AJ65SBTB1-32D is a Mitsubishi MELSEC CC-Link compact remote DC digital module d'entrée
- Définition du code modèle
AJ65: CC-Link remote I/O module series
SBTB1: Compact remote I/O main body
32: 32 Points d'E/S
D: Entrée numérique (DC input)
- Spécifications clés
| Article | Paramètre |
| Réseau | CC-Link Ver.1/2 |
| Taper | Remote DC digital input module |
| Points | 32 points d'entrée |
| Occupied stations | 1 station |
| Tension d'entrée nominale | DC24V |
| Courant d'entrée | Environ. 7mA par point |
| Input response time | 1.5MS (OFF→ON / MARCHE→ARRÊT) |
| Input polarity | Compatible évier/source (works with both NPN and PNP sensors) |
| Isolement | Isolation par optocoupleur |
| Module power supply | DC24V; Module power consumption approx. 45mA |
| ON threshold | ≥14 VCC / ≥3.5mA |
| OFF threshold | ≤6VDC / ≤1.7mA |
| Dimensions hors tout | W179 × H50 × D40 mm |
| Poids | 0.25 kilos |
| Terminaux | M3 screw terminal block |
| Classe de protection | IP2X |
- Scénarios d'application
Remote sensor signal acquisition for production lines: capteurs photoélectriques, détecteurs de proximité, magnetic switches, pushbutton signals
Distributed I/O architecture to reduce bulk hardwiring from control cabinets to field devices via CC-Link bus networking
Compatible with Mitsubishi Q-series, FX3U/FX5U PLCs equipped with CC-Link master station
- Distinction du modèle (Modèles fréquemment confus)
- AJ65SBTB1-32D: Version standard, 1.5réponse de Mme, 32DEPUIS
- AJ65SBTB1-32D1: High-speed version, 0.2réponse de Mme, 32DEPUIS, preferred for high-frequency sensors
- AJ65SBTB1-32T: 32-point transistor output module
- AJ65SBTB1-32DT: 16-input +16-output mixed I/O module
Lifecycle note: AJ65SBTB1-32D is discontinued. Only stock or used units available. Pour les nouveaux projets, AJ65SBTB1-32D1 is the preferred replacement. Same mounting dimensions and terminal definitions; only faster response speed, aucune modification du programme requise.
- Installation & Directives de câblage
- Alimentation: Independent DC24V supply for module itself; sensors also use DC24V signal
- CC-Link bus: DA/DB cables; 110Ω terminating resistors fitted at both ends of the bus
- Common terminals: 8 points per common group, supports NPN/PNP. Keep unified polarity during wiring
- Mise à la terre: Reliable earthing on FG terminal to reduce bus interference
- Station number setting: DIP switches on module body to set CC-Link station number
- Dépannage des pannes courantes
- RUN indicator off: Check DC24V supply, polarity and internal fuse
- ERR indicator flashing: CC-Link communication failure. Inspect DA/DB wiring, résistances de terminaison, duplicate station numbers, shield earthing
- No signal at input channel: Verify sensor power supply and common polarity; measure terminal voltage with multimeter; check for damaged optocoupler channel
- False signal triggering: Cable interference, use shielded cable; check response time. Pour les câbles longs, select D1 high-speed variant
- Alternative Selection List
- Remplacement direct (même taille & bornes): AJ65SBTB1-32D1 (Recommandé pour les nouveaux projets)
- Domestic compatible CC-Link 32DI remote I/O: Innovation, Inwell CC-Link remote input modules (verify CC-Link version and register mapping)
- Upgrade to CC-Link IE Field bus: NZ-series remote I/O (hardware architecture completely different; PLC program rewrite required)
- Référence du code SH
8537101100 (Programmable controller digital input module, for customs declaration only; subject to customs final judgement)
CC-Link Master Station Parameter Configuration (for AJ65SBTB1-32D, Remote I/O Station, occupies 1 station)
Master module: QJ61BT11N (Q-series); Logiciel de programmation: GX fonctionne2; AJ65SBTB1-32D = Remote I/O Station, occupies 1 station, 32-point RX input, no RY output and no RW registers.
Master station fixed station number: Station 0. Slave AJ65SBTB1-32D station number set via DIP switch: 1~64. Station 1 is used in this example.
- Hardware DIP Switch (Set AJ65SBTB1-32D first!)
- Station number DIP switch: Binary DIP switch for station address (par exemple. Station 1 = 00000001)
- Baud rate DIP switch: Must match master station baud rate
000 → 156kbps
001 → 625kbps
010 → 2.5Mbps (most commonly used on site)
011 → 5Mbps
100 →10Mbps
Fit 110Ω terminating resistors at both ends of the bus
- GX Works2 Q-series CC-Link Master Basic Parameters
Path: Project Navigator → Parameters → Network Parameters → CC-Link
| Article | Setting Value | Remarques |
| Modèle de module | QJ61BT11N | Master station module |
| Start I/O Address | 0000 (modify according to actual slot) | Module I/O address |
| Master Station No. | 0 | CC-Link master fixed at station 0 |
| Mode | Remote Net(Ver.1 Mode) | AJ65SBTB1-32D is Ver.1 compatible remote I/O |
| Total Connected Stations | 1 | For single AJ65SBTB1-32D network; update for multiple slaves |
| Communication Speed | 2.5Mbit/s | Must match slave DIP baud rate |
| Retry Count | 3 | Défaut |
| Standby Master | Aucun | Standard single-master system |
| Scan Mode | Asynchrone | Défaut |
Station Information (Critique!)
Cliquez [Station Information], add Station No.1:
| Article | Paramètre | |
| Station No. | 1 | DIP station number of AJ65SBTB1-32D |
| Station Type | Remote I/O Station | ⚠️ NOT Remote Device Station! |
| Occupied Stations | 1 | AJ65SBTB1-32D fixed as 1 station |
| RX(Remote Input) | 32 points | X0~X1F (corresponds to 32DI) |
| RY(Remote Output) | 0 points | This module has inputs only, no outputs |
| RWw/RWr | 0 mots | Remote I/O stations do not use registers |
Remote I/O station soft element mapping rule:
Station1: RX0~RX1F correspond to the 32 DI channels of AJ65SBTB1-32D
PLC internal soft elements for master station: RX mapped to PLC X addresses (auto-refreshed by GX Works)
- Soft Element Refresh Mapping (QJ61BT11N)
CC-Link automatic refresh:
RX: Remote input → PLC internal X
RY: PLC output → Remote module output
RWw: PLC writes to remote registers
RWr: Remote registers read into PLC
AJ65SBTB1-32D (Station 1)
RX0~RX1F (32peu) = 32 DC input channels of the module
Exemple: Sensor ON → RXn=ON; read RX bit directly in program.
- FX5U + FX5-CCL-MS (FX5U CC-Link Master, GX Works2/3)
FX5U with FX5-CCL-MS master card can connect AJ65SBTB1-32D
- Project → Parameters → CC-Link Parameters, Master type: Master station, Ver.1 mode
- Add station entry for Station 1: Remote I/O Station, occupies 1 station, RX=32, RY=0
- Soft element refresh: RX mapped to FX5U X or M (customizable refresh address)
FX5U built-in Ethernet CC-Link IE Field Basic cannot directly connect old AJ65SBTB1-32D. This classic CC-Link uses RS485 bus and requires FX5-CCL-MS module.
- Télécharger & Étapes de mise en service
- Complete all parameter settings, cliquez [Check], confirm no errors;
- Écrire [Paramètres + Programme] to PLC; PLC reset;
- Power up remote modules with DC24V first, then power up PLC master station;
- Observe indicators:
M/S: Master steady ON; COURIR: Slave steady ON;
ERR off = Communication normal; ERR flashing = bus fault;
- Online monitor RX soft elements; trigger sensors and verify corresponding RX bits turn ON/OFF.
- Erreurs courantes
- ❌ Wrong station type: selected as Remote Device Station → communication failure; must use Remote I/O Station
- ❌ Baud rate mismatch between master and slave
- ❌ Missing terminating resistors, random disconnection over long cables
- ❌ Duplicate station numbers, frequent in multi-slave networks
- ❌ Ver.2 mode enabled; old AJ65SBTB1-32D is Ver.1 compatible, use Remote Net Ver.1 Mode by priority
- Sample Program (ST / Ladder compatible)
Directly monitor RX0~RX1F, no special communication instruction required, CC-Link auto cyclic refresh.
Exemple: LD RX0 reads channel 0 input of AJ65SBTB1-32D.
Optional extensions available upon request:
- Screenshot-style GX Works2 CC-Link parameter setup guide
- Batch parameters for multiple AJ65SBTB1-32D network (Station1, Station2, Station3…)
- Communication fault code (ERR lamp) reference table
- Ladder example to map RX to internal M relays for easier programming
CC-Link ERR Lamp + QJ61BT11N Fault Code Reference Table (For AJ65SBTB1-32D)
Two sections: Quick LED Indicator Diagnosis (On-site check) + Hex Fault Codes read from GX Works Diagnosis (Precise troubleshooting)
Maître: QJ61BT11N; Esclave: AJ65SBTB1-32D
- LED Status Quick Reference (Master QJ61BT11N ERR Lamp)
| Master ERR Lamp | Description du défaut | Dépannage |
| DÉSACTIVÉ | Communication normal | – |
| Allumé en continu | All stations communication failure | Bus breakage, DA/DB reversed, dual master conflict, parameter error, baud mismatch, résistance de terminaison manquante |
| Clignotant | Partial slave fault, faulty station exists | Single/multiple slave offline, duplicate station number, slave power off, slave hardware damage |
Slave AJ65SBTB1-32D L.ERR Indicator
| Slave L.ERR Lamp | Description du défaut | Dépannage |
| DÉSACTIVÉ | Communication normal | – |
| Allumé en continu | Slave communication error | Station number out of range, bus broken, power supply abnormal |
| Regular periodic flashing | DIP switch modified under power (station/baud) | Éteindre, reset DIP switch, repower |
| Irregular random flashing | Noise interference / faulty terminating resistor | 110惟 resistors at both bus ends, shield earthing, dommages au câble, parallel power cable interference |
PW lamp OFF: No DC24V supply to slave, check power terminals and fuse first.
L.RUN lamp OFF: Data link not established; master cannot detect this slave station.
- QJ61BT11N Master Hex Fault Codes (Read via GX Works CC-Link Diagnosis)
| Code d'erreur(HEX) | Fault Name | Cause | Action |
| B823 | Remote control mode error | Incorrect master mode setting | Set network parameter to Remote Net(Ver.1 Mode). AJ65SBTB1-32D does not support Ver.2 extended mode |
| B983 / B984 | Invalid module type | Mode incompatibility between master and slave | Old AJ65SBTB1-32D is Ver.1 remote I/O; disable Ver.2 mode |
| BA1B | All stations failure | Whole bus communication interruption | DA/DB wiring, 110惟 terminators, débit en bauds, cable breakage |
| BBC2 | Station number setting error | Station number out of range or wrong station type | Station type must be [Remote I/O Station], not Remote Device Station; station range 1~64 |
| BBC5 | Duplicate master station (multi-master conflict) | 2 masters on the same CC-Link bus | Check bus and keep only one master module |
| BD85 | Master hardware failure | QJ61BT11N module damage | Cycle d'alimentation, replace master module if fault persists |
| BFFE | CPU watchdog timeout | Communication error between PLC CPU and master module | Check QCPU backplane, module installation, PLC reset |
| C92E | Inadéquation du débit en bauds | Master baud differs from slave DIP setting | Set master baud equal to AJ65SBTB1-32D DIP baud |
| C932 | Duplicate station number conflict | Two slaves with identical station DIP setting | Check each module DIP and assign unique station number |
| C940 | Data link stop | Bus break / interference / missing terminator | Check DA DB wiring, shield earthing, résistances de terminaison |
- Q-series CC-Link Special Relay SW (Monitor in GX Works)
Identify offline station quickly via SW registers
- SW0080~SW0083: Link error bits, bit maps to station number. ON = fault at that station
SW0080 bit0 = Station1 fault; bit1 = Station2 fault, and so on
- SW006B: Detailed error type
0: Normale
1: Transmission line fault
2: Parameter error
3: CRC error (interférence électromagnétique)
4: Timeout error (slave no response)
5: Abort error
6: Setting error
- Séquence de dépannage sur site (AJ65SBTB1-32D)
- Check slave PW lamp: OFF → inspect DC24V supply
- Check slave L.RUN / L.ERR lamp
- Open GX Works → CC-Link Diagnosis, read fault code + SW0080 to locate faulty station
- Vérifier: station number, débit en bauds, station type (Remote I/O Station)
- Check DA/DB polarity, 110Ω terminators at both bus ends
- Single-point earthing for shield; avoid both-end earthing to prevent ground loop
- Separate CC-Link cable away from power cables to reduce interference
- Common Pitfall Summary
- Remote I/O Station mistakenly selected as Remote Device Station → BBC2 station type error, ERR flashing
- Master Ver.2 mode enabled, old AJ65SBTB1-32D incompatible → B983 invalid module type
- Terminating resistor fitted only on one end → random flashing, intermittent disconnection
- DA DB wires reversed, entire bus down, master ERR steady ON
- Modify DIP switches while powered on, slave L.ERR flashes periodically; power cycle to recover
Mitsubishi AJ65SBTB1 Series (CC-Link Compact Remote I/O, Screw Terminal Block, all discontinued, 1 station occupancy)
Suffix definition
D: DC Digital Input; D1: High-speed Input; D5: 5V Input
T: Sink transistor output; T1: High-speed transistor output; TE1: Sortie transistor source
DT: Mixed Input+Output; K: Special common terminal specification
All modules in this series are Remote I/O Stations (not Remote Device Stations), CC-Link Ver.1 compatible
- Pure DC Input Modules (DEPUIS)
| Modèle | Points | Brief Specification |
| AJ65SBTB1-8D | 8DEPUIS | DC24V, standard response 1.5ms, NPN/PNP common terminal |
| AJ65SBTB1-16D | 16DEPUIS | DC24V, standard response 1.5ms |
| AJ65SBTB1-16D1 | 16DEPUIS | DC24V, high-speed 0.2ms |
| AJ65SBTB1-32D | 32DEPUIS | DC24V, standard response 1.5ms (votre modèle cible) |
| AJ65SBTB1-32D1 | 32DEPUIS | DC24V, high-speed 0.2ms, direct compatible replacement for 32D |
| AJ65SBTB1-32D5 | 32DEPUIS | DC5V input, special signal acquisition for legacy projects |
| AJ65SBTB1-32KD | 32DEPUIS | DC24V, special common terminal layout |
- Pure Transistor Output Modules (FAIRE)
| Modèle | Points | Brief Specification |
| AJ65SBTB1-8T | 8FAIRE | DC24V sink transistor, 0.5Un par point |
| AJ65SBTB1-8T1 | 8FAIRE | High-speed sink transistor output |
| AJ65SBTB1-8TE | 8FAIRE | Sortie transistor source |
| AJ65SBTB1-16T | 16FAIRE | DC24V sink transistor |
| AJ65SBTB1-16T1 | 16FAIRE | High-speed sink transistor output |
| AJ65SBTB1-32T | 32FAIRE | DC24V sink transistor output |
| AJ65SBTB1-32T1 | 32FAIRE | High-speed sink transistor output |
| AJ65SBTB1-32TE1 | 32FAIRE | Sortie transistor source |
- Modules d'E/S mixtes (DI+DO)
| Modèle | Configuration des E/S | Brief Specification |
| AJ65SBTB1-16DT | 8DI+8DO | Entrée DC24V + sink transistor output |
| AJ65SBTB1-16DT1 | 8DI+8DO | High-speed version |
| AJ65SBTB1-16DT2 | 8DI+8DO | Positive common version |
| AJ65SBTB1-16DT3 | 8DI+8DO | Negative common version |
| AJ65SBTB1-32DT | 16J+16C | 16-in 16-out, modèle standard |
| AJ65SBTB1-32DT2 | 16J+16C | Revised common terminal spec |
| AJ65SBTB1-32DT3 | 16J+16C | Improved revision |
| AJ65SBTB1-32DTE1 | 16J+16C | Sortie transistor source |
| AJ65SBTB1-32KDT2 | 16J+16C | Special common terminal |
| AJ65SBTB1-32KDT8 | 16J+16C | 12E/S VI, special legacy project |
Distinguish other family series (AJ65SBTB2 / AJ65SBTB32 / AJ65SBTC connector type, NOT SBTB1 series)
Frequently confused during procurement, not part of SBTB1 series, reference only
- AJ65SBTB2: Relay output R, analog A modules
AJ65SBTB2-8R, AJ65SBTB2-16R (sortie relais); AJ65SBTB2-8A, 16A analog
- AJ65SBTB32: Compact small terminal block
AJ65SBTB32-8DT / 8DT2, AJ65SBTB32-16DT / 16DT2, AJ65SBTB32-16DR (mixed relay)
- AJ65SBTC: Type de connecteur rapide (not screw terminals)
AJ65SBTC1-32D, AJ65SBTC1-32T, AJ65SBTC1-32DT, field plug wiring, different form factor from SBTB1
Notes de sélection
- All AJ65SBTB1 series are discontinued. Not available for new project purchase, only stock / used units.
- Mêmes dimensions de montage: same point count D/D1, T/T1, DT/DT modules support direct drop-in replacement with no program modification.
- Station type: Must select [Remote I/O Station] in GX Works parameter; fixé 1 occupied station.
- Analog modules are not in SBTB1 series: models AJ65SBT-64AD, AJ65SBT2B-64AD etc.
Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur




















NH42-63-318x560.png)



