Schneider LC1E1801 Contactor

Explicación del código del modelo: LC1E = TeSys E series contactor; 18 = rated 18A at 400V under AC-3 duty; 01 = built-in 1 contacto normalmente cerrado (1CAROLINA DEL NORTE) ⚠️ The LC1E series has been discontinued (production stopped in July 2020). The standard replacement model is LC1N1801, totalmente compatible en el montaje, terminal layout and performance. Key Specifications Main ...

  • Detalles del producto

Explicación del código del modelo: LC1E = TeSys E series contactor; 18 = rated 18A at 400V under AC-3 duty; 01 = built-in 1 contacto normalmente cerrado (1CAROLINA DEL NORTE)

⚠️ The LC1E series has been discontinued (production stopped in July 2020). The standard replacement model is LC1N1801, totalmente compatible en el montaje, terminal layout and performance.

Especificaciones clave

Contactos principales: 3PAG, 3NO

AC-3 (motor duty): 18A @ 400V; AC-1 (carga resistiva): 25A

Motor rating: 7.5kW @ 380/400V; 4kW @ 220V; 9kW @ 440V

Tensión de aislamiento Ui: 690V; Tensión soportada de impulso Uimp: 6kV

Contacto auxiliar: 1CAROLINA DEL NORTE (Normalmente cerrado)

Montaje: Carril DIN / montaje con tornillos de placa base

Dimensiones generales: W45mm × H74mm × D80mm, net weight ≈0.3kg

Clase de protección: IP20; Temperatura de funcionamiento: -5~+55 ℃; No derating up to 3000m altitude

Vida mecánica: 10 millones de operaciones; Vida eléctrica AC-3: 1.2 millones de operaciones; Frecuencia máxima de funcionamiento: 1800 ciclos/hora

Coil suffix definitions (complete model number)

LC1E1801B5: CA 24V, 50Hz

LC1E1801F5: CA 110 V., 50Hz

LC1E1801M5: CA 220 V., 50Hz (más común en China)

LC1E1801Q5: CA380V, 50Hz

Sufijo 7 = 50/60Hz universal; sufijo 6 = 60Hz only

Consumo de energía de la bobina (M5 220V example)

Inrush VA: 95Virginia; Sealed holding VA: 8.5Virginia; Coil heat dissipation: 2~3W

voltaje de captación: 0.85~1.1Uc; voltaje de caída: 0.3~0.6Uc

Par de apriete & calibre de alambre

Torque for main circuit and control circuit terminals: 1.2 Nuevo Méjico

alambre macizo: 1.5~6mm²; alambre trenzado (with ferrule): 1~4mm²

Matching selection reference

Relé de sobrecarga térmica adecuado: LRD07 / LRN07 (current range suitable for 18A)

Accesorios: LA1EN auxiliary contact block, LA9D coil surge suppressor, mechanical interlock block

Alternativa doméstica: CJX2-1801 (similar outline, pay attention to mounting hole and marking differences)

Guía de solución de problemas

  1. Bobina energizada pero sin tracción: Check if coil voltage is within 0.85~1.1Uc; inspect broken coil wire and loose terminals
  2. Pulled in but main circuit no continuity: Erosión del contacto principal, soldadura por contacto, cableado suelto
  3. Buzzing / chattering: Subtensión, large harmonic distortion, dust accumulated on core faces
  4. Failed to drop out after power-off: Welded main contacts, core stuck by oil and dirt

Detailed Installation Procedure for Schneider LC1E1801 Contactor

⚠️ Safety precondition: Operated by qualified electricians; cut off all power supply and verify zero voltage before installation. LC1E1801: 3P main contacts with built-in 1NC auxiliary contact. Marcado de terminales: Circuito principal L1/L2/L3 (line side, incoming), T1/T2/T3 (lado de carga, outgoing); Coil A1, A2; Contacto auxiliar: 95, 96 (1CAROLINA DEL NORTE)

  1. Preparación previa a la instalación
  2. Verificar el voltaje de la bobina: LC1E1801M5=AC220V, Q5=AC380V, F5=AC110V. Coil rated voltage must match control circuit voltage to avoid coil burnout.
  3. Inspección visual: No shell cracks, intact terminals, armature moves freely without jamming when pressed manually.
  4. Herramientas: 2 Destornillador Phillips, pelacables, multímetro, llave dinamométrica; 35mm standard DIN rail or mounting base plate.
  5. Wire specification

Main circuit solid wire: 1.5~6mm²; Cable trenzado con virola: 1~4mm²

circuito de control (A1/A2, contactos auxiliares): 0.75~1.5mm²

Par de apriete: 1.2 Nuevo Méjico (avoid over-tightening to prevent thread stripping, or loose connection causing overheating)

  1. Environmental check: Cabinet temperature -5℃~+55℃, mantener alejado del polvo, humedad y aceite. Mount vertically upright. Do NOT install upside down or horizontally.
  2. Fijación (2 methods: Carril DIN / montaje con tornillos de placa base)

Método 1: 35mm montaje en carril DIN (privilegiado)

  1. The contactor has upper hooks and a spring locking clip at the bottom.
  2. Hook the upper notch onto the top edge of the DIN rail first.
  3. Press the bottom of the contactor down until you hear a click, the bottom clip locks onto the rail.
  4. Shake lightly to confirm firm fixation. Eliminación: Use a flat screwdriver to pry down the bottom clip and pull out the contactor.

Método 2: Screw mounting on insulated base plate (no rail)

  1. Mark and drill holes on the insulated plate according to the rear mounting holes (for M4 screws).
  2. Insert screws diagonally, pre-tighten, then torque evenly in diagonal sequence; do not force one side to avoid casing deformation.
  3. Accessory Fitting (Opcional: LA1EN auxiliary block, mechanical interlock etc.)
  4. Top auxiliary contact block: Align with the slots on top of contactor, push vertically down until latched.
  5. Thermal relay LRD/LRN: Clip directly underneath the contactor, align positioning slots; the linkage will engage automatically.
  6. Surge suppressor LA9D: Clip beside coil terminals A1/A2, absorbs back EMF to protect PLC output points.
  7. Secuencia de cableado (Main circuit → Auxiliary contacts → Coil control circuit)

Standard routing: Line side on top, load side on bottom. L1/L2/L3 on top for three-phase supply; T1/T2/T3 at bottom for load (motor).

  1. Cableado del circuito principal

Strip insulation 5~6mm, avoid loose copper strands; ferrules are mandatory for stranded wire.

Keep phase sequence L1→T1, L2→T2, L3→T3 as per drawing.

Torque screws to 1.2N·m; only one conductor per terminal.

  1. Built-in auxiliary contact (95-96, CAROLINA DEL NORTE)

Terminales 95-96: Conductive when coil de-energized, open when contactor pulls in. Usually used in stop circuit or fault feedback for motor control.

If NO contact is required, add LA1EN auxiliary block.

  1. Coil A1, A2 (circuito de control)

A1 and A2 have no polarity for AC. For AC220V: one to live, one to neutral; for AC380V: connect to two different phases.

Wire in series with start/stop pushbuttons, thermal relay NC contact or PLC outputs.

Route control wires separately from power cables to reduce interference.

Terminal summary:

L1/L2/L3 (Supply In), T1/T2/T3 (Load Out), A1 A2 (Bobina), 95-96 (1NC incorporado)

  1. Inspección previa al encendido
  2. control visual: All terminals tightened, no exposed copper, no short circuit risk, no loose strands touching adjacent terminals.
  3. Prueba de continuidad con multímetro:

Estado desenergizado: No continuity between L-T; 95-96 auxiliary contact is conductive.

Manually press armature to simulate pull-in: L-T becomes conductive, 95-96 abre.

  1. Double-check coil voltage; separate power supply for main circuit and control circuit.
  2. Puesta en marcha
  3. Energize control circuit only, keep main power off: Press start button, contactor should pull-in smoothly without chattering or buzzing; release stop button for reliable drop-out.

parloteo: Baja tensión de alimentación, loose wiring or dirty core surfaces.

  1. After control circuit test passes, energize main circuit and run on load.
  2. Temperature check after 10min running: No obvious overheating at terminals (temperature rise indicates poor connection).
  3. Notas de instalación & Prohibiciones
  4. Keep minimum clearance ≥10mm between contactor and fuse / MCB for heat dissipation.
  5. Minimum spacing ≥5mm between multiple contactors; increase spacing for high ambient temperature.
  6. Do not plug or remove auxiliary blocks when energized.
  7. Do not trap wire insulation inside terminal clamps; copper must be fully clamped.
  8. LC1E discontinued, spare replacement: LC1N1801, same mounting size and terminal definition.
  9. Fallos comunes de instalación

No pull-in after energized: Wrong A1/A2 voltage, broken control wire or open button circuit

Buzzing when pulled in: Subtensión, dust or rust on magnetic core faces

Cannot drop out after power cut: Welded main contacts or core jammed by oil

Schneider Easy TeSys E (LC1E / EasyPact TVS) Series Full List

Nota importante: LC1E series fully discontinued in July 2020. Reemplazo directo: LC1N series, dimensiones de montaje y disposición de terminales idénticas.

Regla modelo: LC1E + current code + auxiliary contact code (10=1NO; 01= 1 NC) + coil suffix

Coil suffix description:

B5=AC24V 50Hz; F5=AC110V 50Hz; M5=AC220V 50Hz; Q5=AC380V 50Hz

B7/F7/M7/Q7=50/60Hz universal; BD=DC24V; 6=60Hz only

  1. 3P LC1E Contactors (AC-3 @400V)
Modelo básicoCorriente AC-3Motor Rating @400VBuilt-in Auxiliary Contact
LC1E06106A2.2kilovatios1NO
LC1E06016A2.2kilovatios1CAROLINA DEL NORTE
LC1E09109A4kilovatios1NO
LC1E09019A4kilovatios1CAROLINA DEL NORTE
LC1E121012A5.5kilovatios1NO
LC1E120112A5.5kilovatios1CAROLINA DEL NORTE
LC1E181018A7.5kilovatios1NO
LC1E180118A7.5kilovatios1CAROLINA DEL NORTE (your referenced model)
LC1E251025A11kilovatios1NO
LC1E250125A11kilovatios1CAROLINA DEL NORTE
LC1E321032A15kilovatios1NO
LC1E320132A15kilovatios1CAROLINA DEL NORTE
LC1E381038A18.5kilovatios1NO
LC1E380138A18.5kilovatios1CAROLINA DEL NORTE
LC1E401140A18.5kilovatios1NO+1NC
LC1E501150A22kilovatios1NO+1NC
LC1E651165A30kilovatios1NO+1NC
LC1E801180A37kilovatios1NO+1NC
LC1E951195A45kilovatios1NO+1NC
LC1E120120A55kilovatiosSin incorporado, add auxiliary block separately
LC1E160160A75kilovatiosSin incorporado, add auxiliary block separately
LC1E200200A90kilovatiosSin incorporado, add auxiliary block separately
LC1E300300A160kilovatiosSin incorporado, add auxiliary block separately

Example complete model: LC1E1801M7 = 18A, 1CAROLINA DEL NORTE, AC220V 50/60Hz universal

  1. Matching LRE Thermal Overload Relays (plug-on fit for LC1E)

LRE01N~LRE35N (for 06~38A); LRE322N~LRE365N (for 40~300A)

LRE01N: 0.1~0.16A

LRE02N: 0.16~0.25A

LRE03N: 0.25~0.4A

LRE04N: 0.4~0.63A

LRE05N: 0.63~1A

LRE06N: 1~1.6A

LRE07N: 1.6~2.5A

LRE08N: 2.5~4A

LRE09N: 4~6A

LRE10N: 6~10A

LRE12N: 10~16A

LRE14N: 16~24A

LRE16N: 24~36A

LRE21N: 28~36A

LRE22N: 36~48A

LRE322N: 55~70A

LRE323N: 63~80A

LRE353N: 80~104A

LRE355N: 104~135A

LRE365N: 130~165A

  1. E-series Accessories
  2. LA1EN: Top-mounted auxiliary contact block (1NO / 1CAROLINA DEL NORTE, stackable)
  3. LAEM1: Módulo de enclavamiento mecánico (for two contactor interlocking)
  4. LA9D: Supresor de sobretensiones de bobina (red RC / varistor, PLC output protection)
  5. LAEB1N / LAEB3N: Thermal relay independent base (when not mounted under contactor)
  6. LA1EBN: Timed auxiliary contact block (retardo / retraso en la salida)
  7. 2PAG / 4P LC1E (single phase, iluminación & carga resistiva, AC-1 duty)

LC1E0920: 2Pregunta 9A

LC1E2520: 2P 25A

LC1E0940: 4Pregunta 9A

LC1E2540: 4P 25A

LC1E4040: 4P 40A

4P versions commonly used for HVAC, lighting and heating resistive loads

  1. Cross Reference Table
Old LC1E ModelDirect Replacement LC1N
LC1E0601/0610LC1N0601 / LC1N0610
LC1E0901/0910LC1N0901 / LC1N0910
LC1E1201/1210LC1N1201 / LC1N1210
LC1E1801/1810LC1N1801 / LC1N1810
LC1E2501/2510LC1N2501 / LC1N2510
LC1E3201/3210LC1N3201 / LC1N3210
LC1E3801/3810LC1N3801 / LC1N3810
LC1E40~95LC1N40~95