Schneider TeSys D / TeSys Deca series, 3-pole with 3 contacts principaux NON. Designed for three-phase motors, CVC, pompes à eau, fans and other load control. It comes with built-in 1NO + 1Caroline du Nord auxiliaire contacts (NC is mirror contact for safety circuits).
✅ Spécifications de base
Poteaux: 3P. (3 AUCUN contact principal)
Rated operational current AC-3 @ 440V: 40 UN
Matched motor power @ 380/400V: 18.5 kW
Max operational voltage (Ue) for power circuit: 690 V
Courant thermique conventionnel (je): 60 UN
Contacts auxiliaires intégrés: 1NON (14) + 1Caroline du Nord (22)
Montage: 35 mm DIN rail or screw fixing
Dimensions hors tout: W55 × H122 × D120 mm
Terminaux: EverLink anti-loosening screw terminals (new version with suffix A)
Certifications: CCC, CEI 60947-4-1, UL, ASC, marine certification
✅ Model Suffix Definition (Exemple de modèle complet: LC1D40AM7C)
UN: New Deca version (old version without A: LC1D40M7C, interchangeable directement)
M.: 220 Bobine V CA (50/60 Hz)
F: 110 V et; Q: 380 V et; B: 24 À DC; BD: standard 24 Bobine V CC
7: 50/60 Hz universel; C: China domestic version
Common stock models:
LC1D40AM7C (220ACC), LC1D40AF7C (110ACC), LC1D40AQ7C (380ACC), LC1D40ABD (24VCC)
✅ Matching Accessories
Relais de surcharge thermique: LRD3353C (adjustment range 23–32 A) pour 18.5 moteurs kW
Bloc de contacts auxiliaires: LA1DN (expand auxiliary contacts)
Verrouillage mécanique: LA9D40 (for star-delta & forward/reverse interlock)
Coil surge suppressor: LA4DA
Time delay attachment, busbar connectors, etc..
✅ Sélection & Remplacement
- Old-to-new replacement: LC1D40 → new LC1D40A, dimensions identiques, mounting holes and wiring, prêt à l'emploi.
- Adjacent frame size: smaller LC1D32; larger LC1D50.
- Economy alternative: Easypact D3N LC1N40.
- Equivalent national: CJX2-4011.
✅ Applications typiques
Ventilateurs, pompes à eau, compresseurs d'air, climatisation centrale, convoyeurs, démarreurs étoile-triangle, forward/reverse control cabinets (AC-3 motor duty); also for AC-1 resistive loads (éléments chauffants).
✅ Installation Instructions
Couple: Main circuit terminals = 5 N·m; control circuit = 1.7 N·m
Max ambient temperature: 60 °C; fréquence de fonctionnement maximale: 3600 cycles/heure
DC coil version requires polarity: A1 = positive, A2 = negative
Matched thermal relay for LC1D40 (18.5kW @ 380V): LRD3353C, setting range 23~32 A, Classe 10A
- LRD3353C Overload Current Setting Table
1) Setting Rule (Obligatoire)
Set the thermal relay knob to motor nameplate full-load current (FLORIDE), NOT the 40A contacteur notation.
380V 18.5kW 3-phase motor: courant nominal ≈ 32 A → set knob directly to 32 UN (pleine échelle).
For fan-type motors, heavy starting & jogging fréquent: set to 100%~105% of FLA; never exceed 115%.
Température ambiante >40°C or enclosed cabinet: reduce setting by 5%~10%.
2) LC1D Series Contactor + LRD Thermal Relay Matching List
| Contactor Model | Courant AC-3 | Motor Power @ 380V | Relais thermique correspondant |
| LC1D40A | 40 UN | 18.5 kW | LRD3353C |
| LC1D50A | 50 UN | 22 kW | LRD3355C |
| LC1D65A | 65 UN | 30 kW | LRD3357C |
| LC1D80A | 80 UN | 37 kW | LRD3359C |
| LC1D95A | 95 UN | 45 kW | LRD3361C |
| LC1D115 | 115 UN | 55 kW | LRD3363C |
| LC1D150 | 150 UN | 75 kW | LRD3365C |
High-current older models (being upgraded to AKUE wide-voltage coil)
LC1D170, LC1D205, LC1D245, LC1D300, LC1D410
- 4-Pole Models (LC1DT, AC-1 resistive loads: chauffage, 3-phase 4 fils)
4NON Contacts principaux (LC1DTxxA)
LC1DT20A, LC1DT25A, LC1DT32A, LC1DT40A, LC1DT60A, LC1DT80A
2NON + 2NC Main Contacts (LC1Dxx8)
LC1D128, LC1D188, LC1D258, LC1D40008, LC1D65008
III. Coil Voltage Suffix Code
AC Coils (50/60Hz universel, suffixe 7)
B7: 24 V et
E7: 48 V et
F7: 110 V et
M7: 220 V et (le plus courant)
P7: 230 V et
Q7: 380 V et
DC Coils (suffix D)
BD: 24 À DC (standard DC coil)
ED: 48 À DC
DG: 125 À DC
End-of-model Letters
C = Domestic China TeSys Deca version (local stock)
A = New EverLink anti-loosening terminals; no A = old terminal version
✅ Full stock model examples:
LC1D40AM7C (220ACC), LC1D40AF7C (110ACC), LC1D40AQ7C (380ACC), LC1D40ABD (24VCC)
- Contacteurs inverseurs (LC2D, Forward/Reverse Control)
LC2D09A, LC2D12A, LC2D18A, LC2D25A, LC2D32A, LC2D40A, LC2D50A, LC2D65A, LC2D80A, LC2D95A
Built-in mechanical + electrical interlock; no extra LA9D40 required.
- Full LRD Thermal Relay Matching List (for LC1D)
- Low current range (0.1~32 A): LRD01C ~ LRD22C
- 40A and above (23~104 A): LRD33 series
LRD3353C: 23–32 A → LC1D40A (18.5 kW)
LRD3355C: 30–40 A → LC1D50A
LRD3357C: 37–50 A → LC1D65A
- Règles de remplacement
- Old LC1D40M7C → new LC1D40AM7C: entièrement interchangeable (même empreinte, montage & câblage).
- Older high-current LC1D115 / LC1D150 → upgrade to LC1D115AKUE / LC1D150AKUE (100–250V AC/DC wide-voltage coil).