El Schneider LC1E400 contactor is a 400A high-current AC contactor belonging to the EasyPact TVS series, specifically designed for industrial applications.
Especificaciones detalladas:
- Parámetros básicos
Número de polo: 3 polos
Tensión de funcionamiento nominal: Power circuit ≤ 690V AC 50/60Hz
Corriente de funcionamiento nominal:
– 400A under AC-3 utilization category (operating temperature ≤ 55°C, operating voltage ≤ 440V AC)
– 500A under AC-1 utilization category (operating temperature ≤ 40°C, operating voltage ≤ 440V AC)
Voltaje de la bobina de control:
– Common specifications include 220V AC 50/60Hz (p.ej., LC1E400M7N) and 110V AC 50/60Hz (p.ej., LC1E400F7N)
Configuración de contacto: 3NO (3 normalmente abierto) contactos principales; some models are equipped with 1NO + 1NC auxiliary contacts
- Características de rendimiento
Corriente Térmica Convencional (Ith): 500A for power circuit at operating temperature ≤ 40°C
Rated Making & Capacidad de ruptura:
– Rated making capacity (Irms): 4000A
– Capacidad de ruptura nominal: 3200A (at operating voltage ≤ 380V AC), Cumple con IEC 60947 estándar
Vida eléctrica: 600,000 operaciones (AC-3), 250,000 operaciones (AC-1)
Vida mecánica: Arriba a 4,000,000 operaciones
- Utilization Categories
AC-3 (Más común): For starting and stopping squirrel-cage motors
AC-1: For controlling non-inductive or slightly inductive loads (p.ej., resistance heating equipment)
- Escenarios de aplicación típicos
– Motor control systems (rango de potencia: 220kW@415V to 280kW@690V)
– AC load control with power factor ≥ 0.95
– Equipos de automatización industrial.
– Main switch control for lighting systems
- Instalación & Alambrado
– Método de montaje: Base mounting
– Cableado del circuito de control: Bolt-fastened, compatible with 1-4mm² flexible or rigid wires
– Power Circuit Wiring: Cable with lugs or terminal connection; terminal specification: 2×30x5mm, tightening torque: 35Nuevo Méjico
Selection Guide for Schneider LC1E400 Contactor
The Schneider LC1E400 is a 400A high-current AC contactor in the EasyPact TVS series, suitable for industrial motor control and high-power load scenarios. Follow these steps for correct selection:
- Determine Basic Parameters
- Tipo de carga & Categoría de utilización
AC-3 (Más común): For starting and stopping squirrel-cage motors
AC-1: For non-inductive or slightly inductive loads (p.ej., resistance heaters)
Selection Key Point: Choose the corresponding utilization category based on actual load. The LC1E400 has a rated current of 400A (AC-3) and 500A (AC-1).
- Tensión de funcionamiento nominal
Main Circuit Voltage: ≤ 690V AC 50/60Hz
Selection Key Point: Contactor’s rated voltage ≥ maximum system voltage (recomendado: 1.2× system voltage)
- Corriente de funcionamiento nominal
LC1E400 Parameters: 400A (AC-3, ≤440V, ≤55°C); 500A (AC-1, ≤440V, ≤40°C)
Selection Formula: Contactor’s rated current ≥ Calculated load current × Safety factor (1.2~1.5 for motor loads)
Calculation Example:
– Rated current of a 400V, 200kW motor ≈ 361A (I=P/(√3×U×cosφ), cosφ=0.85)
– Selected current = 361A × 1.3 ≈ 469A. Por lo tanto, the LC1E400 (400A) is insufficient; a larger model is required.
- Voltaje de la bobina de control
Common Specifications:
– LC1E400M7N: 220V CA 50/60 Hz
– LC1E400F7N: 110V CA 50/60 Hz
– LC1E400U7N: 240V CA 50/60 Hz
Selection Key Point: Must match the control circuit voltage (allow ±10% fluctuation)
- Complete Selection Process
Paso 1: Confirm Load Type & Condiciones de funcionamiento
– Is it a motor load (AC-3) or resistive load (AC-1)?
– Does the ambient temperature exceed 40°C? (Affects rated current)
– Is the starting frequency high? (Affects electrical life)
Paso 2: Calculate or Confirm Load Current
Carga del motor: Ie = Rated power (kilovatios) × 1000 / (√3 × Ue × cosφ × η)
(ue: Tensión nominal; cosφ: Power factor; o: Eficiencia)
Carga resistiva: Ie = Rated power (kilovatios) × 1000 / ue
Paso 3: Select Contactor Specifications
- Clasificación actual: Choose a rating ≥ calculated current and ≥ 400A
- Clasificación de voltaje: Rated voltage ≥ maximum system voltage (p.ej., 500V class for 380V systems)
- Selección de polos: 3 poles for three-phase systems (LC1E400 default); 4 poles optional for special needs (p.ej., LC1E40004 series)
Paso 4: Select Control Coil Parameters
– Choose coil voltage based on control circuit power supply (p.ej., 220V y, 110V y)
– Ensure frequency matching (50Hz or 60Hz)
Paso 5: Select Auxiliary Contact Configuration
Configuración estándar: 3SIN contactos principales
Optional Auxiliary Contacts: 1NO + 1CAROLINA DEL NORTE (p.ej., LC1E400M7N) to meet control circuit requirements
– Add LA series auxiliary contact blocks if standard configuration is insufficient
III. Key Parameter Matching Principles
- Coincidencia actual
Carga del motor: Es decir (contactor) ≥ Ie (Motor) × (1.2~1.5)
– Direct starting: Factor = 1.5
– Star-delta starting: Factor = 0.58
– Frequent starting/stopping or heavy load: Factor = 1.5~2.0
- Coincidencia de voltaje
– Rated insulation voltage ≥ maximum system voltage
– Control coil voltage must match the control circuit
- Utilization Category Matching
AC-3: Suitable for motor starting, running, and stopping (typical application of LC1E400)
– Power range: 220kW@415V to 280kW@690V
AC-1: Suitable for non-inductive loads (p.ej., hornos de resistencia, iluminación) with higher current capacity (500A)
- Selection Example
Guión: Select a contactor to control a 380V, 250kW three-phase asynchronous motor (direct starting, frequent starting/stopping)
Calculation Steps:
- Calculate motor rated current:
Ie = 250,000 / (√3 × 380 × 0.85 × 0.9) ≈ 495A
(Assume cosφ=0.85, η=0.9)
- Determine safety factor: 1.5 for frequent starting/stopping
Selected current = 495A × 1.5 ≈ 743A
- Conclusión: The LC1E400 (400A) is insufficient; a larger model (p.ej., LC1E630) se recomienda.
- Correct Selection: LC1E630M7N (630A, 220V AC coil)
- Notas de selección
- Environmental Factors
– Derate rated current if ambient temperature > 40°C (≈5% derating per 10°C increase)
– Consider derating for altitudes > 2000metro
- Coordination with Protection Devices
– Circuit breaker rated current ≥ Contactor rated current
– Thermal relay setting current should match the motor rated current
- Life Considerations
– vida electrica: 600,000 operaciones (AC-3), 250,000 operaciones (AC-1)
– Vida mecánica: 4,000,000 operaciones
– Choose a higher-rated or special-purpose contactor for frequent operation scenarios
- Resumen
The core principles for selecting the Schneider LC1E400 contactor are “Coincidencia de voltaje, Margen actual, Category Compatibility, and Coil Adaptation”. Selection process:
- Confirm load type and utilization category
- Calculate load current and determine safety factor
- Select appropriate current rating (≥ calculated value)
- Match control coil voltage
- Select auxiliary contact configuration
- Verify coordination with protection devices
The LC1E400 is an ideal choice for motor control with power close to 200kW. For higher power or harsh load conditions, larger models such as the LC1E630 are recommended.
For product quotes, customs clearance services, or customized distribution box solutions, please contact me via WhatsApp for professional support
| hebei china electric Washington:86-13811255435 | ||||||
| shineider-Contactor-F7/M7/P7/Q7 | ||||||
| RMB | Dólar estadounidense | |||||
| LC1F115 | 679.2 | 96.75 | ||||
| LC1F150 | 840.0 | 119.66 | ||||
| LC1F185 | 922.4 | 131.40 | ||||
| LC1F225 | 1140.0 | 162.39 | ||||
| LC1F265 | 1365.0 | 194.44 | ||||
| LC1F330 | 1740.0 | 247.86 | ||||
| LC1F400 | 2376.0 | 338.46 | ||||
| LC1F500 | 3120.0 | 444.44 | ||||
| LC1F630 | 4622.0 | 658.40 | ||||
| hebei china electric Washington:86-13811255435 | ||||||
| shineider-Contactor-F7/M7/P7/Q7/DC | ||||||
| RMB | Dólar estadounidense | |||||
| LC1D09 | 34.2 | 4.87 | ||||
| LC1D12 | 39.9 | 5.68 | ||||
| LC1D18 | 47.5 | 6.77 | ||||
| LC1D25 | 61.8 | 8.80 | ||||
| LC1D32 | 76.0 | 10.83 | ||||
| LC1D38 | 84.5 | 12.04 | ||||
| LC1D40 | 134.9 | 19.22 | ||||
| LC1D50 | 144.4 | 20.57 | ||||
| LC1D65 | 172.9 | 24.63 | ||||
| LC1D80 | 211.0 | 30.06 | ||||
| LC1D95 | 258.4 | 36.81 | ||||
| LC1D40 | hebei china electric Washington:86-13811255435 | |||||
| shineider-Contactor-AC220V/110V/380V/48V/24V | ||||||
| RMB | Dólar estadounidense | |||||
| LC1D40 | 230.0 | 32.76 | ||||
| LC1D50 | 316.0 | 45.01 | ||||
| LC1D65 | 405.0 | 57.69 | ||||
| LC1D80 | 426.0 | 60.68 | ||||
| LC1D95 | 538.0 | 76.64 | ||||
| hebei china electric Washington:86-13811255435 | ||||||
| shineider-Contactor-B/C/M/E/F/M | ||||||
| RMB | Dólar estadounidense | |||||
| LC1D09 | 89.5 | 12.75 | ||||
| LC1D12 | 99.2 | 14.13 | ||||
| LC1D18 | 120.3 | 17.14 | ||||
| LC1D25 | 160.5 | 22.86 | ||||
| LC1D32 | 167.3 | 23.83 | ||||
| LC1D38 | 183.9 | 26.19 | ||||
| LC1D40 | 300.1 | 42.75 | ||||
| LC1D50 | 325.9 | 46.42 | ||||
| LC1D65 | 359.0 | 51.14 | ||||
contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares














![NXC-65 de la serie Kunlun de CHINT Electric es un contactor de CA de 3 polos, nominal de 65 A en la serie NXC. El modelo completo normalmente se expresa como NXC-65 [Voltaje de la bobina] [Frecuencia] NXC-65 from the Kunlun Series by CHINT Electric is a 3-pole AC contactor, rated at 65A in the NXC series. The full model is typically expressed as NXC-65 [Coil Voltage] [Frequency]](https://www.bestcontactor.com/wp-content/uploads/2026/04/ScreenShot_2026-01-30_132315_324-419x560.png)



NH42-63-318x560.png)