Gamme: TeSys F (High-power imported contactor, abandonné)
Model naming rule:
LC1F500 + Coil suffix
LC1F: TeSys F 3-contacteur de pôle
500: Courant de fonctionnement nominal 500 A under utilisation category AC-3 at 440 V
Suffix examples:
M7: CA 220 V, 50/60 Hz (Most common model: LC1F500M7)
Q7: CA 380 V
ED: CC 48 V
⚠️ Recommended replacement after discontinuation: LC1G500 (New-generation TeSys Giga)
- Main Electrical Parameters
Circuit principal
Nombre de pôles: 3P., 3NON (3 contacts principaux normalement ouverts)
Tension assignée d'isolement Ui: 1000 V
AC-3 (Motor load, 55°C): 500 UN
AC-1 (Charge résistive, 40°C): 700 UN
Rated short-time withstand current Icw: 4200 UN / 10 s
Controllable Motor Power (AC-3)
220 V: 147 kW
380/400 V: 250 kW
415 V: 280 kW
440 V: 295 kW
690 V: 335 kW
Paramètres de la bobine (Take AC coil M7 as example)
Inrush power: 1100 Virginie
Hold-in power: 18 Virginie
Plage de tension de fonctionnement: 0.85~1.1 × Uc
Closing time: 40~65 ms; Opening time: 100~170 ms
Durée de vie & Maximum Operating Rate
Durabilité mécanique: 10 millions de cycles
Fréquence de fonctionnement maximale: 2400 cycles/heure
- Construction & Montage
Connexion du circuit principal: Bolt connection for busbars or cable lugs, couple de serrage 35 N·m
Control terminal tightening torque: 1.2 N·m
Dimension hors tout (L × H × P): Environ. 233 × 238 × 232 mm
Montage: Montage par vis sur plaque de base
- Accessoires compatibles
Relais de surcharge thermique
Matching electronic thermal relay: LR9F7375 (132~220 A)
Note: Direct mounting between LC1F500 and LR9F7375 requires swapping Phase A and Phase C terminals of the thermal relay for alignment.
Contacts auxiliaires
LA1F, LA8F auxiliary contact modules (Pas de contacts auxiliaires intégrés; need to be ordered separately).
Verrouillage mécanique
LA7F406 (For forward/reversing circuit).
- Important Discontinuation Notice
LC1F500 series including LC1F500M7 / LC1F500Q7 are fully discontinued.
Stock spare parts are gradually depleted. Pour les nouveaux projets, select the replacement directly:
✅ LC1G500KUEN (Wide voltage coil 100–250 V AC/DC)
✅ LC1G500LSEA (200–500 V AC/DC)
LC1G500 shares the same current rating, but dimension differs; cabinet layout needs hole dimension verification.
- Applications typiques
3-phase fans, pompes à eau, compresseurs d'air, concasseurs, variable frequency drive mains bypass and other LV motor circuits up to 250 kW.
Si nécessaire, je peux fournir:
1) Complete dimension drawing of LC1F500;
2) Comparison checklist for LC1F500 ↔ LC1G500 replacement;
3) Full coil voltage model list.
Schneider LC1F500 (TeSys F Series)
✅ Mechanical durability: 10 millions de cycles (10×10⁶ cycles)
Conditions d'essai: Tension de commande nominale, fonctionnement à vide.
Supplementary reference parameters:
- Durabilité électrique (AC-3, 400 V, 500 UN): Environ. 150,000 cycles;
- Fréquence de fonctionnement maximale: 2400 cycles/heure;
- Rappels: Ce modèle est abandonné; replacement model LC1G500.
Official Replacement Models for Schneider LC1F500 (TeSys F)
LC1F500 full series discontinued. Official upgrade series: TeSys Giga LC1G500 (3-pôle). It offers identical electrical rating: 500 A under AC-3 at 440 V.
- Primary Direct Replacement Models (Sorted by Coil Voltage)
| Original LC1F500 Model | Spécification de la bobine | Recommended LC1G500 Replacement | Coil Range |
| LC1F500M7 | CA 220 V | LC1G500KUEN | 100~250 V AC/DC (Most widely used in China) |
| LC1F500Q7 | CA 380 V | LC1G500LSEA | 200~500 V AC/DC (Couvertures 380 V) |
| LC1F500F7 | CA 110 V | LC1G500EHEA | 48~130 V AC/DC (Couvertures 110 V) |
| LC1F500ED | CC 48 V | LC1G500BEEA | 24~48 V AC/DC |
Model description:
KUEN: Version standard, 100~250 V (Top choice to replace M7)
LSEA: Version avancée, 200~500 V (To replace Q7)
EHEA: Version avancée, 48~130 V (To replace F7)
- Critical Notes During Replacement
- Mounting dimensions are not interchangeable
LC1G width is roughly 35% narrower than LC1F;
✅ To reuse existing mounting holes: Install adaptation base LA9GRFB2 (Suitable for LC1G265~500), no new drilling required.
- Accessories are incompatible; old LC1F accessories cannot be reused
Original: LA1F auxiliary contacts, LA7F mechanical interlock cannot be mounted on LC1G
New accessories for LC1G:
Contacts auxiliaires: LA9G series
Verrouillage mécanique: LA9G970 (Horizontal forward/reversing)
- Matching thermal overload relay updated
Original matched LR9F7375; LC1G500 matches LR9G series electronic thermal relays.
- Comparaison des performances
Durabilité mécanique: LC1F500 = 10 millions de cycles; LC1G500 = 8 millions de cycles
Courant nominal AC-3: Identique 500 A @440 V
LC1G Advantages: Electronic wide-voltage coil, stronger voltage fluctuation resistance, contact wear diagnosis available.
- Alternative Solutions for Two Scenarios
- Emergency spare parts solution
For urgent on-site maintenance: Purchase original stocked LC1F500 from market (Price increased, supply tight, watch out for refurbished units). Not allowed for new projects.
- Cross-brand alternative (Non-Schneider OEM)
Siemens 3RT1075, ABB AF580; Only applicable for retrofit projects, not recommended for new cabinet design.
Simplified Selection Advice
For most domestic working conditions (Original coil AC220V LC1F500M7)
👉 Preferred option: LC1G500KUEN + LA9GRFB2 adaptation base (If original mounting holes need reservation)
Service Life Parameters of Schneider LC1G500 (TeSys Giga)
- Durabilité mécanique (Official Rating)
8 millions de cycles (8×10⁶ cycles)
Tested under no-load condition with rated control voltage.
Compare with old LC1F500: Durabilité mécanique 10 millions de cycles, légèrement plus bas.
- Electrical Durability (AC-3, 400 V, 500 A Motor Load)
✅ Official standard reference value: 150,000 cycles (Same as LC1F500 datasheet value)
Important Remarks:
- Electrical durability is not a fixed value, affected by operating frequency, courant de démarrage, température ambiante, surge suppression and start-stop frequency;
- Under AC-3e (Heavy-duty frequent start-stop), electrical durability will be significantly lower than 150,000 cycles;
- Under AC-4 (Inching, reverse braking), electrical durability is only 20,000~30,000 cycles;
- Under AC-1 resistive load (Heaters), electrical durability can reach more than 500,000 cycles.
- Extra Key Advantages (LC1G VS LC1F)
LC1G500 supports independent replacement of main contact assembly!
When contacts are burned out, only the contact module needs replacement instead of the whole contactor, greatly reducing long-term maintenance cost; LC1F500 does not support separate contact replacement. Once contacts are damaged, the whole unit must be replaced.
- Maximum Allowable Operating Frequency
AC-3: 600 cycles/heure
AC-3e: 600 cycles/heure
AC-1: 300 cycles/heure
AC-4: 150 cycles/heure
Service Life Comparison Table: LC1F500 ↔ LC1G500
| Paramètre | LC1F500 (Discontinué) | LC1G500 (Modèle de remplacement) |
| Durabilité mécanique | 10 millions de cycles | 8 millions de cycles |
| Durabilité électrique (AC-3) | Environ. 150,000 cycles | Environ. 150,000 cycles |
| Separable contact kit | ❌ Non pris en charge | ✅ Pris en charge |
Contacteur,disjoncteur,onduleur solaire,compteur électrique,capteur,Encodeur,API