Schneider ATS48D62Q Soft Starter

Série: Altistart 48, Torque Control Soft Starter (TCS torque control, ideal for pumps & fans to eliminate water hammer) ✅ Model Code Definition ATS48 = Altistart 48 soft starter series D62 = Rated current 62A (connexion de ligne); equivalent 107A for motor delta terminal connection Q = Main circuit voltage version: AC 230~415V (Y version: 208–690V) ...

  • Détails du produit

Série: Altistart 48, Contrôle du couple Démarreur progressif (TCS torque control, ideal for pumps & fans to eliminate water hammer)

✅ Définition du code modèle

ATS48 = Altistart 48 soft starter series

D62 = Rated current 62A (connexion de ligne); equivalent 107A for motor delta terminal connection

Q = Main circuit voltage version: AC 230~415V (Y version: 208–690V)

📌 Core Electrical Parameters

Tension du circuit principal: Three-phase AC 230–415V

Courant nominal: 62UN (connexion de ligne) / 107UN (motor delta terminal connection)

Power rating at 400V:

Line connection (droit standard): 30kW; robuste: 22kW

Delta connection (droit standard): 55kW; robuste: 45kW

Alimentation de contrôle: 110–230 V CA

Mode de démarrage: TCS torque control, max current limit 5×In (factory default 4×In)

Stop mode: Free coasting (défaut) / torque ramp soft stop (0.5~60s, preferred for pumps)

Power loss: 201W under standard duty; 153W under heavy duty

Classe de protection: IP20, montage en armoire

Communication: Built-in Modbus-RTU (RJ45, RS485; débit en bauds: 4800/9600/19200bps); expandable to Profibus, DeviceNet via external gateway

I/O terminals:

2 logic outputs LO1/LO2

3 sorties relais: R1 (faute), R2 (end of start), R3 (motor energized)

1 analogue output AO: selectable 0–20mA / 4–20mA

Dimensions (L×H×P): 190 × 290 × 235 mm; Poids net: 8.3kilos

Normes: CEI/EN 60947-4-2; Certifications: CCC, CE, UL, CSA etc.

🧩 Recommended Replacement Model

Remplacement direct du fabricant d'origine: ATS480D62Y (New Generation Altistart 480)

62Un courant nominal, voltage range extended to 208–690V; control supply fixed at 110–230V AC; fully compatible with ATS48 functions, with built-in bypass logic and dual configuration. This is Schneider’s official upgrade solution.

Note: ATS48Q series is replaced by ATS480Y series. Hardware terminals and program parameters differ; verify drawings and program before cabinet retrofit.

📦 Customs HS Code Reference

Primary declaration code: 84798997 (soft starter controller, widely used for export spare parts)

Alternative code used by some customs brokers: 85044090

Confirm with local customs before declaration.

🛠️ Applications typiques & Lignes directrices de sélection

Suitable for centrifugal pumps, les fans, compresseurs, convoyeurs; mainly used to eliminate water hammer and mechanical shock.

Service standard: Pompes, fans ordinaires; S1 duty cycle

Robuste: Concasseurs, démarrages et arrêts fréquents, charges à forte inertie. Select one size higher or adopt delta connection.

External bypass contactor is recommended to avoid continuous heating after bypass.

⚠️ Common Fault Troubleshooting (ATS48 Series General)

PHF: Perte de phase / déséquilibre de phase

PIF: Phase sequence error

DCF: Surintensité, court-circuit de sortie, thyristor damage, bypass contactor sticking

InF / 5d2: Internal fault; if power cycle reset fails, repair is required

USF: Control supply loss

Use Schneider PowerSuite software to upload parameters and read the latest 5 enregistrements de défauts.

📋 Adjacent Models in the Same Series (Q version, 230–415V)

ATS48D62Q → ATS480D62Y Retrofit Comparison List

Key conclusion: Power main circuit, mounting hole positions and relay terminals are fully interchangeable with existing wiring. The biggest risk is the control supply voltage: ATS48D62Q accepts 220–415V AC, while ATS480D62Y only supports 110–230V AC. If the original control power is taken from 400V line, a control transformer must be added.

  1. Bornes d'alimentation principales (L1/L2/L3, T1/T2/T3, By-pass)
ArticleATS48D62QATS480D62YRetrofit Instruction
Line input terminalsL1, L2, L3L1, L2, L3Same position, cable size and torque; reuse existing cables directly
Motor output terminalsT1, T2, T3T1, T2, T3Delta terminal connection is also supported; rated current remains 62A, equivalent 107A in delta connection
Bypass terminalsBuilt-in bypass wiring terminalsBuilt-in bypass wiring terminalsBypass contactor wiring is compatible; ATS480 has enhanced bypass logic in parameters
Tension du circuit principal230–415 V CA208–690V ACWider voltage range for ATS480; fully workable on 400V systems; same unit for 690V applications
Cotes de montage190×290×235mmMême largeur & hauteur, slightly deeper depthMounting holes match perfectly for direct in-place installation; check rear cabinet clearance
  1. Control Terminal Mapping (Critique)
ATS48D62Q TerminalFonctionCorresponding ATS480D62Y TerminalRemarques
CL1 / CL2Alimentation de contrôleCL1 / CL2⚠️Major difference: ATS48Q: 220~415 V CA; ATS480: only 110~230V AC. If control power is taken from L1-L2 (400V), add a control transformer to step down to 220V.
ARRÊTStop inputARRÊT2-fil / 3-wire control logic remains compatible
COURIRRun inputCOURIR
LI3Programmable DI3DI3Renamed, même fonction
LI4Programmable DI4DI4Renamed, même fonction
R1A-R1CRelais 1 (faute / programmable)R1A-R1CContact normalement ouvert, default fault output. Max contact voltage for ATS480 is limited to 230VAC; evaluate original 400V relay circuits.
R2A-R2CRelais 2 (end of start)R2A-R2CCommonly used for bypass drive; direct wiring reuse
R3A-R3CRelais 3 (motor energized / programmable)R3A-R3C
AO1 / COMAnalogue output 0–20/4–20mAAQ1 / COMRenamed, fonction identique
LO1, LO2Logic outputsDQ1, DQ2Original LO1/LO2 → DQ1/DQ2; 24V active output requires external 24VDC supply
—PTC motor temperature sensingPT1/PT2/PT3ATS48 has no native PTC input; ATS480 adds built-in PTC/PT100 temperature sensing

I/O Power Supplement: Digital inputs and DQ logic outputs on ATS480 require external 24VDC. The unit has built-in 24V terminals to power DI directly, consistent with ATS48 power supply scheme.

  1. Communication Interface Differences
ArticleATS48D62QATS480D62Y
Onboard communicationModbus RTU (RJ45 RS485)Modbus RTU with extended baud rate: 1200~256000bps
Fieldbus expansionExternal communication cards: Profibus, AppareilNetModular communication cards: Profinet, EtherNet/IP, Modbus TCP etc.
LogicielPowerSuiteAlors bouge (Use the migration tool to convert parameter files; PowerSuite projects cannot be downloaded directly)
AdressageSlave address 1–247Same address range; but Modbus register mapping not 1:1; verify PLC program register addresses

⚠️Important: PLC Modbus read/write programs cannot be copied directly. Some status words, fault codes and parameter indexes are changed. Simple start-stop & current reading can be adapted quickly; always verify registers for custom protection settings.

  1. Parameter Menu & Migration Guidelines
  2. Core start parameters remain compatible (TCS torque control retained, critical for pumps & les fans)

Initial voltage, start time, arrêter le temps, limite actuelle, arrêt en douceur, protection actuelle, motor thermal overload; parameter definitions are nearly identical.

  1. Menu structure revised:

ATS48: SEF, PRO, DRC, IO, COP, SOUPER

ATS480: New tree menu with revised naming; no identical menu codes

  1. Recommended migration method:

Use the built-in ATS48→ATS480 conversion tool inside SoMove. Upload ATS48 parameter files, auto-convert then download to ATS480.

Avoid manual parameter entry, which easily omits protection settings, relay assignments and analogue calibration.

  1. Factory security update: ATS480 initializes on power-up, requiring language setup and security password; new encryption & firmware security policies added.
  2. Fault codes: Basic faults (PHF, USF) keep the same meaning; interne & communication fault codes are updated.
  3. Relay Contact Voltage Risk (Piège courant)

ATS48 relay contacts: Max 400VAC

ATS480 on-board relay contacts: Max 230V AC only

👉 If R1/R2/R3 directly drive 400V contactor coils: Direct wiring is NOT allowed!

Solution: Add 220V intermediate relay isolation before driving 400V contactors.

  1. Delta Connection Compatibility

Both models support motor delta terminal connection (internal delta) to raise rated current; wiring topology is identical. Current conversion formula unchanged: Line In ×1.732 ≈ Delta equivalent current. ATS48D62Q and ATS480D62Y both have 62A main current, equivalent 107A in delta connection; power rating remains the same.

  1. On-site Retrofit Checklist (Follow in sequence)

CL1/CL2 control supply: Confirm voltage is 110–230V AC. If original power is 400V, install a control transformer.

Relay output loop: Check contactor coil voltage. Add intermediate isolation relays for 400V coils.

Câbles d'alimentation, bypass cables & mise à la terre: Reuse directly; keep tightening torque unchanged.

DI/DO/AQ terminal one-to-one mapping; add PTC temperature wiring if needed.

Communication: Convert parameters via SoMove; verify Modbus registers and fault codes in PLC program.

2-wire/3-wire control: ATS480 auto-detects wiring mode; no extra control mode setting required.

Cabinet depth clearance: Ensure cabinet door & cable trunking do not collide with the new unit.

Remote keypad: Old VW3G48101 keypad is incompatible; replace with ATS480 remote keypad kit.

  1. Summary of Incompatibilities
  2. Control supply voltage range (highest risk item)
  3. Max AC voltage rating of relay contacts
  4. Software tool change: PowerSuite → SoMove; parameters must be converted
  5. Modbus register mapping & fault codes are not fully consistent
  6. Newly added PTC temperature sensing, cyber security and dual-motor configuration functions

Schneider Altistart 48 (ATS48) Liste complète des modèles

Series Note: ATS48 is discontinued (Date de la dernière commande: 31 Déc 2023; service support until 31 Déc 2030). TCS torque-controlled soft starter, optimized for pump/fan water hammer suppression.

Définition du suffixe

Q: Three-phase 230~415V AC; supports internal delta terminal connection

Oui: Three-phase 208~690V AC; delta connection is NOT permitted

Prefix breakdown: D (faible puissance), C (medium power), M. (haute puissance)

  1. ATS48 Q Version (230–415V, delta connection supported, most popular for export)
ModèleCourant nominal (UN)400V Standard Duty (Line Connection) kW400V Standard Duty (Connexion Delta) kWDimensions W×H×D mm
ATS48D17Q177.515160×275×190
ATS48D22Q221118.5160×275×190
ATS48D32Q321522160×275×190
ATS48D38Q3818.530160×275×190
ATS48D47Q472245160×275×190
ATS48D62Q623055190×290×235
ATS48D75Q753755190×290×235
ATS48D88Q884575190×290×235
ATS48C11Q1105590190×290×235
ATS48C14Q14075110200×340×265
ATS48C17Q17090132200×340×265
ATS48C21Q210110160320×380×265
ATS48C25Q250132220320×380×265
ATS48C32Q320160250320×380×265
ATS48C41Q410220315400×670×300
ATS48C48Q480250355400×670×300
ATS48C59Q590315450400×670×300
ATS48C66Q660355500400×670×300
ATS48C79Q790400560770×890×315
ATS48M10Q1000500710770×890×315
ATS48M12Q1200630800770×890×315
  1. ATS48 Y Version (208–690V, line connection only, delta connection forbidden)

Model numbering matches the above list exactly; only suffix changes to Y:

ATS48D17Y / D22Y / D32Y / D38Y / D47Y / D62Y / D75Y / D88Y

ATS48C11Y / C14Y / C17Y / C21Y / C25Y / C32Y / C41Y / C48Y / C59Y / C66Y / C79Y

ATS48M10Y / M12Y

Y version covers up to 690V, suitable for mining & overseas 660V systems. Nominal current is identical to the same code Q model; delta terminal current expansion is not supported.

  1. OEM Upgrade Mapping (ATS48 → ATS480, Référence clé)

Règle: ATS48□□Q / ATS48□□Y → ATS480 same code + suffix Y

Exemples:

ATS48D62Q → ATS480D62Y

ATS48C41Q → ATS480C41Y

ATS48M12Y → ATS480M12Y

ATS480 only has Y suffix, voltage 208–690V, fixed control supply 110–230V AC; no Q version, no Q/Y split anymore.

  1. Dimension Group Summary (For cabinet retrofit verification)
  2. D17~D47: 160 × 275 × 190
  3. D62~C11: 190 × 290 × 235
  4. C14~C17: 200 × 340 × 265
  5. C21~C32: 320 × 380 × 265
  6. C41~C66: 400 × 670 × 300
  7. C79~M12: 770 × 890 × 315
  8. ATS48 Exclusive Accessories List

VW3G48101: Local keypad (old model, NOT compatible with ATS480)

VW3A4810: Modbus terminal kit (Modbus built-in; no extra card required for most cases)

VW3A4820: Profibus DP communication expansion card

VW3A4830: DeviceNet communication expansion card

VZ3V481 / VZ3V482 / VZ3V483 / VZ3V484 / VZ3V485: Cooling fan spare parts (split by power range)

  1. Rappels de sélection des clés
  2. Delta connection only available on Q suffix units. Equivalent current ≈ nominal current ×1.732. Restrictions: partial soft-stop functions are limited; dual-motor switching is not supported.
  3. For heavy-duty loads (concasseurs, démarrages et arrêts fréquents), select one power rating higher.
  4. Software difference: ATS48 uses PowerSuite; ATS480 uses SoMove. Parameter files cannot be imported directly and must be converted.
  5. Control supply difference: ATS48 Q/Y supports 110–415V AC; ATS480 only accepts 110–230V AC (the biggest retrofit risk).