Type de produit: Single-phase SSR (Solid State Relais), integrated heat sink, zero-cross turn-on
Saisir: DC 5~24V; Sortir: AC 24~240V, 60Un @ 40 ℃
- Spécifications clés
Entrée de contrôle: DC 5–24V, max control current 7mA; operate voltage ≤4V, release voltage ≥1V
Tension de charge: AC 24~240V (operating range 19~264VAC, 50/60Hz)
Courant nominal: 60UN (AC-1, 40℃); derate to 48A when densely installed side-by-side
Surge Current: 440UN (60Hz, 1 faire du vélo); VDRM 600V
On-state Voltage Drop: ≤1.6V RMS; Off-state Leakage Current: ≤20mA @ 200VAC
Trigger Mode: Zero-crossing Turn-on, minimizes inrush & EMI
Isolement: Phototriac optocoupler isolation
Rigidité diélectrique: 4000VAC 1min; Insulation Resistance ≥100MΩ (DC500V)
Montage: Rail DIN / montage à vis; with operation indicator
Température ambiante: -30~+80℃ (pas de condensation); Stockage: -30~100℃
Fonctionnalité: Replaceable power cartridge for low maintenance cost
- Model Number Decoding
G3PA: Series of high-current SSR with replaceable power modules
2: Output voltage class AC24–240V (4 = AC200–400/480V high voltage)
60: Rated current 60A
B: Integrated heat sink
VD: DC voltage input (DC5–24V)
- Applications typiques
Resistive AC loads such as heating tubes, infrared lamps, ventilateurs et convoyeurs; directly driven by PLC transistor outputs.
Note: Add varistor/RC snubber for inductive motor loads; never operate over current or over temperature.
- Same Series Cross Reference
G3PA-240B-VD: AC24–240V, 40UN
G3PA-430B-VD: AC200–400V, 30UN
- Domestic Equivalents (DC5-24V input, AC24-240V, 60A zero-cross SSR)
Meigeer MGR-1 D60
Ximanton H360ZF
Yangming SSR-60DA-H
Application Scenarios for G3PA-260B-VD
Core features summary: DC5–24V control, AC24–240V single-phase output, 60UN, zero-cross trigger, built-in heat sink, field-replaceable power cartridge, PLC direct drive, sans contact, high-frequency switching. First choice for resistive heating loads.
Rappels: This is a single-phase SSR; utiliser 3 units in parallel for 3-phase heating control (one per phase).
Principales applications (Best Match)
- Temperature-controlled heating systems (largest application)
Fours industriels, drying cabinets, thermostatic baths, aging test chambers; barrel heating for injection & machines d'extrusion, contrôleurs de température de moule; heat-seal blades, hot plates on packaging machines; electroplating tank heaters, thermal oil heaters.
Avantage: Zero-cross switching avoids voltage spikes; matches PID time-proportion control from temperature controllers; contact-free design delivers ultra-long life for frequent cycling.
- High-power resistive lighting
Infrared heating lamps, halogen lamps, greenhouse supplementary lighting arrays.
✘ Not recommended: Fluorescent lamps & Alimentations LED (inductive/capacitive surge loads).
- Light-duty fans & convoyeurs (inductive loads with surge protection)
Petits ventilateurs centrifuges, hot air circulation blowers, single-phase conveyor motors with infrequent starts.
⚠️ Motors are inductive loads; external varistor/RC snubber is mandatory to suppress back EMF, otherwise the SSR will break down easily. Not suitable for large motors or frequent forward/reverse operation.
Other General Automation Applications
- Machines d'emballage: Heat shrinkers, hot-knife cutters, hot air power control
- Caoutchouc & plastic equipment: Heating platens for vulcanization & thermoforming molds
- Environmental test equipment: Heating circuits in temperature & humidity chambers
- Machines alimentaires: Baking lines, fryer heating elements, thermal blanching equipment
- CVC: Electric duct heaters, auxiliary air-conditioning heating sections
- Cabinet power distribution: Remplacer le relais + combinaisons de contacteurs; quiet, arcless operation, Installation sur rail DIN.
When to choose this SSR instead of electromagnetic contactors
Cycles marche/arrêt fréquents & PID power regulation (switching every several seconds)
Controlled by PLC or temperature controller DC24V transistor outputs
No arc noise, no contact burn-out & low maintenance required
DIN rail mounting with limited cabinet space, integrated heat sink included
Quick power cartridge replacement without full rewiring later
Unsuitable / Applications restreintes
Direct-on-line starting of large motors, frequently started pumps (high inrush current causes instant damage)
Charges capacitives, large switching power supply banks
400VAC loads (max rated voltage only 264VAC)
DC loads (this model is AC-output SSR only)
Circuits requiring short-circuit protection: SSR has no built-in short-circuit protection; fuse/circuit breaker must be installed upstream.
Sizing Tips
Derate to 48A when tightly mounted side-by-side (80% note actuelle); always leave current margin.
Charges inductives: Fit external 471K (470V, ≥1000A) varistor across output terminals, shortest wiring possible.
3-phase heating scheme: 3 independent G3PA-260B-VD, one per phase, keep 3-phase load balanced.
PID Power Regulation Wiring + Varistor Selection + Derating Installation Standard
Key note: This is a zero-crossing SSR, designed exclusively for time-proportion PID power regulation, not for phase-angle voltage regulation. DC5~24V input, control current ≤7mA; PLC transistor outputs and temperature controller SSR ports can drive it directly without auxiliary relays.
- PID Control Wiring (Contrôleur de température / API)
Définition du terminal (G3PA-260B-VD)
Entrée de contrôle: A1(+), A2(-) (DC5~24V; reverse polarity will not burn the unit, just no operation)
Puissance de sortie: Line IN, Line OUT (series-connected on live wire, 24~240 VCA)
Recommended wiring: MCB → semiconductor fast fuse → SSR output → Load → Neutral (N wire bypasses SSR entirely).
Schème 1: Driven by OMRON E5CC/E5EC Temperature Controller (Most Common Heating Loop)
- SSR output of temperature controller → A1(+), A2(-) of G3PA
- Separate power supply & PT100 thermocouple wiring
- Critical parameter settings
Output mode: RSS / Time Proportion (Zero-cross); DO NOT select phase-angle mode
Cycle Time (T): 20~40s for resistive heating; 30s for ovens & mold heaters. Too short a cycle causes overheating; too long creates large temperature fluctuations.
Run AT auto-tuning after stable temperature holding.
Note: Open-collector outputs on temperature controllers have built-in 24VDC drive power, directly compatible with G3PA.
Schème 2: PLC Transistor DO Drive (PNP / NPN)
Sortie PNP: PLC Y terminal → A1(+); 0V of 24VDC → A2(-)
Sortie NPN: 24VDC+ → A1(+); PLC Y terminal → A2(-)
Programme automate: Use fixed-cycle duty-cycle output (par exemple. 30s period, 0~100%). Avoid high-frequency PWM which overheats the thyristor.
Only 7mA input current; standard PLC transistor outputs can drive it without current-limiting resistors.
3-phase Heating (3× G3PA-260B-VD)
Independent phase control: one single-phase SSR per A/B/C phase. Inputs can share multi-channel SSR outputs from one temperature controller or multiple PLC DO points.
⚠️ This is not a 3-phase SSR; seulement 3 separate single-phase units, keep load current balanced across 3 étapes.
- Varistance & RC Snubber Selection (Mandatory for Inductive Loads)
The G3PA has an internal varistor, but inductive back EMF exceeds internal absorption capacity; external MOV is required, wired directly across SSR output terminals with minimal lead length.
220VAC System (Demande principale)
Varistance: 14D471K (470V, ≥1000A surge current); 10D471K also acceptable.
110VAC System: 14D271K (270V, ≥1000A)
Amortisseur RC (for solenoid valves, petits ventilateurs & transformateurs):
C=0.047~0.1μF / 630ACC; R=100~220Ω / 2W, series RC across output terminals.
✅ Resistive heating tubes: External snubber optional; ✅ Fans, bobines & transformers will blow the SSR without external MOV.
Upstream Fuse Protection (Critique: SSR has no short-circuit protection)
Semiconductor SSR fails instantly under short-circuit conditions; use aR/gR semiconductor fast fuses, not standard gG general fuses.
Resistive heating loads: 80A fast fuse (1.2~1.5× rated current of 60A)
Inductive fan loads: 100A fast fuse
Install fuse immediately upstream of the SSR to shorten fault loop length.
- Déclassement & Spécifications d'installation (G3PA-260B-VD Special Rule)
The G3PA-260B-VD cannot be tightly mounted side-by-side (stated in official datasheet), different from 240B/220B models.
- Full rating condition: Vertical independent mounting, ≥10mm clearance left & droite, ambient temp ≤40℃ → 60A full current.
- Densely arranged on DIN rail:
2 or more units installed tightly together: Max current limited to 48A (80% déclassement).
4+ units side-by-side: Maintain ≥10mm gap between adjacent SSRs, otherwise overheating failure occurs.
Vertical stacking: ≥80mm vertical gap between upper & lower SSRs to keep airflow.
- Horizontal flat mounting (heat sink sideways): Derate current by an additional 30%; avoid this mounting orientation.
- Cabinet ambient >40℃: Further derate current per temperature derating curve; add cabinet cooling fans.
- Couple aux bornes: Bornes à vis M3.5, tighten to 0.8~1.2N·m. Loose terminals cause overheating & bornes brûlées.
- Cartridge replacement: G3PA allows standalone replacement of the G32A power cartridge without rewiring main power circuits, ideal for bulk maintenance.
- Commissioning Troubleshooting Checklist
- Never use this zero-cross SSR for phase-angle dimming/power control; it only supports time-proportion ON/OFF power regulation.
- Off-state leakage: ≤20mA residual voltage across load when SSR is OFF; always isolate upstream MCB before maintenance.
- Do not add large series resistors on input side; low voltage will cause false triggering.
- Separate DC24V control wiring from high-current power cables to avoid EMI interference.
- Cold heating element inrush current: Limit heater rated current to ≤70% of SSR rated current for extra safety margin.
- Quick Fault Diagnosis
Indicator ON, load no heat: Open circuit on main circuit, fusible grillé, broken heater element.
Indicator OFF: No input voltage/polarity reversed, temperature controller output disabled, PLC program no output.
Repeated SSR breakdown: No external MOV for inductive loads, insufficient heat dissipation, oversized fuses, frequent mains voltage surges.
Severe temperature oscillation: PID cycle time too short, P-gain too high, poor thermal insulation, thermocouple misposition.
OMRON Single-Phase SSR + Electromagnetic Power Relay List
Note: All SSRs are zero-crossing, opto-isolé. G3PA series (votre modèle actuel) features replaceable power cartridges, integrated heat sink & Montage sur rail DIN. G3NA/G3NE are cost-effective compact SSRs. Electromagnetic relays are plug-in cabinet relays for PLC & temperature control loops.
Partie 1: G3PA Series (Single-phase SSR, Priority Model)
| Modèle | Charge de sortie | Entrée de contrôle | Remarques |
| G3PA-210B-VD-X | AC24~240V, 10UN | DC5~24V | Slim low-current model |
| G3PA-220B-VD-X | AC24~240V, 20UN | DC5~24V | Slim model |
| G3PA-240B-VD | AC24~240V, 40UN | DC5~24V | Standard heating model |
| G3PA-260B-VD | AC24~240V, 60UN | DC5~24V | ✅ Current model |
| G3PA-420B-VD | AC200~400V, 20UN | DC12~24V | High voltage version |
| G3PA-420B-VD-2 | AC200~480V, 20UN | DC12~24V | Wide high voltage range |
| G3PA-430B-VD | AC200~400V, 30UN | DC12~24V | High voltage model |
| G3PA-430B-VD-2 | AC200~480V, 30UN | DC12~24V | Wide high voltage range |
| G3PA-450B-VD-2 | AC200~480V, 50UN | DC12~24V | High voltage high-current model |
Replaceable Power Cartridges
G32A-A20-VD-X: For G3PA-220B
G32A-A40-VD: For G3PA-240B
G32A-A60-VD: For G3PA-260B
Partie 2: G3NA Economy Single-phase SSR (No integrated heat sink)
| Modèle | Charge de sortie | Entrée de contrôle |
| G3NA-210B | AC24~240V, 10UN | DC5–24V |
| G3NA-220B | AC24~240V, 20UN | DC5–24V |
| G3NA-240B | AC24~240V, 40UN | DC5–24V |
| G3NA-260B | AC24~240V, 60UN | DC5–24V |
| G3NA-290B | AC24~240V, 90UN | DC5–24V |
| G3NA-420B | AC200–400V, 20UN | DC5–24V |
| G3NA-440B | AC200–400V, 40UN | DC5–24V |
Partie 3: G3NE Compact Mini SSR (Space-saving low-power use)
| Modèle | Charge de sortie | Entrée de contrôle |
| G3NE-210T | AC24~240V, 10UN | DC5–24V |
| G3NE-220T | AC24~240V, 20UN | DC5–24V |
Partie 4: G3PJ / G3PE New Generation SSR (Bornes à ressort, high surge resistance)
G3PJ-225B: AC24–240V, 25UN, DC5–24V
G3PJ-245B: AC24–240V, 45UN, DC5–24V
G3PE-225B: AC24–240V, 25UN, DC5–24V
G3PE-245B: AC24–240V, 45UN, DC5–24V
Règle de codage du modèle:
2 = AC24~240V (220V heating mainstream)
4 = AC200~400/480V high voltage
VD = DC input; A = AC input
Partie 5: OMRON Electromagnetic Power Relays (Plug-in cabinet type)
- Série G2R (General-purpose Intermediate Relays)
| Modèle | Formulaire de contact | Contacter l'évaluation | Options de tension de bobine |
| G2R-1-SN | 1un | 10A 250VAC | DC24V, DC12V, AC220V |
| G2R-2-SN | 2c | 5A 250VAC | DC24V, DC12V, AC220V |
| G2R-1-E | 1un | 10UN | PCB-mount version |
- LY High-current Plug-in Power Relays (Replace small contactors)
| Modèle | Formulaire de contact | Contacter l'évaluation |
| LY1N | 1un | 10UN |
| LY2N | 2c | 10UN |
| LY3N | 3c | 10UN |
| LY4N | 4c | 10UN |
| LY1F | 1un | 15UN |
- G7L High-capacity Power Relays (30A direct single-phase load control)
| Modèle | Formulaire de contact | Contacter l'évaluation |
| G7L-1A-T | 1un | 30A 277VAC |
| G7L-2A-T | 2un | 30A 277VAC |
- G6B / G6D PCB Mini Relays (Onboard PLC & contrôleurs de température)
G6B-1174P: 1un, 5UN, DC24V
G6D-1A: 1un, 5UN, DC24V
Partie 6: Guide de sélection: SSR vs Electromagnetic Relay
- Chauffage, PID power regulation, frequent switching & arcless operation → G3PA (Premier choix) / G3NA
- PLC DO signal conversion, low-frequency switching → G2R intermediate relay
- ≤30A low-frequency single-phase loads, cost-sensitive → G7L / LY relays
- Low-power, space-restricted applications → G3NE, G3PJ
Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur




















NH42-63-318x560.png)



