(Phase Sequence / Perte de phase / 3-Phase Voltage Unbalance)
Série: Zélio Contrôle / Harmony RM17T Series, Montage sur rail DIN 3-phase monitoring relay, commonly known as phase sequence protector.
✅ Monitoring Functions
Phase sequence detection (L1-L2-L3): Instant trip upon reverse phase sequence
Phase loss detection: Instant trip if any phase is lost (including phase loss with regenerated voltage from motors)
3-phase voltage asymmetry (déséquilibrer): Adjustable threshold from 5% à 15% of Un, with time-delayed tripping
Logic rule: Phase reversal / phase loss → instantaneous trip; voltage unbalance → delayed trip.
📌 Key Electrical Specifications
Monitoring voltage range: AC 208~480V (operating limit: 183~528V AC)
Fréquence: 50/60 Hz (±10%)
Output contact: 1 CO (SPDT), 5UN / 250ACC
Time delay adjustment: 0.1~10s (only for unbalance faults)
Reset delay: Environ. 1.5s
Consommation d'énergie: ≤22VA @ 400V 50Hz
Montage: DIN 35mm rail; width 17.5mm (1 largeur du module)
Indication: Status LED; sealed transparent cover prevents accidental parameter changes
🧮 RM17T Series Selection Comparison (Key for Model Selection)
RM17TT00: Séquence de phases + perte de phase (NO unbalance monitoring)
RM17TA00 (Current Model): Séquence de phases + perte de phase + 3-phase voltage asymmetry
RM17TU00: Séquence de phases + perte de phase + sous-tension
RM17TE00: Séquence de phases + perte de phase + asymmetry + surtension + sous-tension (full-function model)
🛠️ Scénarios d'application typiques
Ascenseurs, levage & conveying equipment, compresseurs d'air, pompes à eau, refrigeration units, machines d'emballage; prevents motor reverse rotation, burnout from phase loss, and overheating caused by three-phase unbalance.
🔌 Wiring Guidelines
- Connect L1/L2/L3 directly to the monitored three-phase supply (auto-alimenté, no separate auxiliary supply required).
- Terminaux 15/16/18 form one changeover contact: 15-16 = normally closed; 15-18 = normally open.
- Panel setting: First select rated voltage (208/220/380/400/415/480V), then set unbalance threshold and fault delay time.
- Récupération de panne: Automatic reset once power returns to normal; no manual reset button.
⚠️ Dépannage
Relay does not energize after power-up: Check phase sequence, perte de phase, and voltage range dip switch setting.
Frequent tripping during normal operation: Increase unbalance percentage threshold, extend time delay, and investigate single-phase load current imbalance.
No LED illumination: Three-phase input voltage exceeds the 183~528V operating range.
📎 Replacement Options
Direct upgraded replacement within the same product line: RM22TA33 (RM22 series, same functions with 2 C/O contacts).
Alternatives nationales: Chint / Delixi three-phase phase-sequence & unbalance monitoring relays.
- Full Model List of RM17T Series
(3-phase supply monitoring relays, 17.5mm single-module width, Montage sur rail DIN)
1) Modèle de base: RM17TG (Only phase sequence + perte de phase; no unbalance / undervoltage monitoring)
RM17TG00: 1 C/O changeover contact, 208~480V AC
RM17TG20: 2 C/O dual changeover contacts, 208~440V AC
2) Multifunction Models (RM17TT / PAREMENT / TU / LE, 208~480V AC, 1 C/O contact uniformly)
| Modèle | Fonctions de surveillance de base |
| RM17TT00 | Séquence de phases + perte de phase (version de base, no unbalance / sous-tension) |
| RM17TA00 (Current Model) | Séquence de phases + perte de phase + 3-phase voltage unbalance (asymmetry) |
| RM17TU00 | Séquence de phases + perte de phase + sous-tension |
| RM17TE00 | Séquence de phases + perte de phase + déséquilibrer + surtension + sous-tension (full function) |
Abbreviation explanation:
TU = T + Sous-tension
TE = T + Everything (fonctions complètes)
III. Common Specifications for the Whole Series (All Models Identical)
Plage de tension: AC 208~480V (operating limit 183~528V)
Évaluation des contacts: 5UN / 250ACC; RM17TG00/TT/TA/TU/TE = 1 CO; only RM17TG20 = 2 CO
Largeur: 17.5mm (1P module)
Mode de réinitialisation: Automatic reset after fault clears; no manual reset button
- Upgraded Replacement Models (RM22 Series with Extra Contacts)
RM17TA00 → RM22TA33 (2 C/O contacts)
RM17TU00 → RM22TU23
RM17TE00 → RM22TE33
RM17TA00 Overall Dimensions (L × H × P)
17.5 mm × 90 mm × 72 mm
Largeur: 17.5 mm (1-pole module, same width as 1P MCB)
Hauteur: 90 mm
Profondeur (from DIN rail front face): 72 mm
Montage: DIN35 standard rail
Poids net: Environ. 0.13 kilos
✅ All models in RM17T series (RM17TT00 / RM17TU00 / RM17TE00 / RM17TG00) share identical dimensions.
Core Positioning of RM17TA00
It provides phase sequence + perte de phase + three-phase voltage unbalance protection, mainly for three-phase asynchronous motors. It prevents reverse rotation, motor burnout from phase loss, and overheating caused by long-term voltage imbalance. Auto-alimenté, compact 1-module DIN rail design, ideal for compact control cabinets and retrofitting projects where no PLC signal collection is needed.
- Industrie & Applications d'équipement
- Levage & Convoyage (Demande principale)
Overhead cranes, electric hoists, convoyeurs à bande, gerbeurs, ascenseurs; prevents motor reverse rotation after phase reconnection and overheating damage to gearboxes and motors due to long-term unbalance.
- Ascenseurs & Plateformes élévatrices
Freight elevators, simple lifting platforms, parking lift power circuits; wrong phase sequence causes reverse car movement; voltage unbalance leads to excessive temperature rise of traction motors.
- Pompes à eau & Pumping Stations
High-power centrifugal pumps, submersible sewage pumps, pre-power monitoring before variable-frequency drives; unbalance is frequently caused by mixed single-phase loads in water supply, sewage treatment and chiller pump systems.
- Compresseurs d'air & HVAC Refrigeration Units
Screw air compressors, refroidisseurs d'eau, air-source heat pumps, compresseurs de réfrigération; compressors are highly sensitive to three-phase unbalance, which easily burns out motor windings.
- Conditionnement, Textile & Woodworking Automation
Lignes de conditionnement, machines textiles, extrudeuses, équipement auxiliaire de moulage par injection; frequent power maintenance and phase swapping require phase sequence verification before power-on.
- Fan Loads
Ventilateurs d'extraction, induced draft fans, ventilateurs de séchage; large inertia fans produce regenerated voltage after phase loss; this model supports phase loss detection under regenerated voltage conditions.
- Control Panels & OEM Equipment Matching
380V three-phase control cabinets, non-standard automation OEM factory-fitted protection; old equipment retrofits, hard-contact interlock without adding PLC analog modules.
- Selection Boundary: Approprié / Scénarios inappropriés
✅ Recommandé:
Three-phase motor loads with risks of voltage asymmetry overheating (core advantage over RM17TT00)
Supply voltage AC 208~480V, 50/60Hz
Espace de rangement limité, seulement 1 module width available
Hard-contact interlock directly wired into main contactor coil circuit
❌ Not recommended:
Surtension + undervoltage monitoring required → choose RM17TE00
Only undervoltage protection without unbalance → choose RM17TU00
Dual independent alarm contacts required → upgrade to RM22TA33 (2CO)
Motors behind variable-frequency drives: VFDs already have built-in phase loss & protection contre le déséquilibre; extra relay is generally unnecessary.
III. Typical Control Logic
Contact wired in series with the main contactor coil circuit:
Normal power supply → relay energizes and closes, contactor power permitted;
Phase reversal / perte de phase / voltage unbalance detected → relay de-energizes and opens, cutting off main power, with dry contacts available for PLC or audible-visual alarm signals.
Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur