Only for current input (4-20mA / 0-20mA), 8 chaînes, AI module dedicated to MELSEC-Q series; comparison within the same series: Q68ADV is the 8-channel voltage module d'entrée, and Q64AD is the 4-channel module with switchable voltage/current input.
Spécifications de base
Modèle: Q68ADI
Canaux: 8CH, current input only, voltage signal input is not supported
Input range: DC 0~20mA (4~20mA transmitters are widely used)
Input resistance: 250Oh (built-in sampling resistor; do NOT add an extra 250Ω resistor externally)
Occupied I/O points: 16 points
5VDC backplane power consumption: 0.64UN
Conversion speed: 80μs par canal; an additional 160μs total conversion time is required when temperature drift compensation is enabled
Précision: ±0.1%FS at 25±5℃; ±0.3%FS with temperature drift compensation, ±0.4%FS without compensation
Resolution modes (selected by software)
Normal mode: -4096~+4095 (0~20mA full scale corresponds to 0~4000)
High-resolution mode: -12288~+12287 (0~20mA full scale corresponds to 0~12000)
Maximum allowable input current: ±30mA (permanent damage may occur if exceeded)
Isolement: Optocoupler isolation between module terminals and PLC power supply; pas d'isolation entre les canaux (crosstalk may occur when multiple transmitters share the same ground)
Withstand voltage: AC500V for 1 minute (terminal side vs PLC power supply side)
Dimensions: 27.4(W) × 98(H) × 90(D) mm; Poids: 0.19kilos
Certifications: CE, UL/cUL, UKCA; marine certifications ABS/BV/DNV, etc..
📌 Model Code Explanation
Q: MELSEC-Q series PLC
68: 8-channel analog
UN: Analogique
D: Numérique (A/D conversion)
je: Saisir, I = Current (V = Voltage for Q68ADV)
🧩 Software Configuration
Logiciel de configuration: GX fonctionne2 / GX Developer + GX Configurator-AD (dedicated analog configuration tool, recommended to reduce heavy FROM/TO instruction programming)
Éléments configurables: Channel enable/disable, gamme (0~20mA), resolution mode, temperature drift compensation, moving average filtering, offset & gain calibration
Stockage des données: Raw A/D converted values are stored in the module buffer memory (BFM); the PLC reads data via FROM instructions
Common 4-20mA Conversion (High-resolution mode, 0~12000)
4mA → 2400
20mA → 12000
Portée: 9600 (corresponds to 16mA)
Engineering conversion formula: Engineering value = (Raw value 2400) / 9600 × (Upper range limit − Lower range limit) + Lower range limit
🔌 Wiring Guidelines (Pièges courants)
- 2-wire transmitter (le plus courant): Transmitter positive to module I+, transmitter negative to module I−; transmitters are powered by external 24VDC. The module does NOT supply power to transmitters.
- 4-wire transmitter: Connect the two signal current wires to I+/I− of the corresponding channel; power supply is independently wired to 24VDC.
- No inter-channel isolation: For multi-signal applications, single-point grounding on the transmitter side is recommended to avoid ground loops and unstable readings.
- Câble blindé: The shield of analog cable shall be grounded at one end only (ground at transmitter side, floating at PLC side).
- Interdiction: Do not connect an extra 250Ω resistor in parallel externally. The built-in 250Ω resistor will cause abnormal readings after parallel connection.
⚠️ Replacement & Comparaison de sélection
| Modèle | Canaux | Type de signal |
| Q68ADI | 8CH | Current only, 0~20mA |
| Q68ADV | 8CH | Voltage only (0~10 V, etc.) |
| Q64AD | 4CH | Voltage/current selectable per channel |
| Q68AD-G | 8CH, isolated version with inter-channel isolation, coût plus élevé |
Replacement reminder: Q68ADI cannot directly replace Q68ADV. One is for current and the other for voltage, with completely different internal circuits.
🛠️ Common Troubleshooting
- Fixed reading at 0: No power supply to transmitter, fil cassé, or channel disabled in software
- Fluctuating and unstable readings: Interférence de boucle de terre, blindage mis à la terre aux deux extrémités, cables routed together with power cables, inter-channel crosstalk
- Reading stuck at full scale: Short-circuited signal wire, faulty transmitter, input current exceeding 20mA
- Severe drift at low/high temperature: Temperature drift compensation function not enabled
- Module ERR light on: Incorrect buffer memory parameter settings, wrong FROM/TO read/write addresses, poor contact between module and base unit
Scénarios d'application de Mitsubishi Q68ADI (For 4-20mA/0-20mA Current Transmitters, 8-Channel AI for Q Series)
Matched with SHAKO solenoid valve pneumatic circuits mentioned previously: Q68ADI collects process values such as pressure and flow; the PLC executes PID/logic calculation and drives SD90822DJSN coils via output points to control PU520/BM520 pneumatic valves, forming closed-loop pneumatic regulation systems.
Scénario 1: Pneumatic Automation Circuits (Most common with SHAKO solenoid valves)
Collected signals: Main air supply pipe pressure, branch pipe pressure, vacuum negative pressure, filter differential pressure, air receiver tank pressure (4-20mA pressure transmitters)
Logique de contrôle: Open air inlet solenoid valve when pressure is below lower limit; open pressure relief valve for overpressure; PID constant pressure regulation
Équipement typique: Transfer machines, montages d'outillage, welding jigs, vacuum adsorption equipment, valve island systems
Caractéristiques: Mostly 2-wire pressure transmitters which perfectly match Q68ADI; 8 channels support simultaneous multi-point pressure acquisition and centralized monitoring
Scénario 2: Machines d'emballage (Emballeuses à flux horizontal, machines verticales de formage-remplissage-scellage, thermoscelleuses)
Collected signals: Heat sealing temperature (4-20mA temperature transmitter), hopper level, air supply pressure, film tension, ink tank liquid level
Interlock control: Pneumatic cutting cylinders, pressure rollers, material stop solenoid valves (SHAKO PU520) interlocked by temperature and pressure values
Avantages: Fast conversion speed of 80μs per channel suitable for high-frequency, short-cycle packaging processes; standardized wiring with universal 4-20mA 2-wire transmitters
Scénario 3: Traitement de l'eau, RO Reverse Osmosis & Dosing Systems
Collected signals: Liquid level (submersible level transmitter), couler (electromagnetic/vortex flowmeter), PH/ORP transmitter, turbidity, chemical dosing flow, pre-membrane and post-membrane differential pressure
Interlock control: On-off control for inlet, concentrate and dosing pneumatic/electric valves, flow totalization, high/low liquid level interlock protection
Working condition: Current loop is preferred in humid sites for better anti-interference performance than voltage signals; Q68ADI is suitable for multi-point process acquisition
Scénario 4: Extrusion, Moulage par injection & Rubber and Plastic Auxiliary Machines (Material loaders, granulateurs, lignes d'extrusion)
Collected signals: Melt pressure, barrel temperature, température de l'huile, vacuum feeding negative pressure, hopper level, cooling water flow
Logique de contrôle: Interlock feeding pneumatic valves and blow cleaning solenoid valves based on negative pressure and pressure; alarm and shutdown on overpressure
Working condition: Stable long-distance transmission of current signals in high-temperature and dusty workshops
Scénario 5: 3C Non-Standard Automation, Testing Machines and Assembly Equipment
Collected signals: Press-fitting force (4-20mA force sensor), test air pressure, leak detection differential pressure, fixture clamping pressure
Fonctions: Press-fitting force monitoring, air tightness leak judgment, OK/NG sorting; pressure curve recording and MES data upload
Description: Transmitters are centrally arranged in clean workshops. The high-density 8-channel design saves slot space. Double-solenoid valves are used to maintain station status.
Scénario 6: CVC, Clean Rooms, Fan Coils and Purification Air Conditioning
Collected signals: Duct differential pressure, pression statique, température & humidity transmitter, débit d'eau, temperature difference between inlet and outlet of chiller
Logique de contrôle: Pneumatic damper actuators and chilled water circuit regulating valves, constant static pressure, température constante & régulation PID d'humidité
Scénario 7: Transport de matériaux, Sorting Lines and Warehouse Conveying Lines
Collected signals: Belt weigher flow, silo level, dust removal negative pressure, air supply pressure
Interlock logic: Trigger feeding/discharging pneumatic valves by high/low level; alarm when dust removal negative pressure is insufficient
Scénario 8: Small-Scale Chemical Industry, Fluid Proportioning & Quantitative Dosing Systems
Collected signals: Flow transmitter, tank liquid level, medium pressure
Fonctions: Flow totalization, quantitative feeding, contrôle des proportions, over-limit interlock shutoff; suitable for multi-component batching with simultaneous multi-channel flow collection
Scénario 9: Pump Stations, Air Compressor Rooms and Centralized Air Supply Station Monitoring
Collected signals: Air compressor discharge pressure, air receiver pressure, pipeline flow, cooling water temperature, filter differential pressure
Fonctions: Load/unload linkage of multiple air compressors, overpressure protection, pressure logging, alarm upload to SCADA
Lignes directrices de sélection (When to prefer Q68ADI and when to avoid it)
Suitable applications:
All measuring points use 4-20mA 2-wire / 4-wire transmitters (pression, niveau, couler, température, force, PH)
8-channel current acquisition required, high channel density on a single module and cost-sensitive
Long signal transmission distance or sites with heavy electromagnetic interference (current loop has better anti-interference performance than voltage signals)
Unsuitable (avoid selection):
0~10 V, ±5V voltage signal acquisition required → Select Q68ADV
Electrical isolation between channels required (chemical explosion-proof, high interference sites) → Select isolated Q68AD-G
Flexible switching between voltage and current per channel for scattered measuring points → Select Q64AD
Mitsubishi Current Analog Input (IA) Module List
Deux catégories: 【Current-only modules for 4~20mA / 0~20mA】, 【Dual-purpose voltage/current modules with current range selectable by software】, sorted by MELSEC-Q / iQ-R / L / FX (iQ-F) série
- MELSEC-Q Series (Q68ADI included)
Current-only Modules (Current input only, voltage not supported)
Dual-purpose Voltage/Current Modules (Range switchable by software for current acquisition)
| Modèle | Canaux | Description | Remarques |
| Q64AD | 4CH | Voltage/current selectable | 80μs/ch, usage général |
| Q64ADH | 4CH | High-speed voltage/current | 20渭μs/ch, haute résolution |
| Q64AD-GH | 4CH | Isolated voltage/current | Inter-channel isolation |
| Q68AD-G | 8CH | Isolated voltage/current | Channel isolation for high-interference sites |
| Q62AD-DGH | 2CH | Isolated with signal conditioning | 2-channel isolated AI |
| Q64AD2DA | 4AI+2AO | Mixed module, AI supports current | Combined analog input & sortir |
There is no Q64ADI (4-channel current-only module) for Q series; Q68ADI is the only 8-channel current-only option.
- MELSEC iQ-R Series (New-generation RCPU)
Current-only Modules
| Modèle | Canaux | Description | Remarques |
| R60AD4 | 4CH | Voltage/current selectable | Screw terminal general model |
| R60ADH4 | 4CH | High-speed voltage/current | 1渭s/ch high-speed sampling |
| R60AD8-G | 8CH | Isolated voltage/current | 40-épingle |
| R60AD16-G | 16CH | Isolated voltage/current | Haute densité 16 chaînes |
Dual-purpose Voltage/Current Modules (Current range selectable)
| R60AD4 | 4CH | Voltage/current selectable | Screw terminal general model |
| R60ADH4 | 4CH | High-speed voltage/current | 1μs/ch high-speed sampling |
| R60AD8-G | 8CH | Isolated voltage/current | 40-épingle |
| R60AD16-G | 16CH | Isolated voltage/current | Haute densité 16 chaînes |
III. MELSEC-L Series (LCPU)
No dedicated current-only modules for L series; all modules support both voltage and current
| L60AD4 | 4CH | Switchable voltage / actuel |
| L60AD8 | 8CH | Switchable voltage / actuel |
| L60AD16 | 16CH | Switchable voltage / actuel |
| L60AD4-G | 4CH | Isolated voltage / actuel |
| L60MD4-G | 4CH | Multifonction (voltage/current/RTD/TC) |
- FX / iQ-F (FX5U, FX3U) Compact PLC Analog Adapters
FX series uses ADP adapters instead of backplane modules; all dual-purpose voltage/current
| FX5-4AD-ADP | 4CH | FX5U dedicated, supports 4-20mA |
| FX3U-4AD-ADP | 4CH | FX3U, supports 4-20mA |
| FX3UC-4AD | 4CH | Module type for FX3UC |
| FX2N-8AD | 8CH | Old FX2N (abandonné) |
- Référence de sélection rapide (For procurement & remplacement)
- Q68ADI (Q) ↔ R60ADI8 (R.): Equivalent function, 8-channel current-only
- HART smart transmitters required → R60ADI8-HA (iQ-R)
- Heavy interference, chemical or explosion-proof cabinet with channel isolation requirement: Q68AD-G (Q dual-purpose) / R60ADI8-HA, R60AD6-DG (R isolated current-only)
- Small quantity of 4 measuring points requiring flexible voltage/current switching: Q64AD / R60AD4
- Critical Notes to Avoid Mistakes
Q68ADI supports current only and cannot collect 0~10V voltage signals; Q68ADV supports voltage only
For dual-purpose modules (Q64AD, R60AD4), the current mode must be selected in software parameters for correct 4-20mA acquisition
All Mitsubishi current AI modules have built-in 250Ω sampling resistors, never connect an extra 250Ω resistor externally
Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur