Explication du code modèle
| Segment de code | Signification | Description détaillée |
| LC1 | Identifiant de la série de produits | Basic code for Schneider TeSys contactors |
| D | Code de série | TeSys Deca series, high-performance full-range industrial contactors |
| 25 | Courant nominal | 25UN (rated operational current under AC-3 utilization category) |
| 6 | Coil characteristic | Low-power consumption coil (<2.4W), energy-saving design |
| B | Tension de bobine | 24V |
| L | Coil type | Bobine CC |
| Description complète | Three-pole contactor of Schneider TeSys Deca series, rated current 25A, 24VDC low-power coil, ring terminal connection, 1NO+1NC auxiliary contacts |
- Principales spécifications techniques
| Catégorie | Données techniques | Remarques |
| Paramètres de base | ||
| Type de produit | 3-pole non-reversible contactor | 3 main NO contacts |
| Courant nominal (AC-3) | 25Un à 400 V | For controlling 11kW three-phase motors |
| Courant nominal (AC-1) | 40Un à 400 V | Pour charges résistives |
| Tension de fonctionnement nominale | Max.. 690ACC / Max.. 300VCC | |
| Spécification de la bobine | 24VCC, Faible puissance (≤2.4W) | Tension d'appel: 19.2-30VCC |
| Mécanique & Endurance électrique | ||
| Durée de vie mécanique | 15,000,000 cycles (pas de charge) | |
| Durée de vie électrique (AC-3) | 1,600,000 cycles (with load) | |
| Physical Features | ||
| Type de montage | Montage sur rail DIN standard de 35 mm | |
| Type de connexion | Ring-lugs | For firm wiring |
| Contacts auxiliaires | 1NON+1NC (standard) | Expandable |
| Dimensions (mm) | Environ. 45×85×101 | Taille compacte, économise de l'espace dans l'armoire |
| Certifications & Normes | CEI 60947-4-1, DANS 60947-4-1, RoHS compliant | Comply with international industrial standards |
| Environnement opérationnel | ||
| Température de fonctionnement | -25°C ~ +70°C | Wide temperature range for harsh industrial environments |
| Température de stockage | -40°C ~ +85°C | |
| Protection contre la pénétration | IP20 (main unit) | Use with qualified protective enclosures |
- Liste complète des modèles (LC1D Series, 25A Range)
| Modèle | Tension de bobine | Type de bobine | Consommation électrique de la bobine | Contacts auxiliaires | Reference Order No. |
| LC1D256BL | 24VCC | CC | Faible puissance (<2.4W) | 1NON+1NC | LC1D256BL |
| LC1D256B7 | 24ACC | CA | Faible puissance | 1NON+1NC | LC1D256B7 |
| LC1D2501BL | 24VCC | CC | Standard power | 1NON+1NC | LC1D2501BL |
| LC1D2501B7 | 24ACC | CA | Standard power | 1NON+1NC | LC1D2501B7 |
| LC1D2510BL | 24VCC | CC | Standard power | 1NC+1NO | LC1D2510BL |
| LC1D2510B7 | 24ACC | CA | Standard power | 1NC+1NO | LC1D2510B7 |
| LC1D25BD | 24VCC | CC | Standard power | 1NON+1NC | LC1D25BD |
| LC1D25M7 | 220ACC | CA | Standard power | 1NON+1NC | LC1D25M7 |
| LC1D25Q7 | 380ACC | CA | Standard power | 1NON+1NC | LC1D25Q7 |
| LC1DT256BL | 24VCC | CC | Faible puissance | 1NON+1NC (4-pôle) | LC1DT256BL |
- Multimarque & Old/New Model Replacement List
4.1 In-brand Replacement (Schneider)
| Modèle original | Modèle de remplacement | Description |
| LC1D25BD | LC1D256BL | Upgraded to low-power coil, 24VDC retained with improved performance |
| LC1D25B7 | LC1D256B7 | Low-power AC coil version |
| LC1D2500BL | LC1D256BL | Optimized auxiliary contacts (1NO+1NC replaces 0NO+0NC) |
4.2 Cross-brand Replacement
| Original Brand | Modèle original | Schneider Equivalent | Matching Level | Remarques |
| ABB | A26-30-10 | LC1D256BL | ★★★★★ | 3-pôle 25A, 24Bobine V, identical specifications |
| Siemens | 3RT6026-1AN20 | LC1D256BL | ★★★★☆ | 25UN, 24VCC, même configuration de contact auxiliaire |
| Omron | GMC-25 | LC1D256BL | ★★★★☆ | 3-pôle 25A, 24VCC, equivalent mechanical life |
| Mitsubishi | S-N25 | LC1D256BL | ★★★★☆ | 3-pôle 25A, low-power 24VDC coil |
- Environnement d'application & Cas industriels
5.1 Applications recommandées
Automatisation industrielle: Control of three-phase asynchronous motors (les fans, pompes à eau, compresseurs, convoyeurs)
Systèmes CVC: Air conditioning compressors and ventilation systems
Building Electrical: Building automation, lighting systems and fire-fighting equipment
Industrie de l'énergie: Power generation equipment, power distribution systems and renewable energy facilities
Traitement de l'eau: Water pump control and wastewater treatment equipment
Marin & Railway: Transportation industry requiring special certifications (LC1D series advantages)
5.2 Not Recommended Applications
High-frequency switching: Sur 1200 operations per hour (Select LC1Q / LC1R series instead)
Haute altitude: Elevation over 2000m (Derate load or use special models)
Corrosive environments: Direct exposure to acid, alkali and salt mist (Additional protection required)
Zones antidéflagrantes: Special explosion-proof certified models are mandatory
5.3 Cas d'application typiques
- Automobile Manufacturing Plant
Used for motor control of stamping production lines. Après remplacement, breaking time is reduced by 30%, failure rate drops by 50%, maintenance time is shortened from 2 hours to 30 minutes, and annual maintenance cost is cut by about 200,000 RMB.
- Nourriture & Industrie des boissons
Applied to three-phase motors of filling lines. Thanks to 2.4W low power consumption, each contactor saves approximately 18 kWh per year under 24-hour continuous operation. A factory with 100 units saves 1,800 kWh annually.
- Centre de données
Controls air conditioning compressors and ventilation fans. The 24VDC low-power coil ensures stable operation under UPS power supply, reduces battery load and extends backup duration.
- Lignes directrices de sélection & Quick Reference Rules
Quick Selection Tips
This is a 3-pole 25A contactor with 24VDC low-power coil and ring terminals. Equipped with 1NO+1NC auxiliary contacts, it features energy efficiency, high reliability and long service life, ideal for motors, pompes à eau et compresseurs.
Quick Reference Rules
- Correspondance actuelle: 25A under AC-3 for 11kW three-phase motors; 40A capacity for resistive loads under AC-1.
- Coil Identification: Suffix BL = 24VDC low power; B7 = 24VAC low power; BD = 24VDC standard power.
- Contacts auxiliaires: Standard 1NO+1NC. Models with suffix 01 ou 10 for alternative contact configurations.
- Installation: Montage sur rail DIN standard de 35 mm; ring terminals ensure reliable connection.
- Energy Saving: Low-power coil (≤2.4W) saves 70% energy compared with standard coil (environ. 8W), perfect for long-term operation.
- Défauts courants & Dépannage
| Phénomène de défaut | Causes possibles | Solutions |
| Le contacteur ne parvient pas à s'enclencher | Insufficient coil voltage / Mauvais câblage | Check power voltage (19.2-30VCC) et câblage |
| Bobine brûlée | Surtension / Reverse polarity | Confirm 24VDC polarity; install overvoltage protection |
| Overheated contacts | Surcharge / Câblage lâche | Check load current and retighten terminals |
| Welded contacts | Surcharge / Court-circuit | Inspect circuit protection devices and replace contact assembly |
| Bruit excessif | Dirty core contact surface | Clean core surface and check short-circuit ring |
- Key Ordering Information
Modèle standard: LC1D256BL
Modèles alternatifs: LC1D25BD (standard power version), LC1D256B7 (24VAC low-power version)
Accessoires compatibles:
Auxiliary contact blocks: Série LADN (par exemple. LADN20C: 2NON; LADN02C: 2Caroline du Nord)
Overload relays: série LRD (par exemple. LRD08C: 6-10UN, matches 25A contactor)
Mounting base: Optional separate base
Application Scenarios for LC1D256BL
Core features: 3-pôle 25A, 24VDC low-power coil, longue durée de vie, standard DIN rail mounting, 1NO+1NC auxiliary contacts, strong anti-interference performance.
- Scénarios d'application recommandés (Principales applications)
Featured with 24VDC low-power DC coil, this model perfectly matches standard industrial DC control circuits. Its 25A rating is suitable for three-phase motors up to 11kW and resistive loads up to 40A, serving as a mainstream component for automatic control cabinets.
1.1 Équipement d'automatisation industrielle (Application principale)
Équipement applicable
PLC/DCS control cabinets, petites machines-outils, manipulator auxiliary mechanisms, inverter-driven fans, small drive motors, test and inspection equipment.
Avantages
24VDC is the mainstream control voltage for industrial control systems, no extra power converter required.
DC coil provides strong EMC performance, avoiding misoperation caused by inverters and servos.
Faible puissance (≤2.4W) generates little heat during continuous power-on, adapté pour 24/7 standby equipment.
1.2 CVC & Air Ventilation Systems
Équipement applicable
Intérieur & outdoor unit fans of central air conditioners, condensate pumps, ventilateurs de tour de refroidissement, fresh air handling units, damper drive motors, machine room exhaust fans.
Avantages
HVAC rooms widely adopt 24VDC automatic control circuits for high compatibility.
Low power design reduces energy consumption and cabinet temperature for year-round continuous operation.
Plage de température de fonctionnement: -25°C ~ +70°C, adapts to drastic temperature changes in machine rooms.
1.3 Building Electrical & Fire Emergency Systems
Équipement applicable
Domestic water pumps, basement exhaust fans, fire smoke exhaust fans, fire roller shutter motors, centralized emergency lighting circuits (charges résistives).
Avantages
Standard 24VDC for fire emergency circuits, directly powered by UPS/emergency batteries for normal operation during power failure.
Built-in 1NO+1NC auxiliary contacts transmit operation/fault signals to fire alarm hosts and building monitoring systems.
40A load capacity under AC-1 for multi-circuit lighting control.
1.4 Water Treatment Industry (Sewage / Purified Water / Circulating Water)
Équipement applicable
Circulating water pumps, dosing metering pumps, aeration fans, small agitator motors, ventilation equipment for water treatment workshops.
Avantages
Almost all automatic control systems for water treatment use 24VDC.
IP20 protection rating adapts to slightly humid indoor machine rooms.
Satisfactory electrical endurance for frequent start-stop operation with low failure rate.
1.5 Nouvelle énergie, PV & Energy Storage Cabinets
Équipement applicable
Cooling fans for PV boxes, temperature control pumps for battery compartments, ventilation motors of energy storage cabinets, small auxiliary inverter loads.
Avantages
PV and energy storage systems are DC-powered inherently; no inverter needed for 24VDC coil.
Ultra-low coil power avoids extra consumption of backup battery power and extends backup time.
No AC humming for DC coil, ideal for quiet energy storage rooms.
1.6 Logistique, Entreposage & Conveyor Lines
Équipement applicable
Convoyeurs à bande, roller sorting lines, small elevators, warehouse ventilation fans.
Avantages
Mechanical and electrical endurance meets frequent regular start-stop for long-running production lines.
Auxiliary contacts realize interlock, chain control and sequence start to ensure safety logic of production lines.
1.7 Nourriture, Conditionnement & Light Industrial Equipment
Équipement applicable
Conveyors of packaging machines, auxiliary motors of filling lines, dehumidifiers and ventilation fans for workshops.
Avantages
Suitable for clean indoor workshops without heavy corrosion; standard rail mounting facilitates standardized cabinet wiring.
Compact structure saves cabinet space, a standard OEM component for complete machines.
- Non recommandé / Scénarios interdits (Risques & Alternatives)
2.1 High-frequency Start-Stop (Sur 1200 cycles per hour)
Risque: Excessive switching frequency causes rapid contact ablation, welding and shortened service life.
Alternative: Schneider LC1R / LC1R series high-frequency contactors.
2.2 Altitude supérieure à 2000m
Risque: Thin air degrades arc extinction capability, leading to arcing and reduced insulation performance.
Recommandation: Use special high-altitude contactors or derate the load by over 30%.
2.3 Severe Corrosion, Salt Spray & Heavy Dust (Chemical Plants, Coastal Open Areas, Mines)
Risque: IP20 rating cannot protect coil, terminals and contacts from acid, alcali, salt mist and dust erosion.
Exigence: Bare installation is forbidden. Use sealed enclosures of IP54 or higher; select anti-corrosion models for chemical environments.
2.4 Direct Outdoor Installation without Protection
Risque: Rain, sunlight and condensation lead to coil short circuit and contact oxidation.
Mandatory Requirement: Install inside distribution cabinets or control enclosures with IP54 or higher protection.
2.5 High-power Pure DC Main Circuit Loads
Risque: Designed mainly for AC loads with poor DC breaking capacity; high DC loads easily cause contact welding.
Alternative: Schneider LP1D dedicated DC contactors.
2.6 AC220V / AC380V Control Circuits
Risque: 24VDC coil will burn out instantly if connected to AC power.
Alternative AC coil models:
24ACC: LC1D256B7
220ACC: LC1D25M7
380ACC: LC1D25Q7
2.7 Control Three-phase 380V Motors over 11kW (AC-3)
Risque: Rated 25A under AC-3 corresponds to 11kW motor; overload results in overheating and burnt contacts.
Alternative: Upgrade to higher current models such as LC1D32 series.
- Notes for Marginal Operating Conditions (Usable with Protection Measures)
- Basements & Humid Machine Rooms
The product is applicable. Install dehumidifiers inside control cabinets to prevent condensation inside the contactor.
- Ambient Temperature near Limits (-25°C / +70°C)
Derate the load by 10% and avoid long-term full-load operation.
- Coil Wiring Length over 10m
Voltage drop occurs on 24VDC lines. Ensure terminal voltage of the contactor coil is no lower than 19.2V (minimum pull-in voltage).
- Control Inductive Loads such as Motors
Equip with surge suppressors (Schneider LADRC series) to absorb back EMF and protect the coil.
- Scenario Summary
✅ Preferred Applications: Indoor control cabinets, 24VDC control systems, three-phase motors up to 11kW, 24/7 continuous-operation equipment (Automation, CVC, Fire Protection, Traitement de l'eau, Stockage d'énergie).
❌ À éviter: High-frequency switching, haute altitude, unprotected outdoor areas, heavily corrosive environments, high-power DC main circuits, AC control power supply.
Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires






















NH42-63-318x560.png)