Marque: LS Électrique | Produit: LA63N Series MCB
Description du modèle:
LA63N: Code de série, 6kA pouvoir de coupure
4P.: 4-pôle (3 étapes + Neutre, 4 connection poles)
J10: D-curve trip, rated current In=10A
✅ Core Technical Data
| Article | Spécification |
| Modèle | LA63N 4P D10 |
| Courant nominal entrant | 10UN |
| Courbe de déplacement | Type D: Instantaneous trip at 10~16In. Suitable for motors, transformers and inductive loads to avoid tripping on inrush current |
| Tension de fonctionnement nominale Ue | C.A. 400 V (3-phase); DC 125V |
| Rated Short-circuit Breaking Capacity Icn | 6le (IEC60898) |
| Poteaux | 4P. (L1/L2/L3+N, simultaneous pole disconnection) |
| Montage | 35mm Montage sur rail DIN |
| Classe de protection | IP20 (front face) |
| Normes | IEC60898-1, GB/T10963.1 |
| Endurance mécanique | 20,000 opérations; Endurance électrique: 10,000 opérations |
| Température ambiante | -5℃ ~ +40℃ |
📌 Application
4P MCB with D-curve, for power circuits: 3-moteurs phase, onduleur saisir, transformateurs, solenoid valves and inductive load distribution. It protects 3 phases and neutral line simultaneously and prevents nuisance tripping caused by high starting inrush current. Not suitable for general lighting (C-curve preferred for lighting).
🧩 Equivalent Replacement Models
- Legacy LS model: BKN-4P D10 (LA63N is upgraded version of BKN)
- Alternatives nationales: CHINT NB63-4P D10, Delixi DZ47s 4P D10
- Alternatives importées: Schneider iC65N 4P D10, ABB S204M D10
⚠️ Sélection & Notes d'installation
- D trip characteristic: Instantaneous trip at 10~16 times rated current, immune to motor starting inrush; Courbe C: 5~ 10 pouces; Courbe B: 3~5In.
- 4P feature: Neutral line disconnects together with phase conductors for safe maintenance; 3P+N is available if neutral disconnection is not required.
- Breaking capacity 6kA: Sufficient for factory end cabinets and small power panels; upgrade to LA63H (10le) when short-circuit current exceeds 6kA.
- No residual current protection. If earth leakage protection is needed, select LA63N series RCBO.
📦 Customs HS Code Reference
8536200000 (Basse tension disjoncteur, rated voltage ≤1000V)
🛠️ Dépannage
Déplacements immédiatement après la fermeture: Court-circuit / load earth fault
Trips when motor starts: Verify wrong C-curve selection or excessive line voltage drop
Déplacements après avoir couru pendant un certain temps: Surcharge, check if continuous load current >10UN
Can Schneider MCB E9CN-4P-C16 directly replace LA63N-4P-D10?
Conclusion: Direct replacement is NOT allowed
Although the DIN rail dimension, pole count and breaking capacity allow physical fitting, rated current and trip curve are inconsistent, leading to mismatched protection characteristics.
Comparaison des paramètres
| Article | LS LA63N-4P-D10 (Original) | Schneider E9CN-4P-C16 (Candidate) | Risque |
| Courant nominal entrant | 10UN | 16UN | Overload protection threshold increased, cable loses protection. The original circuit cable is sized for 10A. Replaced with 16A, cable may overheat without breaker tripping, risque d'incendie |
| Courbe de déplacement | Type D: Instant trip 10~16In (100~160A) | Type C: Instant trip 5~10In (80~160A) | Original for motor/inductive load. D-curve avoids starting inrush; C-curve tends to nuisance trip during motor startup |
| Poteaux | 4P. | 4P. | ✅ Matched, tous les pôles se déconnectent ensemble |
| Icn nominal de coupure de court-circuit | 6le | 6le | ✅ Matched |
| Dimension | 4P.,72mm, rail DIN35 | 4P.,72mm, rail DIN35 | ✅ Physiquement montable |
Deux options de remplacement
✅Option 1: Remplacement entièrement équivalent (Recommandé, protection inchangée)
Pièce Schneider: E9CN-4P-D10
Entrée=10A, voyage D, 4P.,6le; la protection électrique correspond entièrement au LA63N-4P-D10 pour un échange direct.
⚠️Option2: Si E9CN-4P-C16 doit être utilisé (Rarement acceptable)
Toutes les conditions ci-dessous doivent être remplies:
- Courant de fonctionnement continu de la charge ≤10A
- Calibre du câble et des bornes revérifié pour 16A
- La charge n'est PAS un moteur en ligne directe / transformateur ou charge inductive à appel élevé (sinon trébuchement au démarrage)
- Dessins, calendrier de protection et certificats de test mis à jour et ré-approuvés
Non recommandé pour les circuits électriques industriels.
Notes complémentaires
- La courbe de surcharge thermique est identique pour les types C et D. La différence réside uniquement dans le déclenchement instantané par court-circuit magnétique.
- La capacité du terminal est similaire, compatible avec câblage haut en bas et sortie.
- Même code SH: 8536200000.
Comment identifier le type de charge pour une sélection appropriée du MCB
Flux de travail principal: Classer le type de charge → Déterminer le courant de fonctionnement continu → Sélectionner la courbe de déclenchement (B/C/D) → Choisir le courant nominal In → Vérifier le pouvoir de coupure en court-circuit Icn → Sélectionner le nombre de pôles
- Identifier le type de charge & Courbe de déplacement correspondante
La protection contre les surcharges thermiques est identique pour B/C/D; la différence est un déclenchement magnétique instantané en cas de court-circuit/courant d'appel.
| Type de voyage | Portée de déclenchement magnétique instantanée | Applications typiques | Remarques |
| Type B | 3~5 po | Electronique basse tension, appareils de précision, petits circuits CC, boucles de capteurs | Très sensible aux courts-circuits; rarement utilisé pour l'alimentation secteur industrielle |
| Type C | 5~10 po | Éclairage, prises de courant, charges résistives, petits ventilateurs, alimentation générale de l'armoire | Le plus courant pour la distribution commerciale/ordinaire; faible charge d'appel |
| Type D | 10~16 po | Moteurs en ligne directe, transformateurs, électrovannes, batteries de condensateurs, charges inductives | Withstand high starting inrush and prevent nuisance tripping |
Quick reference:
Charges résistives (radiateurs, lampes à incandescence) → C-curve
Inductive loads with high inrush (moteurs, transformateurs) → D-curve
Precision low-power DC/electronic circuits → B-curve
- Calculate Load Current and Select MCB Rated Current In
1) Charge résistive (Chauffage, Resistor) Monophasé
Simplified estimation for 380V 3-phase motor: ~2A per kW
Exemple: 3Moteur triphasé kW, rated current≈6A; starting current ~6~8×In → D-curve selected.
Selection rule: MCB rated current ≥ motor rated current and withstand starting inrush.
Note: MCB mainly provides short-circuit protection. Motor overload shall be protected separately by thermal relay. MCB is NOT intended as primary overload protection for motors.
Margin Rule
Continuous duty load: Dans ≥ 1.1 × continuous load current
Intermittent load: In ≥ continuous load current
❌ Never arbitrarily increase In: L'intensité admissible du câble doit correspondre à la valeur nominale du MCB. Sinon le câble brûle sans déclencher le disjoncteur.
- Sélectionnez le nombre de pôles
1P.: Phase de protection uniquement, connexion permanente neutre; pour l'éclairage
1P+N: Phase et neutre câblés au disjoncteur, phase protégée uniquement; circuits de prise
2P.: Phase + neutre tous deux protégés, déconnexion simultanée; équipement monophasé
3P.: 3-phase 3 fils, déconnecter trois phases; 3-moteurs phase
3P+N: 3 étapes + neutre, neutre non déconnecté; distribution triphasée équilibrée
4P.: 3 étapes + neutre, le neutre se déconnecte ensemble; Système TN-S, isolation complète pour la maintenance, Entrée UPS et onduleur triphasé
LS LA63N-4P-D10 ci-dessus: 4-pôle, déconnexion synchronisée du neutre.
- Pouvoir de coupure en court-circuit Icn (Souvent négligé)
Icn: Courant de court-circuit maximum que le disjoncteur peut interrompre en toute sécurité.
Armoire de bout / distribution ordinaire en atelier: 6le (LSLA63N, Schneider E9CN sont 6kA) suffisant
À proximité d'un transformateur ou d'un panneau principal avec un courant de court-circuit présumé élevé: Sélectionnez 10 kA,15Le modèle de kA
Si courant de court-circuit réel MCB Icn: Breaker may fail and explode during short circuit, cannot cut fault.
- On-site Checklist for Load Identification
✅ Check equipment nameplate:
- Resistive or coil/motor/transformer load
- Tension nominale, courant nominal, puissance nominale
- Starting method: DOL / Étoile-triangle / Démarreur progressif
DOL motor has maximum inrush → D-curve; soft starter reduces inrush, C-curve acceptable in some cases
✅ Field judgment:
Obvious hump and current surge at power-on → High-inrush inductive load → D-curve
Smooth startup without current spike → Resistive / general power supply → C-curve
- Common Pitfall Case (Matching previous model comparison)
Original circuit: LS LA63N-4P-D10 (10A D-curve)
Charger: Small DOL 3-phase motor
If replaced with Schneider E9CN-4P-C16:
- In rises from10A→16A: Overload protection threshold increased, original cable loses overload protection
- C-curve magnetic trip at5~10In: L'appel de démarrage du moteur peut tomber dans la plage de déclenchement instantané → Déclenchement immédiat au démarrage
- Procédure de sélection complète des MCB
- Identifier le type de charge: Résistif / Inductif (Moteur/Transformateur) / Électronique
- Lire la puissance/courant sur la plaque signalétique et calculer le courant de fonctionnement continu
- Sélectionnez la courbe de déclenchement B/C/D en fonction de la caractéristique d'appel
- Choisissez le MCB classé In et vérifiez l'intensité admissible du câble correspondante.
- Calculez le courant de court-circuit présumé au point d'installation et sélectionnez Icn
- Sélectionnez le nombre de pôles en fonction du système de distribution (TN-S/TN-C) et besoin d'entretien
- Contrôle du déclassement: Température ambiante et déclassement pour les disjoncteurs montés de manière dense dans l'armoire
Facteurs à prendre en compte pour la sélection des pôles MCB
Concept de base: Le nombre de pôles définit quels conducteurs sont commutés et protégés. La sélection doit tenir compte du type de système de distribution, type de charge, sécurité de l'entretien, Exigences en matière de courant de défaut neutre et de protection.
Poteaux disponibles:1P.,1P+N,2P.,3P.,3P+N,4P.
- Type de système de distribution (TN-C / TN-S / TN-C-S)
Critère principal, détermine si la ligne neutre peut être déconnectée.
TN-C (PEN combiné): Le conducteur PEN ne doit PAS être déconnecté. N'utilisez PAS 2P/4P avec commutation neutre; PEN reste continu.
TN-S / TN-C-S (Séparer N et PE): Le neutre est indépendant. Décidez s'il faut passer au neutre selon les besoins.
Si le neutre peut transporter une surtension/un courant de défaut et une isolation complète requise pendant la maintenance → 4P (3-phase)/2P.(monophasé)
Charge triphasée équilibrée avec un courant neutre négligeable, déconnexion du neutre inutile →3P+N (le neutre passe sans commuter)
- Charge monophasée ou triphasée
Charge monophasée: 1P.,1P+N,2P.
1P.: Seul le conducteur de phase est déconnecté, le neutre reste connecté. Risque: Le neutre peut devenir excité si le neutre en amont se brise; principalement pour l'éclairage.
1P+N: Phase et neutre connectés au disjoncteur, seule la phase est protégée, neutre pas de protection contre les surcharges/courts-circuits, pôles ouverts simultanément.
2P.: Phase et neutre protégés et commutés ensemble; préféré pour les prises et les équipements monophasés nécessitant une isolation complète.
Charge triphasée:3P.,3P+N,4P.
3P.: Protéger et déconnecter uniquement les conducteurs triphasés; moteurs triphasés équilibrés sans neutre.
3P+N: 3 phases protégées, neutre câblé au disjoncteur mais le neutre n'a pas de protection contre les surcharges/courts-circuits, peuvent basculer ensemble ou passer à travers; pour charge triphasée déséquilibrée.
4P.: L1/L2/L3+N tous protégés, déconnexion simultanée de phase et de neutre. LS LA63N-4P appartient à ce type.
- Sécurité de l'entretien (Critique)
Isolement complet requis: Tous les conducteurs sont hors tension après la coupure du disjoncteur. Monophasé →2P; Triphasé →4P.
Exemple: Entrée onduleur, UPS, puissance principale de l'armoire de commande. 4P déconnexion complète des pôles requise avant l'ouverture de l'armoire pour l'entretien.
Moteur d'extrémité ordinaire sans neutre: Seules trois phases nécessitent une isolation pour la maintenance; 3P est suffisant.
⚠️ Attention: 1Le disjoncteur P laisse le neutre connecté au système en amont. Si le neutre amont est cassé, l'équipement peut devenir sous tension. 1P n'est pas recommandé pour l'accès de maintenance.
- Surcharge neutre, Courant de court-circuit et harmonique
Charge triphasée déséquilibrée, grande quantité de VFD / alimentation à découpage: Un courant harmonique important circule sur le neutre, le neutre peut surcharger.
✅ Le conducteur neutre nécessite une protection → MCB 4P.
Charge de moteur triphasée pure équilibrée, courant neutre presque nul: 3P suffisant, pas besoin de 4P.
Scénario typique: Armoire de commande avec de nombreux automates, Alimentations CC. La sommation de la troisième harmonique rend le courant neutre encore plus grand que le courant de phase → 4P requis pour protéger le neutre.
- Compatibilité avec la protection contre les fuites à la terre (RCBO / MCB+ELM)
La détection du courant résiduel nécessite la détection de tous les courants entrants et sortants, y compris le neutre.
Disjoncteur monophasé: Généralement 1P+N ou 2P
3-fuite à la terre entre phases: 3P+N /4P. Le neutre doit passer par CT, sinon la protection contre les fuites échoue.
Si un module de fuite est prévu, la configuration des pôles doit inclure le fil neutre.
- Surtension du système & Exigence d'isolement
Risque de surtension, tension inverse, circuit de transfert de puissance double: Déconnexion complète des pôles (2P/4P) recommandé pour empêcher le retour de tension via le neutre et endommager l'équipement en aval.
Circuit d'alimentation ordinaire sans risque particulier de surtension: 3Pacceptable.
- Coût et espace du cabinet
Un nombre de pôles plus large occupe plus d'espace sur le rail DIN:
3P.:54mm; 3P+N:72mm;4P.:72mm
Classement des coûts:4P>3P+N>3P. 3P/3P+N préféré pour gagner de la place lorsque la protection du neutre n'est pas nécessaire.
- Distinguer 3P+N et 4P (Le plus confus pour les circuits triphasés)
| Taper | Protection des phases | Protection neutre | Commutation neutre | Application |
| 3P. | L1/L2/L3 protégé | Pas de neutre | Pas de neutre | Moteur triphasé pur sans neutre |
| 3P+N | L1/L2/L3 protégé | Neutre sans protection contre les surcharges/courts-circuits | Interrupteurs neutres avec pôles | Charge triphasée déséquilibrée, faible harmonique, neutre pas de risque de surcharge |
| 4P. | L1/L2/L3 tous protégés | Neutre avec surcharge & protection contre les courts-circuits | Phase + neutre ouvert ensemble | Harmonique haute, risque de surcharge neutre, isolation complète pour la maintenance, entrée onduleur/UPS |
LS LA63N-4P-D10: 4P., neutre protégé et entièrement commuté, adapté à l'entrée de l'onduleur et aux circuits triphasés avec neutre nécessitant une isolation de maintenance.
✅ Liste de contrôle de sélection rapide des pôles
- Charge monophasée ou triphasée?
- Système de distribution TN-C / TN-S? La déconnexion du neutre est-elle autorisée?
- Présent neutre? Harmonique lourde / courant neutre déséquilibré? Protection neutre requise?
- Isolation complète requise pendant la maintenance?
- Accessoire différentiel prévu? (Le neutre doit passer par CT)
- Évaluation de l'espace et des coûts
Référence d'application typique
- 3-moteur asynchrone phase sans neutre: 3P MCB Courbe D
- Alimentation principale de l'armoire de commande avec de nombreuses alimentations à découpage, harmonique haute, ouverture d'armoire pour entretien: 4P MCB
- Éclairage triphasé ordinaire, charge déséquilibrée à faibles harmoniques:3Courbe C P+N
- Circuit de prise monophasé:2P Courbe C /1P+N RCBO
Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur

















NH42-63-318x560.png)