V810iCN-080, manufactured by Japan Fuji HAKKO Electric. 10.4-inch resistive touch-screen IHM, Alimenté par courant alternatif, built-in Ethernet, obsolete discontinued model.
-080: Firmware version suffix; hardware base model = V810iCN
1|Model Decoding V810iCN-080
| Segment | Définition |
| V810 | 10.4‑inch unit |
| je | High‑performance version: On‑board Ethernet LAN port |
| C | TFT‑LCD, VGA 640×480 resolution |
| N | AC100‑240V AC power supply; no expansion option port |
| ‑080 | Firmware revision number |
⚠️V810iCN: No external option unit port; analog resistive touch screen, 8 physical function keys on panel edge.
2|Core Hardware Specifications
| Article | Paramètre |
| Afficher | 10.4″ Écran LCD couleur TFT |
| Résolution | 640×480 VGA |
| Couleurs d'affichage | 65536 couleurs |
| Rétroéclairage | Rétroéclairage LED |
| Type tactile | Tactile résistif analogique, 1024×1024 |
| Physical Keys | 8 side function switches |
| Alimentation | AC100‑240V ±10% |
| Consommation d'énergie | Environ. 70Virginie |
| On‑board LAN | RJ45 Ethernet 10/100Mbps |
| Serial Port CN1 | D‑SUB9 RS232C/RS422/485 |
| MJ Port | 8‑Pin modular interface ×2, RS232‑485 |
| USB | USB‑A, USB‑MiniB |
| Carte mémoire | CF‑card slot |
| Backup Clock | Lithium coin battery |
| Front‑panel Protection | IP65 |
| Température de fonctionnement | 0‑50℃ |
Overall & Cut-out Dimensions
Dimension hors tout: 303(W)×231(H)×62(D) mm
Panel cut-out: 274 × 204 mm
3|Communication Capabilities
Supports simultaneous communication with up to 8 PLC devices, multi-brand PLC protocols supported; capable of gateway data forwarding.
Logiciel de programmation: V-SFT (configuration software for V8 series).
Fonctions prises en charge: Gestion des recettes, journalisation des alarmes, historical data, CF-card storage, macro script.
4|Lifecycle & Options de remplacement
✅V8 series is discontinued. V810iCN-080 is an end-of-life spare part, only second-hand / refurbished stock available.
OEM Upgrade Replacement (Fuji HAKKO V9 series)
- V9100iS-080 (10.4-pouce, VGA, Alimentation CA, cut-out compatible, project conversion required within V-SFT)
Note: V8 project files cannot be directly downloaded to V9 hardware; project migration via software conversion is mandatory.
Domestic Compatible Replacements (Cut-out reference)
Weinview MT8102iP; Inovance IT7100; FLEXEM FE6100C; MCGS TPC1061Ti.
⚠️Cut-out dimension 274×204 mm: Most standard 10-inch HMIs on market have different cut-out sizes, cabinet modification may be required.
5|Second-hand Spare-part Inspection Checklist
- Test de mise sous tension: Check backlight for yellowing or flickering; backlight degradation is a common failure.
- Touch verification: Full-screen touch test, no drift or dead zones.
- Battery inspection: Built-in coin-cell battery; flat battery causes loss of clock and SRAM recipe data.
- Full-interface test: Port Ethernet, two MJ serial ports, D-SUB9 serial port, USB read-write functionality.
- CF-card slot read-write test.
- Read firmware version to confirm-080 revision.
6|Common Faults
- Touch failure: Panneau tactile endommagé; touch glass can be replaced independently.
- Black screen at power-up: Power-board fault or LED backlight damage.
- Time reset: Depleted backup lithium coin battery.
- CF-card read-write failure: Poor contact of card slot.
- Communication instable: Oxidation of MJ connectors, high-failure-rate interface.
Fuji HAKKO MONITOUCH V8 Series HMI Full Model List
V8 series discontinued in 2017, logiciel de programmation: V-SFT; suffix definition: N=AC100-240V AC supply, D=DC24V DC supply, i=built-in Ethernet port.
Suffixe-0XX indicates firmware version (e.g.-080), not part of hardware model designation.
Définition du code modèle
| Character | Signification | ||
| je | On‑board RJ45 Ethernet LAN (high‑function version); no “je” = no Ethernet | ||
| S | SVGA 800×600 TFT | ||
| C | VGA 640×480 TFT | ||
| T | VGA 640×480 TFT (RGB/video expansion capable) | ||
| X | XGA 1024×768 TFT | ||
| T | QVGA TFT; M. | Monochromes; CH | 7.5‑inch handheld with enable switch |
| N | AC100‑240V power; D | DC24V power | |
| M. | Matrix touch; no “M.” = analog resistive touch |
Full Series Grouped by Screen Size
5.7-inch|QVGA 320×240|DC24V(D) power only
V806 series, no AC variants
V806MD: Affichage monochrome, pas d'Ethernet
V806iMD: Affichage monochrome, built-in Ethernet
V806CD: STN color, pas d'Ethernet
V806iCD: STN color, built-in Ethernet
V806TD: TFT color, pas d'Ethernet
V806iTD: TFT color, built-in Ethernet
7.5-inch Handheld Unit|VGA 640×480|With Dead-man Safety Enable Switch
V808CH: Handheld, pas d'Ethernet
V808iCH: Handheld, built-in Ethernet
DC24V power supply only
8.4-inch|800×600(SVGA)/640×480(VGA), CA(N)/CC(D) power options
SVGA(800×600):
V808SDN (CA) / V808SD (CC)
V808iSDN (CA) / V808iSD (CC)
VGA(640×480):
V808CDN (CA) / V808CD (CC)
V808iCDN (CA) / V808iCD (CC)
10.4-inch|V810 Series (V810iCN-080 belongs to this family)
SVGA 800×600
V810SN (CA) / V810S (CC)
V810iSN (CA) / V810iS (CC)
VGA 640×480 C-type (Standard TFT)
V810CN (CA) / V810C (CC)
V810iCN (CA) / V810iC (CC)👉 Base hardware unit of your model
VGA 640×480 T-type (RGB/video option module support)
V810TN (CA) / V810T (CC)
V810iTN (CA) / V810iT (CC)
Matrix-touch variants available (V810iTM-N, V810TM-N etc.), rarely deployed in industry.
12.1-inch SVGA 800×600
V812SN (CA) / V812S (CC)
V812iSN (CA) / V812iS (CC)
15-inch XGA 1024×768 (Flagship Model)
V815iXN (CA) / V815iX (CC)👉V815 only available with Ethernet “je” version
Référence de sélection rapide
- Avec “je” = On-board RJ45 Ethernet; no “je” = No Ethernet interface
- Suffix N = AC100-240V; Suffix D = DC24V
- V806 & V808CH series: DC24V seulement, no AC models
- -080,-070: Firmware revision only, hardware remains unchanged. Exemple: V810iCN-080 = V810iCN hardware + 080 micrologiciel.
OEM Direct Replacement (Série V9)
| Legacy V8 Model | Recommended V9 Replacement | Remarques |
| V810iCN‑080 | V9100iS‑080 | Cut‑out compatible, project conversion required in V‑SFT |
| V808iCDN | V9080iSD‑080 | |
| V812iSN | V9120iS‑080 | |
| V815iXN | V9150iX‑080 |
V8 project files cannot be directly downloaded to V9 hardware; perform project conversion within software for migration.
Common Second-hand Unit Failure Patterns
- Resistive touch aging: Touch drift or partial non-response
- Depleted internal lithium coin-cell: Loss of real-time clock and SRAM recipe data
- Oxidation of MJ-8P serial connectors leading to unstable communication
- LED backlight ageing: Yellowing and dim display
Application Scenarios for Fuji HAKKO MONITOUCH V806iMD
V806iMD: 5.7-pouce, 16-level grayscale monochrome STN display, QVGA 320 × 240, Alimentation DC24V, “je” for built-in Ethernet, multi-serial ports (D-SUB9 + dual MJ-8P), 512Ko de SRAM, contact résistif; discontinued hardware, programming software V-SFT.
Points forts: Monochrome grayscale, faible consommation d'énergie, good sunlight readability, Ethernet plus multi-serial ports. Suited for equipment without demand for complex color graphics yet requiring network data upload. Compared with V806MD, integrated Ethernet enables data upload, SCADA host connection and multi-device gateway functions.
Key Feature-Driven Application Attributes
- 16-level monochrome grayscale: Optimized for text, numeric values and simple bar graphs; not suitable for complex color diagrams or process flowcharts; superior sunlight legibility versus early-generation color STN HMIs.
- Ethernet intégré: PLC data upload, alarm notification upload, multi-PLC gateway functions; V806MD (non-i variant) supports serial communication only.
- Three serial communication channels: D-SUB9 + MJ1/MJ2, connect multiple PLCs, temperature controllers and inverters simultaneously; jusqu'à 8 external devices concurrent communication.
- DC24V supply: Direct power from cabinet 24VDC system, no AC power circuit required.
- IP65 front panel for cabinet panel mounting; CF-card & USB support for recipe storage, alarm logging and data sampling.
Industries typiques & Equipment Use-cases
1|Stand-alone Compact Machinery (Panneau de commande local)
Priority on parameter setup, status monitoring and alarm viewing; complex color visuals not required
Auxiliary injection-molding equipment, séchoirs, mélangeurs, mélangeurs
Compact packaging machines: scellants, small filling machines, étiqueteuses
Matériel de presse, compact presses, simple tooling fixtures
Machines textiles: machines à enrouler, compact textile finishing equipment
Fonctions: Configuration des paramètres, comptage de la production, fault alarm display, simple recipe recall; Ethernet transmits production figures and alarm events to plant-level host system.
2|Thermal & Temperature-controlled Equipment
Industrial furnaces, fours, small heat-treatment furnaces, reflow ovens, curing furnaces
Environmental test chambers, température constante & humidity cabinets
Avantages: Good visibility under strong workshop lighting; multi-serial ports connect PLC plus multiple temperature controllers concurrently; Ethernet uploads temperature trends and alarms to central control.
3|Water-treatment, Environnemental & Fluid-handling Compact Control Cabinets
Small-scale wastewater equipment, water reclamation, chemical dosing control systems
Local pump-station control cabinets, compact water-purification units
Use-case: Local panel monitoring for pump-valve status, liquid level and flow readings; alarm event logging; Ethernet connects to plant SCADA for data acquisition, no complex color flow charts needed.
4|Workstation Nodes & Auxiliary Stations on Production Lines
Stand-alone workstation controllers on conveyor lines, sorting auxiliary panels
Local control units for material handling conveyors
Single V806iMD connects multiple sub-station PLCs via multi-serial ports, performs data exchange via gateway function, accesses factory LAN through Ethernet.
5|Machinery & Container-mounted Control Cabinets (DC24V System)
Vehicle-mounted industrial equipment, mobile packaged units; container-type compact system control cabinets
Direct compatibility with 24V on-board power supply; IP65 front-panel withstands dust and vibration; good readability under bright ambient light.
6|Retrofit & Spare-part Replacement for Legacy Installations
Replacement of failed original V806iMD on existing machines.
⚠️Avoid arbitrary substitution with color HMIs: Cabinet cut-out dimension 289 × 216.2 mm; most 5.7-inch third-party HMIs feature different cut-out dimensions, cabinet machining modification is required.
❌Unsuitable Applications for V806iMD
- Projects requiring extensive color process flowcharts, animations and image display; select V806iCD / V806iTD color variants instead.
- Applications requiring high-definition color trend curves and sophisticated visualization.
- Severe high-humidity and corrosive environments (enclosed protective cabinet required).
V806iMD vs V806MD Selection Comparison
| Modèle | Ethernet | Application Difference |
| V806iMD | ✅On‑board LAN | Data upload, SCADA interconnection, multi‑device gateway, network‑enabled factory projects |
| V806MD | ❌No Ethernet | Stand‑alone local operation only, serial‑link to PLC, no upper‑level data transmission |
OEM Replacement Model
Legacy V806iMD discontinued; recommended OEM successor: TS2060i (5.7-pouce, cut-out compatible, DC24V, on-board Ethernet, affichage couleur; V-SFT project conversion and migration required).
Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur