NT: MasterPact NT series disjoncteur pneumatique (PBR, modèle hérité, abandonné; replacement model MTZ1 06H2)
06: Taille du cadre 06, frame rated current 630A
H2: Breaking capacity class H2; Icu=50kA@440VAC, short-time withstand current Icw=50kA (1s), Class B selective protection
Paramètres électriques de base
| Article | Spécification |
| Frame rated current In | 630UN (à 40℃) |
| Tension assignée d'emploi Ue | C.A. 690 V, 50/60Hz |
| Tension assignée d'isolement Ui | C.A. 1000V |
| Tension assignée de tenue aux chocs Uimp | 12kV (1.2/50μs lightning impulse) |
| Pouvoir ultime de coupure en court-circuit Icu | 50kA à 440 V; 42kA à 690 V |
| Nombre de pôles | 3P. / 4P en option |
| Construction type | Fixé / Débrochable |
| Déclencheur | Frame supplied without trip unit, MicroLogic trip unit to be ordered separately |
| Normes | CEI 60947-2, with isolating function |
Notes clés
- Statut d'arrêt: NT series scheduled for end-of-sale by the end of 2025. Replacement model MTZ1 06H2, part number LV947203 (draw-out version)
- Parameter Clarification
Ue=690V: Maximum normal operating voltage
Ui=1000V: Tension de tenue à fréquence industrielle
Uimp=12kV: Tension de tenue aux chocs de foudre. NOT applicable for 12kV high-voltage switchgear, this is an insulation index for low-voltage ACB
- Application: Incoming feeder, bus tie and heavy-load outgoing feeder in low-voltage distribution systems, for industrial plants, data centers and marine power distribution; supports selective protection and coordination with upstream/downstream devices
- Reference Frame Part Numbers
NT06H2 3P Fixed: 47113
NT06H2 3P Draw-out: 47203
NT06H2 4P Fixed: 47119
Accessoires & Des pièces de rechange
Trip Units: MicroLogique 2.0 / 5.0 / 6.0 / 7.0 (surcharge, délai de courte durée, instantaneous and earth-fault protection)
Accessoires: Motor operating mechanism, contacts auxiliaires, fault alarm contacts, closing coil, shunt trip coil, verrouillage de porte, phase barriers
Draw-out base: Mandatory independent cradle for draw-out version
Directives de dépannage
- Défaut de fermeture: Undervoltage coil de-energized, incomplete spring charging, cradle not in connected position, interlock blocking
- Unintended tripping: Check trip unit protection curve, défaut à la terre, harmonic distortion and temperature rise
- Essai d'isolation: Power frequency withstand test at Ui=1000V level; 12kV impulse withstand is type-test only, no on-site 12kV impulse test
Référence alternative nationale
Domestic MT06H2 (Schneider domestic MT series). Compatible breaking capacity and mounting dimensions for direct replacement.
Schneider MasterPact NT06H2 Air Circuit Breaker Technical Manual (Full Engineering Version, per original datasheet 0613CT0001)
Remarques: NT series is legacy discontinued ACB, frame size NT06, Entrée=630A; breaking class H2; frame supplied without trip unit, MicroLogic trip unit to be ordered separately; standard IEC 60947-2, isolating function, Class B selective protection
Table des matières
- Présentation du produit & Explication du code modèle
- Paramètres électriques évalués
- Paramètres mécaniques, Dimensions hors tout & Poids
- MicroLogic Trip Unit Selection
- Liste des accessoires & Secondary Terminal Definition
- Installation & Exigences de câblage
- Opération, Handling & Interlock Description
- Entretien, Inspection & Dépannage
- Conditions ambiantes
- Replacement Model Information
- Original Document Index
- Présentation du produit & Explication du code modèle
1.1 Aperçu
MasterPact NT series low-voltage air circuit breakers for incoming feeders, bus ties and high-current outgoing feeders in 400/690V low-voltage distribution systems. NT06H2 maximum frame rating 630A, available in draw-out or fixed construction, spring charged operation, configurable with intelligent MicroLogic protection unit, supports remote signalling, metering and communication.
Rappel important: Ui=1000V (rated insulation voltage), Uimp=12kV (lightning impulse withstand voltage). NOT 12kV high voltage circuit breaker, only for AC ≤690V low-voltage distribution.
1.2 Répartition du modèle
NT: MasterPact NT series air circuit breaker
06: Taille du cadre 06, frame rated current 630A
H2: Breaking class H2; Icu=50kA@440VAC, Icw=50kA 1s, Class B selective
Numéros de pièces:
NT06H2 3P Fixed: 47113
NT06H2 3P Draw-out: 47203
NT06H2 4P Fixed: 47119
1.3 Statut du produit
NT series scheduled end-of-sale by end of 2025; replacement model MTZ1 06H2, part number LV947203 (retrait). Mounting dimensions and secondary interfaces fully compatible for direct replacement.
- Paramètres électriques évalués
| Article | Valeur |
| Frame rated current In | 630UN (at 40℃ ambient) |
| Tension assignée d'emploi Ue | CA 50/60 Hz, max 690V |
| Tension assignée d'isolement Ui | 1000V |
| Tension assignée de tenue aux chocs Uimp | 12kV (1.2/50μs lightning impulse) |
| Pouvoir ultime de coupure en court-circuit Icu | 50kA à 440 V; 42kA à 690 V |
| Rated short-time withstand current Icw | 50le, 1s |
| Pouvoir de coupure de service nominal IC | 100% d'ICU |
| Selectivity class | Classe B (with short-time delay selective protection) |
| Isolating function | Complies with IEC60947-2 isolation requirement |
| Nombre de pôles | 3P. / 4P en option |
- Paramètres mécaniques, Dimensions hors tout & Poids
3.1 Endurance mécanique
Durée de vie mécanique: 20,000 opérations (no-load make/break)
Durée de vie électrique (400V, Dans): 10,000 opérations
Spring charging: Manual charging / motor charging MCH optional
3.2 Dimensions hors tout (3P., unité: mm)
Type fixe: W300 × H415 × D266
Type débrochable (with cradle): W300 × H415 × D376
4P version width 360mm, height and depth unchanged
3.3 Poids
Fixed frame only: ≈32kg
Draw-out frame + cradle: ≈52kg
3.4 Three positions for draw-out version
- Connected Position: Main circuit and secondary circuit fully connected, normal operation
- Test Position: Main circuit disconnected, secondary circuit remains connected for protection test
- Disconnected Position: Main and secondary circuits fully disconnected, breaker can be withdrawn for maintenance
- MicroLogic Trip Unit Selection (Must be ordered separately, not included with frame)
| Trip Unit Model | Fonctions de protection | Application typique |
| MicroLogique 2.0 | Long-time overload protection only | Isolator, overload-only protection |
| MicroLogic 5.0A | Long-time Ir, short-time delay Isd, instantaneous Ii | Incoming feeder, bus tie (le plus courant) |
| MicroLogic 6.0A | All functions of 5.0A + protection contre les défauts à la terre | Critical incoming feeder requiring earth fault protection |
| MicroLogic 7.0A | 6.0UN + protection contre les courants résiduels + surveillance des harmoniques | Centres de données, sensitive loads |
Protection setting range: Et (longue durée) 0.4~1×In; Isd short-time delay 0.5~10×In, delay 0.1/0.2/0.4s; Ii instantaneous 1~15×In.
- Liste des accessoires & Secondary Terminal Definition
5.1 Accessoires en option
- MCH: Charging motor AC220V / DC24V
- XF: Closing solenoid AC220V / DC24V
- MX: Shunt trip coil (remote opening)
- MN: Déclencheur à sous-tension (MNu time-delayed undervoltage for auto-transfer application)
- DE: Contacts auxiliaires (CB on/off status feedback)
- SDE: Fault trip contacts (signal for overload/short-circuit/earth fault trip)
- PF: Cradle position contacts (connected / test / disconnected position)
- Phase barriers, cabinet door interlock, mechanical interlock cables, padlock device
- ULP communication module: Modbus-RTU, remote signalling & mesure
5.2 Secondary Terminal Definition
| Code | Nom | Terminaux | Description |
| MCH | Charging motor | B1, B2 | Auto charging upon power-up; B1-B3 charged ready CH contact |
| XF | Closing coil | A1, A2 | Closing actuation |
| MX | Déclenchement de dérivation | C1, C2 | Remote opening |
| MN | Déclencheur à sous-tension | D1, D2 | Trip on loss of voltage, core component for auto-transfer |
| DE | Auxiliary position contact | 11-12 Caroline du Nord /11-13 NON | On/off status feedback |
| SDE | Fault trip contact | 81,82 | Protection action signal |
| PF | Cradle position contact | 251/252/254 | Draw-out position signal |
- Installation & Exigences de câblage
- Montage: Vertical upright installation, ±5° tilt allowed; inverted mounting prohibited
- Connexion du circuit principal: Connexion frontale / rear horizontal / rear vertical connection; apply specified tightening torque for copper busbars to avoid overheating
- Secondary control wiring: 0.75~1.5mm² multi-core shielded cable; independent AC220V/DC24V control power supply for secondary circuit
- Essai d'isolation: Power frequency withstand test at Ui=1000V level; 12kV impulse withstand is type test only, no on-site 12kV impulse test
- Draw-out operation: Use dedicated crank for rack-in / rack-out; prohibit racking out breaker from connected position under live condition
- Opération, Handling & Interlock Description
7.1 Operation Procedure
- Charging: Manual charging handle or MCH motor auto charging; charging complete, charged indicator lights on
- Clôture: Local front panel close pushbutton / XF remote close; verify interlock conditions before closing
- Ouverture: Local open pushbutton / MX remote opening / automatic protection tripping; after fault trip, fault reset button must be manually reset before re-closing
7.2 Verrouillage (Two-incoming one bus tie scheme)
Verrouillage mécanique: Steel cable mechanical interlock, physically prevents simultaneous closing of three ACBs
Verrouillage électrique: Close circuit wired in series with normally closed contacts of other breakers for double protection
Cradle position interlock: Closing circuit blocked when not in connected position, closing prohibited
Fault trip interlock: Auto-transfer closing logic blocked upon SDE contact activation
- Entretien, Inspection & Dépannage
8.1 Entretien périodique
Semi-annual: Check charging status, on/off indication, contact temperature rise, tightness of secondary wiring
Annuel: Dust cleaning, insulation inspection, trip unit test (using MicroLogic test cable)
Révision (chaque 5 années): Disassemble to inspect main contacts and arc chamber, mechanical lubrication, mechanical life verification
8.2 Dépannage typique
- Défaut de fermeture
Incomplete charging; undervoltage MN coil de-energized; cradle not in connected position; interlock blocked; fault trip not reset
- Unintended tripping
Verify protection curve; défaut à la terre; harmonic overload; loose wiring with overheating; voltage dip triggering MN undervoltage trip
- Charging failure
No power supply to MCH motor; jammed charging mechanism; damaged charged-ready contact
- No fault signal output
Wrong SDE auxiliary contact wiring, contacts brûlés
- Conditions ambiantes
Température ambiante de fonctionnement: -5℃ ~ +70℃; déclassement requis au-dessus de 40 ℃
Température de stockage: -40℃ ~ +85℃
Humidité relative: ≤95% (sans condensation)
Altitude: ≤2000m; derating and insulation correction required above 2000m
Degré de protection: Device IP30; IP40 with cabinet door closed
Degré de pollution: 3
- Replacement Model Information
NT06H2 → MTZ1 06H2
Frame 630A, Icu = 50 kA, compatible MicroLogic trip unit
Cotes de montage, primary busbar and secondary terminals fully compatible, no cabinet modification required for in-panel retrofit
Supports ECOSTRUXURE Power software commissioning, upgraded communication interface
Schneider MasterPact NT Full Series Model List (IEC Version, Discontinued ACB, Frame 630~1600A)
Naming Rule: NT + Frame Code + Rompre la classe
Frame Code: 06=630A; 08=800A; 10=1000A; 12=1250A; 16=1600A
Rompre la classe: N1 / H1 / H2 / L1; Construction: Fixé / Débrochable; Poles 3P/4P; Frame without trip unit, MicroLogic to be ordered separately
Common Base Parameters: Ui=1000V, Uimp=12kV, Ue max AC690V, Class B selective protection
Breaking Class Definition (440V, Icu ultimate breaking capacity)
N1: 35le
H1: 42le
H2: 50le (same class as NT06H2)
L1: 130le (current-limiting type, application for high short-circuit capacity)
NT Full Model List
| Cadre | Frame In | Rompre la classe | Modèle complet | Icu@440V | Icw(1s) | Typical 3P Fixed Part No. |
| NT06 | 630UN | N1 | NT06N1 | 35le | 35le | 47111 |
| NT06 | 630UN | H1 | NT06H1 | 42le | 42le | 47112 |
| NT06 | 630UN | H2 | NT06H2 | 50le | 50le | 47113 |
| NT06 | 630UN | L1 | NT06L1 | 130le | 50le | 47114 |
| NT08 | 800UN | N1 | NT08N1 | 35le | 35le | 47121 |
| NT08 | 800UN | H1 | NT08H1 | 42le | 42le | 47122 |
| NT08 | 800UN | H2 | NT08H2 | 50le | 50le | 47123 |
| NT08 | 800UN | L1 | NT08L1 | 130le | 50le | 47124 |
| NT10 | 1000UN | N1 | NT10N1 | 35le | 35le | 47131 |
| NT10 | 1000UN | H1 | NT10H1 | 42le | 42le | 47132 |
| NT10 | 1000UN | H2 | NT10H2 | 50le | 50le | 47133 |
| NT10 | 1000UN | L1 | NT10L1 | 130le | 50le | 47134 |
| NT12 | 1250UN | N1 | NT12N1 | 35le | 35le | 47141 |
| NT12 | 1250UN | H1 | NT12H1 | 42le | 42le | 47142 |
| NT12 | 1250UN | H2 | NT12H2 | 50le | 50le | 47143 |
| NT12 | 1250UN | L1 | NT12L1 | 130le | 50le | 47144 |
| NT16 | 1600UN | N1 | NT16N1 | 35le | 35le | 47151 |
| NT16 | 1600UN | H1 | NT16H1 | 42le | 42le | 47152 |
| NT16 | 1600UN | H2 | NT16H2 | 50le | 50le | 47153 |
| NT16 | 1600UN | L1 | NT16L1 | 130le | 50le | 47154 |
Draw-out part number: ajouter 10 to the last digit. Example NT06H2 3P Draw-out:47203; 4P fixed part number +6 (NT06H2 4P Fixed 47119)
Derivative Isolator Models (HA version)
NTxxHA: Isolator (without trip unit, IEC60947-3)
NT06HA / NT08HA / NT10HA / NT12HA / NT16HA
Compatible Trip Unit List (Universal for full NT series)
MicroLogique 2.0: Long-time overload only
MicroLogic 5.0A: Longue durée + délai de courte durée + instantané (preferred for incoming / bus tie)
MicroLogic 6.0A: 5.0UN + protection contre les défauts à la terre
MicroLogic 7.0A: 6.0UN + protection contre les courants résiduels + harmonic measurement
Replacement Cross Reference Table (NT → MTZ1)
| Legacy NT Model | Replacement MTZ1 Model |
| NT06N1 | MTZ1 06N1 |
| NT06H1 | MTZ1 06H1 |
| NT06H2 | MTZ1 06H2 |
| NT06L1 | MTZ1 06L1 |
| NT08~NT16 follow same rule | MTZ1 08 /10 /12 /16 + cours de rupture |
Selection Remarks
- NT series fully discontinued, not recommended for new projects; MTZ1 can be used for spare parts replacement for existing projects with compatible primary and secondary interfaces.
- L1 current-limiting type for systems with extremely high short-circuit current, coût plus élevé; H2 is preferred for normal incoming feeder and bus tie.
- Rated current can be derated within the same frame by changing current sensor inserts, par exemple. NT06 frame available with 400A/500A/630A sensors.