6AV2123-2MB03-0AX0
Nombre completo: SIMATIC HMI KTP1200 Basic Color PN
- Desglose del código del modelo
`6AV2123-2MB03-0AX0`
6AV2123: 2nd-generation Basic HMI series
2METRO: KTP1200 (12-pulgada, keys + touch operation)
B: PN (PROFINET Ethernet interface)
03: Versión de hardware
0AX0: Standard delivery version
Distinction of DP variant: 6AV2123-2MA03-0AX0 (PROFIBUS-DP) – not directly interchangeable.
- Especificaciones principales de hardware
| Artículo | Parámetro |
| Mostrar | 12.1-inch TFT wide screen, retroiluminación LED |
| Resolución | 1280 × 800, 65536 bandera |
| Operación | Toque resistivo + 10 physical function keys (keys operable with gloves) |
| Interfaces de comunicación | 1×PROFINET (RJ45), 1×onboard USB (program download via USB flash drive / peripheral connection) |
| Fuente de alimentación | CC 24 V (19.2~28.8V), typical current 510mA, power consumption ≈12.2W |
| Clase de protección | Panel frontal IP65 / NEMA4X; rear side IP20 |
| Real-Time Clock | Integrated hardware RTC, backup duration approx. 6 weeks without power |
| Project Memory | 10 MEGABYTE (maximum limit for Basic projects) |
| Dimensiones generales | W. 330 mm × H 245 mm × Depth 60 milímetros |
| Tamaño de recorte | 306 × 221 milímetros (standard mounting cutout) |
| Temperatura de funcionamiento | 0 ~ +50℃; Temperatura de almacenamiento -20 ~ +70℃ |
| Certificaciones | CE, cULus, RCM, marine certifications (GL/ABS/DNV, etc.) |
III. Software Configuration Information
- Minimum configuration version: TIA Portal WinCC Basic V13 / STEP7 Basic V13
- Supported engineering environments: WinCC Basic / Comfort / Avanzado / Profesional
- ⚠️ Key Limitations:
VBS scripts are not supported (hard limitation of Basic panels)
Supports basic trends, alarms, multi-language (arriba a 10 languages for online switching)
Sm@rtServer available (TIA Portal V14 and above, remote monitoring via mobile devices)
No SD card slot, large-capacity local archiving is not supported
- Compatible PLCs for Communication
✅ Natively supported:
S7-1200 / S7-1500 / S7-200 INTELIGENTE (Ethernet models)
⚠️ Notes:
No DP/MPI port; cannot connect directly to S7-300/400 via DP port. Connection requires Ethernet CP module / PN-DP gateway.
No native Modbus TCP driver for Basic panels. For Modbus TCP communication, select Comfort series or deploy an external gateway.
- Intra-series Comparison & Opciones de reemplazo
1) Same-size Basic HMIs
6AV2123-2MB03-0AX0: KTP1200 Basic PN (Ethernet, tocar + keys) 【Current model】
6AV2123-2MA03-0AX0: KTP1200 Basic DP (PROFIBUS, no Ethernet port)
6AV2123-2GB03-0AX0: TP1200 Basic PN (touch-only, no physical keys)
2) Higher-performance Upgrade
TP1200 Comfort 6AV2124-0QC02-0AX0
Ventajas: Supports scripts, SD card archiving, Modbus functions and larger memory; cutout dimensions are incompatible, cabinet cutout modification required.
- Directrices de selección & Common Pitfalls
- Avoid oversized screens and picture resources in projects; el 10 MB memory limit can be easily exceeded.
- Resistive touch screen: compatible with gloved operation, avoid scratching with sharp hard objects.
- IP65 rating applies only to the front panel. Ensure tight cabinet sealing; never spray water onto the rear side.
- Program download methods: direct Ethernet connection or USB flash drive.
- Script functions are unavailable; complex logic must be implemented inside the PLC.
- Production status: This model is mainstream 2nd-generation Basic HMI with no official end-of-life notice.
VII. Escenarios de aplicación típicos
Maquinaria de embalaje, rubber & plastic equipment, machine tool auxiliary units, medio & pequeñas líneas de producción, sistemas de tratamiento de agua, general stand-alone machinery HMI.
6AV2123-2MB03-0AX0 (KTP1200 Basic PN) Full List of Compatible Components
- Compatible PLC Controllers (Native S7 Protocol over Ethernet)
The HMI is only equipped with PROFINET (RJ45); no DP/MPI port. Direct connection to legacy S7-300/400 (interfaz DP) requires PN-DP gateway.
✅ Native direct connection (built-in TIA Portal drivers)
- S7-1200 Series
6ES7211/212/214/215/217-1AE/1BE/1AG/4AG/1HG/4BG and all related CPUs
- S7-1500 Series
All 6ES7511/512/513/515/516/517 CPUs
- S7-200 INTELIGENTE
6ES7288-1SR20/SR30/SR40/SR60/ST20/ST30/ST40/ST60 (Ethernet-enabled models)
- ET200SP PN CPU
6ES7510-1DJ01-0AB0
⚠️ Gateway required for communication
S7-300 / S7-400 (DP-only): Recommended 6GK1415-2BA10 (PN-DP Coupler)
Third-party Protocol Support
Supports Modbus TCP, compatible with Inovance, Xinje, Omron CP1E/CP2E-N (Ethernet versions)
- Original Manufacturer Accessories Order Numbers
1) Power Terminal Connector
6AV6671-8XA00-0AX0
2-pin DC24V power plug (10 pieces per package)
2) Screen Protective Film (scratch & oil resistance)
6AV2181-3MJ20-0AX0
Dedicated film for KTP1200 Basic, 10 pieces per set
3) Industrial Ethernet Cable & RJ45 Connectors
IE FC RJ45 Fast Connector: 6GK1901-1BB10-2AA0
Pre-assembled industrial cable (5 metro): 6XV1440-4BH50
Bulk industrial Ethernet cable: 6XV1840-2AH10
4) Industrial USB Flash Drive for Backup & Archivar (OEM recommended)
6AV6881-0AS42-0AA1 (32G Industrial USB)
Restriction: KTP1200 Basic has no SD card slot. Program backup and historical archiving rely solely on USB drive; format: FAT32, capacity ≤32 GB.
5) Mounting Clips
No separate order number from Siemens; supplied standard with HMI. For bulk replenishment, use universal 2nd-gen Basic panel clip kits.
6) Wide-temperature Conformal Coated Version (SIPLUS for outdoor / high condensation environments)
6AG1123-2MB03-2AX0
Conformal coating variant based on the base model; operating temperature range -10~+50℃
III. Recommended Siemens Industrial Network Switches
SCALANCE XB208: 6GK5208-0BA00-2AB2 (8-port entry-level switch)
SCALANCE XB216: 6GK5216-0BA00-2AB2 (16-puerto)
tipo compacto: SCALANCE XB005 6GK5005-0BA00-1AB2
- DC24V Cabinet Power Supplies
HMI power consumption ≈12.2W, allow sufficient margin during selection:
2.5 A: 6EP1332-2BA20
4 A: 6EP1333-2BA20
10 A: 6EP1334-2BA20
- Interchangeable HMIs with Identical Cutout (306×221mm)
| Modelo | Diferencia |
| 6AV2123-2MB03-0AX0 | KTP1200 Basic PN (Modelo actual, tocar + physical keys, Ethernet) |
| 6AV2123-2GB03-0AX0 | TP1200 Basic PN (Touch-only, no physical keys) |
| 6AV2123-2MA03-0AX0 | KTP1200 Basic DP (PROFIBUS, no Ethernet port; not a direct replacement) |
Upgrade alternative (cutout incompatible, cabinet modification required)
TP1200 Confort: 6AV2124-0QC02-0AX0 (script support, SD card archiving, enhanced Modbus functions)
- Matching Engineering Software
Minimum TIA Portal version: WinCC Basic V13
Compatible versions: V13 / V14 / V15 / V16 / V17 / V18 / V19
VII. Selection Risk Checklist
- Cannot connect DP-bus PLCs directly; PN-DP gateway is mandatory.
- Basic panels do not support VBS scripts. Implement complex logic within PLC.
- 10 MB internal memory; external USB required for extensive trend archiving.
- Resistive touch screen supports gloved operation; avoid sharp hard objects.
- Prefer PROFINET-certified industrial cables; standard office cables risk packet loss under continuous vibration.
contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares