced series or match with soft starter
Altitude>2000mPerformance derating requiredHigh-altitude specified breaker or add upstream protection
Strong Corrosive AtmosphereUncoated terminals prone to oxidationAnti-corrosion coated model or protective enclosure
Explosion Hazard ZonesStandard version without ATEX certificationATEX certified explosion-proof breakers
Single-Phase Motors3-pole structure cannot provide single-phase protectionGV2 single-phase motor breaker series
  1. Detailed Field Application Cases

Case1: 22kW Fan Protection in Food Factory

Setup: 3×22kW centrifugal fans 380V/50Hz, independent control per unit

Scheme: GV3P50 + LC1D65 contactor + GV3AE11 auxiliary contact

Lógica: Manual/Auto switch; auto stop & alarm upon overload

Resultado: Triple protection realized; failure rate -40%, maintenance cost -30%

Case2: Submersible Sewage Pump Control at WWTP

Setup: 4×22kW submersible sewage pumps 380V/50Hz, alternating operation

Scheme: GV3P50 + PLC interlock + level transducer

Condición: Humid environment, 10~15 starts/hour frequent cycling

Resultado: Anti-stall burnout + remote auto-switching, confiabilidad mejorada del sistema

Case3: Central Air-conditioning for Shopping Mall

Setup: 3×22kW chilled water pumps with VFD control 380V/50Hz

Scheme: GV3P50 + inversor + temperature sensor

Característica: Speed auto-adjust by return water temp; coordinated protection by inverter + breaker under overload

Resultado: ≥30% energy saving, service life doubled, superior system stability

  1. Recommended Matching Components & Consejos de selección
  2. Recommended Matching List
AccesorioNúmero de pieza.FunciónValor
Contactor de CALC1D65Remote control for frequent start-stopEnable automatic control & reduce manual operation
Contacto auxiliarGV3AE111NO+1NC signal outputAlarm feedback or PLC interlock
Relé de sobrecarga térmicaLRD4363Optional secondary overload protectionDouble motor protection for enhanced safety
Control PushbuttonXB4 SeriesManual start/stopHMI & emergency shutdown function
  1. Sizing Rules
  2. Power Match: 22kilovatios (~44A @400V) optimally paired with GV3P50 (37–50A)
  3. Trip Setting: Motor rated current ×1.1 ≤ breaker setting ≤ motor rated current ×1.3
  4. Mount Clearance: ≥50mm gap to adjacent contactors; ≥10mm free space for heat dissipation
  5. Wiring Torque: Cable terminal tightening torque fixed at 2.5Nm
  6. Ambient Derate: Reducir 1% rated current per every 1°C rise above +40°C ambient temperature