Bloque de contactos auxiliares Schneider GVAE11

GVAE11 is a 1NO + 1NC instantaneous auxiliary contact block of Schneider TeSys GV series. It is front-mounted and compatible with GV2/GV3 series motor circuit breakers. With a rated current of 2.5A and IP20 protection degree, it is used for status monitoring and signal feedback of motor control circuits, serving as a standard accessory for ...

  • Detalles del producto

GVAE11 is a 1NO + 1NC instantaneous bloque de contactos auxiliares of Schneider TeSys GV series. It is front-mounted and compatible with GV2/GV3 series motor circuit breakers. With a rated current of 2.5A and IP20 protection degree, it is used for status monitoring and signal feedback of motor control circuits, serving as a standard accessory for motor control in industrial automation systems.

Segmento de códigoSignificadoDescripción
GVACategoría de productoAuxiliary contact block for GV series
miPosición de montajeFront mounting, different from side-mounted models
11Configuración de contacto1 Normalmente abierto (NO) + 1 Normalmente cerrado (CAROLINA DEL NORTE) instantaneous contacts with mechanical linkage

Full Model Definition: GVAE11 = Schneider GV series, front-mounted, 1NO+1NC instantaneous auxiliary contact block

  1. Especificaciones técnicas básicas
CategoríaPresupuestoObservaciones
Características generales
Tipo de productoInstantaneous auxiliary contact blockMechanically linked, operates synchronously with main contacts of circuit breaker
Configuración de contacto1NO + 1CAROLINA DEL NORTE (Instantáneo)NO/NC status switches in sync with the main circuit of the circuit breaker
Compatible DevicesSchneider TeSys GV2/GV3 series motor circuit breakersCompatible with GV2L, GV2LE, GV2ME, GV2P, GV2RT, GV3L, GV3P and other models
Método de montajeFront snap-on installationTool-free assembly & quick removal with precise positioning
Parámetros eléctricos
Tensión operativa nominal24–240 VCA, 24–60V DCSuitable for standard voltages of control circuits
Corriente operativa nominal2.5A (Ith)Continuous current carrying capacity
Tensión nominal de aislamiento690V yComplies with insulation requirements for industrial control circuits
Resistencia mecánica100,000 ciclos de operaciónHigh reliability for frequent operations
Resistencia eléctrica100,000 ciclos de operación (AC-15 2.5A/240V)Meets long-term service requirements of control circuits
Tipo de terminalTerminales de tornilloCopper wire cross-section: 0.5–1.5mm²; Par de apriete: 0.8–1.2Nm
Físico & Parámetros ambientales
Grado de protecciónIP20Evita el acceso de los dedos a piezas vivas.
Dimensiones (Ancho × Alto × Fondo)45 × 20 × 15mmEstructura compacta, no extra installation space required for circuit breakers
Temperatura de funcionamiento-25℃ ~ +60℃Amplio rango de temperatura para entornos industriales.
ColorGrisMatches the appearance of GV series circuit breakers
CertificacionesCCC, UL, CSA, CAOMulti-standard certifications for global application
Información de pedido
Manufacturer Part No.GVAE11Official Schneider model
Standard Order CodeGVAE11Original imported version
EAN Code3.38911E+12International universal commodity code
  1. Full Model List (GVAE Series Auxiliary Contacts)
ModeloConfiguración de contactoPosición de montajeCompatible DevicesAplicación principal
GVAE11NO or 1NC (Opcional)FrenteSerie GV2/GV3Simple status indication, single signal output
GVAE111NO + 1CAROLINA DEL NORTEFrenteSerie GV2/GV3Standard status monitoring, output open/close signals simultaneously
GVAE202NOFrenteSerie GV2/GV3Control circuits requiring multiple NO signals
GVAE022CAROLINA DEL NORTEFrenteSerie GV2/GV3Control circuits requiring multiple NC signals
GVAE141NO + 1CAROLINA DEL NORTELadoSerie GV2/GV3Side mounting for space-limited installations
GVAE242NOLadoSerie GV2/GV3Side mounting for multiple NO signal demands
GVAE042CAROLINA DEL NORTELadoSerie GV2/GV3Side mounting for multiple NC signal demands
  1. Modelos de reemplazo & Comparación de competidores

4.1 Internal Schneider Replacements

Modelo OriginalModelo de reemplazoDiferenciasEscenarios de aplicación
GVAE11GVAE14Different mounting position (montaje lateral)Insufficient front space, side mounting required
GVAE11GV2ME + Built-in ContactsDiseño integrado, no extra assembly neededNew equipment selection for integrated layout
GVAE11GV3P + Built-in ContactsUpgraded series with enhanced functionsHigh-standard applications requiring advanced protection

4.2 Cross-brand Competitor Comparison

MarcaModeloConfiguración de contactoCompatible DevicesPrincipales diferencias
SchneiderGVAE111NO + 1CAROLINA DEL NORTESerie GV2/GV3Precise mechanical linkage, Protección IP20, alta compatibilidad
TEJIDOMS132-011NO + 1CAROLINA DEL NORTEMS132 SeriesSide mounting, rated current 3A, similar price
siemens3RV2091-1A1NO + 1CAROLINA DEL NORTE3RV20 SeriesMontaje enchufable, rated current 2A, complete certifications
EatonPKZM0-AUX111NO + 1CAROLINA DEL NORTEPKZM0 SeriesFront mounting, rated current 2.5A, terminales de resorte
chintNXC-A111NO + 1CAROLINA DEL NORTESerie NXCRentable, reliable domestic alternative
  1. Entornos de aplicación & Casos típicos

5.1 Aplicaciones recomendadas

Motor Control Circuit: Feedback circuit breaker ON/OFF status for PLC/DCS system monitoring

Alarm System: Trigger audible and visual alarms via NC contacts when the circuit breaker trips

Interlock Control: Prevent simultaneous startup of multiple motors and realize sequence control

Monitoreo remoto: Transmit status signals to SCADA system for remote diagnosis

Circuito de seguridad: Form safety protection circuits together with emergency stop buttons

5.2 Not Recommended Applications

Main Circuit Usage: Rated current is only 2.5A, not applicable for motor main circuits

High-frequency Switching: Encima 1000 switching cycles per hour will shorten service life

Severe Electromagnetic Interference Environment: Additional shielding is required to avoid malfunction

Humid/Corrosive Environment: IP20 protection is insufficient; install extra enclosure or select higher protection grade products

5.3 Casos de aplicación típicos

Caso 1: Pump Unit Control in Wastewater Treatment Plant

Equipo: 15kW submersible pump, GV2P32 circuit breaker + GVAE11 auxiliary contact

Configuración: NO contact of GVAE11 connected to PLC digital input module; NC contact connected to alarm circuit

Outcome: Real-time monitoring of pump operating status, automatic alarm and event recording upon faults

Caso 2: Conveyor System in Automotive Production Line

Equipo: 12 conveyor lines, each equipped with GV2P32 + GVAE11

Configuración: GVAE11 contacts linked with PLC to realize sequential startup and interlock protection for conveyors

Características: Mechanical linkage ensures accurate status feedback and reduces misjudgment of control systems

  1. Solución de problemas & Maintenance Manual

6.1 Fallos comunes & Soluciones

Fenómeno de fallaPosibles causasSoluciones
No change of contact signals1. Improper installation of contact block1. Reinstall the block and ensure the clip is fully engaged
2. Damaged mechanical linkage2. Inspect linkage mechanism and replace damaged unit
3. Burned or oxidized contacts3. Clean or replace the contact block
4. Cableado incorrecto4. Check wiring and confirm correct connection of NO/NC contacts
Contact welding1. Excessive current in control circuit1. Ensure control circuit current ≤ 2.5A
2. Overheating caused by frequent switching2. Reduce switching frequency or select higher-rated contacts
3. Arc erosion3. Replace with a new contact block
Interferencia de señal1. Control wires not separated from main wires1. Separate control wires from main wires (spacing ≥ 100mm)
2. No shielded cable used2. Use shielded cable with single-end grounding
3. Mala conexión a tierra3. Inspect and ensure reliable grounding
Instalación suelta1. Clip not fully locked1. Reinstall until a click sound is heard
2. Loosening caused by vibration2. Fit shock-absorbing pads or reinforce installation

6.2 Maintenance Procedures

  1. Inspección diaria (Semanalmente)

Check installation condition and ensure no looseness

Inspect terminals for overheating and looseness

Test contact switching to confirm synchronization with circuit breaker

  1. Mantenimiento de rutina (Cada 6 Meses)

Power off and remove dust on the contact block

Measure contact resistance (shall be ≤ 50mΩ)

Check flexibility of mechanical linkage

  1. Annual Maintenance

Replace frequently used contact blocks

Test insulation performance of control circuits

Retighten all electrical connections

6.3 Quick Diagnosis Tips

No signal? Check installation and linkage first.

Contact welded? Limit current and cut switching times.

Interferencia de señal? Separate wires, apply shielding and good grounding.

Loose fitting? Re-clip firmly and add shockproof measures for vibrating sites.

  1. Selección & Pautas de instalación

7.1 Reglas de selección

Compatibilidad: Confirm matching with GV2/GV3 series circuit breakers; not applicable for other series

Configuración de contacto: Select 1NO+1NC (GVAE11), 2NO (GVAE20) or 2NC (GVAE02) according to control demands

Posición de montaje: Choose GVAE11 for front mounting, GVAE14 for side mounting

Coincidencia actual: Control circuit current shall not exceed 2.5A; select higher-specification products if overloaded

7.2 Notas de instalación

Installation Sequence: Install circuit breaker first, then attach the contact block and fully lock the clip

Estándar de cableado: Use 0.5–1.5mm² copper wires with tightening torque of 0.8–1.2Nm; avoid over-tightening

Clear Marking: Label NO/NC contacts to prevent wiring errors

Linkage Test: Manually operate the circuit breaker after installation to verify synchronous contact action

Medidas de protección: Install extra enclosures for dusty or humid environments

  1. Production Status & Soluciones de reemplazo

Current Status of GVAE11: In production, no discontinuation plan (as of June 2026)

Mejora & Opciones de reemplazo:

  1. Actualización funcional: GV3 series models with built-in contacts (no extra assembly, fewer fault points)
  2. Intelligent Upgrade: TeSys T series (with communication function for network-based status transmission)
  3. Alternativa Doméstica: Compatible domestic GVAE11 models (lower cost with equivalent performance)