ABB HPA24/612C 24kV indoor SF6 medium voltage circuit breaker

ABB HPA24/612C is a 24kV indoor SF6 medium voltage circuit breaker with rated current 630A and rated short-circuit breaking current 12.5kA. It is compatible with SafeSix switchgear and has been discontinued. The recommended replacement models are VD4-24/630-16 and HD4-24/630-16.

ABB HPA24/612C is a 24kV indoor SF6 disjoncteur moyenne tension with rated current 630A and rated short-circuit breaking current 12.5kA. It is compatible with SafeSix switchgear and has been discontinued. The recommended replacement models are VD4-24/630-16 and HD4-24/630-16.

  1. Explication du code modèle
Segment de codeSignificationDescription
HPACode de série de produitsABB indoor SF6 medium voltage circuit breaker series, sharing the same platform with HD4 series, applicable for SafeSix switchgear
24Rated voltage level24kV (Norme CEI, matching domestic 24kV power system)
612Combination of current and breaking capacity6 stands for 630A rated current; 12 stands for 12.5kA rated short-circuit breaking current
CStructure & configuration codeConfiguration standard, fixed type or withdrawable type (depends on switchgear type)
  1. Paramètres techniques de base (2026 Official Manual Version)
ParamètreValeurBase standardRemarques
Tension nominale (Un)24kVCEI 62271-100Max operating voltage: 27.5kV
Courant nominal (Ir)630UNCEI 62271-100Continuous operation at ambient temperature 40℃
Rated Short-circuit Breaking Current (Isc)12.5leCEI 62271-1003-second short-circuit withstand
Courant de tenue nominal de courte durée (Icw)12.5kA/3sCEI 62271-100Thermal stable current
Rated Peak Withstand Current (Ipk)31.5leCEI 62271-100Dynamic stable current
Mécanisme de fonctionnementSpring energy storageCEI 62271-100Manuel / electric operation optional
Insulating MediumSF6 gasCEI 62271-100Rated pressure: 0.45MPa @20℃
Degré de protectionIP4XCEI 60529Cabinet installation condition
Endurance mécanique10,000 opérationsABB technical specificationStandard operation cycle
Endurance électrique100 foisCEI 62271-100Rated short-circuit breaking times
PoidsEnviron. 85kilosABB technical specificationExcluding accessories
Numéro de commande1VYN400551-XXXOfficial ABBSubject to actual configuration
  1. Cross-brand Compatibility Comparison (MV SF6 Circuit Breaker)
Modèle ABBSchneiderSiemensEatonTechnical Differences
HPA24/612CMVnex 24/630-12.53AH4 24kV/630A/12.5kAPower Xpert 24kV/630A/12.5kAABB HPA series adopts SF6 insulation and spring mechanism, fits SafeSix switchgear
Remplacement: VD4-24/630-16HVX 24/630-163AH5 24kV/630A/16kAPower Xpert 24kV/630A/16kAVD4 adopts vacuum insulation with 30,000 mechanical operations and superior environmental performance
  1. Full HPA Series Model List
ModèleTension nominaleCourant nominalCapacité de coupureScénarios d'application
HPA12/616C12kV630UN16leDistribution d'énergie industrielle, substation
HPA12/620C12kV630UN20leIndustrie lourde, large factories
HPA12/1225C12kV1250UN25leRegional substation, power plant
HPA12/1631C12kV1600UN31.5leLarge industrial users, hub substation
HPA24/612C24kV630UN12.5le24kV power distribution system, small substation
HPA24/616C24kV630UN16le24kV power distribution system, medium-sized factories
HPA24/1220C24kV1250UN20le24kV regional substation
HPA24/1625C24kV1600UN25le24kV large industrial projects
HPA36/616C36kV630UN16le36kV power distribution system
  1. Défauts courants & Directives d'entretien
Phénomène de défautCauses possiblesÉtapes de dépannageSuggestions d'entretien
Failure to close1. Incomplete energy storage1. Check energy storage indicator1. Test manual energy storage
2. Abnormal control voltage2. Measure control circuit voltage (DC220V/AC220V)2. Repair control circuit fault
3. Interlock not released3. Inspect mechanical interlock status3. Adjust interlock device
Failure to open1. Burnt trip coil1. Mesurer la résistance de la bobine (normal: approx.100Ω)1. Replace trip coil
2. Tripping mechanism stuck2. Test manual opening operation2. Clean and lubricate tripping mechanism
3. Low SF6 gas pressure3. Check SF6 pressure gauge (≥0.4MPa)3. Refill gas or inspect air leakage
SF6 gas leakage1. Aging sealing parts1. Detect leakage with SF6 leak detector1. Replace sealing components
2. Loose connectors2. Check all connecting parts2. Fasten connectors
3. Shell crack3. Observe shell appearance3. Replace shell for severe damage
Excessive contact resistance1. Contact wear1. Measure contact resistance (≤50μΩ)1. Replace contacts
2. Dirty contact surface2. Inspect contact surface2. Clean contact surface
3. Loose connecting bolts3. Check bolt tightening torque3. Fasten bolts per standard torque
  1. Environnement d'application & Cas industriels

6.1 Scénarios applicables

24kV industrial power distribution system (chimique, métallurgie, mining industry)

Secondary substation of urban power grid

Commercial buildings and infrastructure (airport, hôpital, centre de données)

Renovation projects matching SafeSix switchgear

6.2 Inapplicable Scenarios

Altitude above 2000m (derating required, derating factor: 0.9 per 1000m)

Severe corrosive environment (seaside, chemical zone, special anti-corrosion treatment required)

Frequent short-circuit breaking operation (exceed 10% of rated breaking times)

Areas with strict environmental requirements (SF6 has strong greenhouse effect, VD4 vacuum circuit breaker is preferred)

6.3 Cas d'application typiques

Cas 1: 24kV Power Distribution Renovation for Chemical Plant

Application: Replace old oil-minimum circuit breakers to improve power supply reliability

Solution: 8 sets HPA24/612C matched with ABB REF542 protection relay

Effect: Fault outage duration reduced by 80%, maintenance cost cut by 50%

Cas 2: 24kV Traction Substation for Urban Rail Transit

Application: Protection for traction transformer and feeder line

Solution: 4 sets HPA24/612C with withdrawable structure for quick replacement

Effect: Meet high reliability requirements of rail transit, MTTR<30 minutes

  1. Air Freight Compliance & Certification Information

7.1 Air Freight Compliance

Hazard Classification: Non-dangerous goods (no lithium battery, no explosive materials)

IATA Shipping Category: General cargo

Packaging Standard: Comply with ISTA 3A standard to avoid SF6 seal damage caused by transportation vibration

Note: Close SF6 inflation valve during transportation to prevent gas leakage

7.2 Certification Documents

CE Certificate No.: 1YHA000091 (universal for HPA series)

IEC Standard Approval: CEI 62271-100:2017

China National Standard Approval: FR 1984-2014 High-voltage Alternating Current Circuit-breakers

Environmental Certification: SF6 gas recovery complies with IEC 62271-4

  1. Sélection du modèle & Replacement Suggestions
  2. Model Confirmation: HPA series is fully discontinued. It is recommended to contact ABB customer service 400-810-8888 and provide nameplate photos to confirm detailed configuration.
  3. Solutions de remplacement

First choice: VD4-24/630-16 (vacuum type, 30,000 mechanical operations, SF6-free eco-friendly design)

Alternative choice: HD4-24/630-16 (SF6 type, same platform as HPA, direct replacement without switchgear modification)

  1. Achat de pièces de rechange: Limited stock of HPA series spare parts. Pre-order via authorized ABB distributors in advance or plan overall equipment upgrading.

ABB HPA24/612C is a 24kV indoor SF6 medium voltage circuit breaker with rated current 630A and rated short-circuit breaking current 12.5kA. It is compatible with SafeSix switchgear and has been discontinued. The recommended replacement models are VD4-24/630-16 and HD4-24/630-16.