SIMATIC ET200SP RQ 4×120VDC…230VAC/5A NO ST Relay Output Module Distributed IO ET200SP, 4-channel normally-open digital relay output module, contact isolated type ✅ Model Code Interpretation 6ES7: SIMATIC S7 Automation System 132: ET200SP Digital Output Module 6HD01: 4-channel relay output, 120VDC~230VAC, 5A normally open 0BB1: Single pack (1 unité par boîte); `2BB1` = 10-piece bulk pack ...

  • Détails du produit

SIMATIC ET200SP RQ 4×120VDC…230VAC/5A NO ST Relay Module de sortie

Distributed IO ET200SP, 4-channel normally-open digital relais output module, contact isolated type

✅ Model Code Interpretation

6ES7: SIMATIC S7 Automation Système

132: ET200SP Digital Output Module

6HD01: 4-channel relay output, 120VDC~230VAC, 5A normally open

0BB1: Single pack (1 unité par boîte); `2BB1` = 10-piece bulk pack

📋 Key Technical Specifications

ArticleParamètre
Nombre de chaînes4 normally-open relay outputs (NON), channel-to-channel isolation
Contacter l'évaluation120V DC ~ 230V AC, maximum. 5Un par canal
Base Unit TypeCompatible with BU B0 / BU B1 base units; color code CC40
Backplane Bus Supply55mA, typical power consumption 1.5W
Fonctions de diagnosticModule supply diagnostics, substitute value output
Température de fonctionnement0 ~ +60 ℃ (standard module)
CommunicationPROFINET / PROFIBUS-DP (with ET200SP interface module)
Code SH85389091

🧩 Features

  1. Relay dry contact isolation: Galvanic isolation between PLC low-voltage side and load high-voltage side. Suitable for solenoid valves, contacteurs, indicator lamps and other AC loads.
  2. Substitute value: When communication fails or CPU stops, output state can be preset in TIA Portal: hold / reset to 0 / réglé sur 1.
  3. Channel status LEDs + module diagnostic LED for fault alarm.
  4. Separate base & electronic module design: Hot-swappable electronics while wiring remains on base for easy maintenance.

⚙️ Typical Application Scenarios

Control of 220VAC solenoid valves, small contactors, lampes d'alarme, fan start/stop in control cabinets

Not suitable for high-frequency switching applications (limited relay mechanical service life; cannot handle high-speed pulses)

Distributed remote IO station deployed with IM155-6 interface module

⚠️ Sélection & Remarques sur le câblage

  1. Base unit must be BU B0 / BU B1 type, A-type bases are incompatible; recommended BU20-P16+A0+2B.
  2. Relay contacts are passive dry contacts. Load power is not supplied by module backplane, external power supply required.
  3. Charges inductives (bobines de contacteur) are recommended to connect varistor / freewheeling diode in parallel to extend relay service life.
  4. 5A per channel is rated current; pay attention to heat dissipation when all 4 channels run at full load simultaneously.

📌 Alternative & Modèles dérivés

6AG1132-6HD01-7BB1: SIPLUS wide-temperature conformal coated version, -40~+70℃, for harsh environments (industrie chimique, de plein air)

Alternatives nationales: ET200SP compatible 4-channel normally-open 5A relay modules. Verify base compatibility and diagnostic telegram.

Application Scenarios for 6ES7132-6HD01-0BB1 (ET200SP 4-Channel Relay Output Module)

Core features: Passive dry contacts, isolation des canaux; maximum. 5A pour les charges résistives, maximum. 2A for inductive loads; supports 24V~230V AC/DC loads; PROFINET distributed remote IO. Ideal for low-frequency switching control requiring galvanic isolation between strong and weak circuits.

  1. Industry-specific Applications
  2. Machinery Manufacturing (Le plus courant)

220VAC pneumatic & hydraulic solenoid valve control (cylinder, hydraulic valve on/off)

Drive coils of small AC contactors to indirectly control fans, pompes, convoyeurs

Equipment alarm lights, audible & visual alarms, panel indicator lamps

Door interlock, guard door signal output, equipment enable signal

En vigueur: Machines d'emballage, machines-outils, lignes de production, machines de moulage par injection, textile machinery remote IO stations

  1. Automatisation des processus / Traitement de l'eau

Remote field cabinet: 220V solenoid valves, dosing pumps, drain valves, agitator start/stop control

Field instrument power switching, feux d'avertissement, on-site audible & visual alarms

Water tank level interlock output; remote stations deployed at different plant locations

Avantage: Relay isolation prevents field high-voltage interference from coupling into PROFINET bus

  1. CVC & Automatisation des bâtiments

AC220V air damper actuators, electric butterfly valve on/off control

Contactor coil control for fans, ventilateurs d'extraction, pompes à eau

Fire linkage signal output, on-site alarm indication

  1. Énergie, PV & Power Auxiliary Control

Switchgear auxiliary circuit, relay loop switching, alarm contact output

Small heater, dehumidifier on/off control

Signal isolation transfer: Convert PLC low-voltage signals to dry contacts for 3rd-party systems (DCS, relay protection)

  1. Supported Load Types
  2. AC220V solenoid valves, voyants lumineux, buzzers
  3. AC220V contactor / bobines de relais intermédiaires
  4. Charges résistives: heating tapes, lampes à incandescence (≤5A)
  5. DC24V~DC120V DC loads (dry contacts work for both AC and DC)
  6. Passive contact output for hard-wired interlock with other control systems

III. Applications inappropriées

  1. ❌ High-frequency switching: Mechanical relay has limited service life, not for multiple operations per second. Use transistor DQ modules for high frequency.
  2. ❌ Direct drive of high-power motors (only drives contactor coils, not main motor circuit)
  3. ❌ Inductive load current exceeding 2A (solenoid & contactor are inductive loads; varistor / freewheeling diode required to absorb back EMF)
  4. ❌ Safety circuits (this module is non-failsafe. F-RQ failsafe modules are required for emergency stop and safety gate circuits)
  5. ❌ High inrush current loads (contact erosion risk; each channel needs external 6A max. fast fuse protection)
  6. Architecture Characteristics

ET200SP distributed IO: This module is mounted in remote field enclosures away from the main PLC and connected via IM155-6 PROFINET interface module.

Load wiring for 220VAC is routed locally, reducing long-distance high-voltage cables

Relay isolation protects PLC low-voltage system and improves EMC immunity

Substitute value configurable in TIA Portal: Output state can be defined for bus interruption or CPU stop to ensure safe equipment status

ET200SP Digital Output Module Selection Comparison Sheet

Compare 6ES7132-6HD01-0BB1 (RQ 4-channel relay output) vs common transistor DQ modules

  1. Tableau de comparaison des paramètres de base
Article6ES7132-6HD01-0BB16ES7132-6BH01-0BA06ES7132-6BD20-0BA0
Relay Output RQTransistor DQ 16×24VDCTransistor DQ 4×24VDC/2A
Type de sortiePassive dry contact, normally-open relay NOTransistor PNP, active 24VDCTransistor PNP, active 24VDC
Nombre de chaînes4 chaînes16 chaînes4 chaînes
Load Voltage Range120VDC ~ 230VAC, CA & Compatible CCDC24V seulementDC24V seulement
Courant nominal par canal5A resistive; 2A inductive0.5Un par canal2Un par canal
Galvanic Isolation✅ Channel isolation, strong/weak voltage isolation❌ No channel isolation, common 24V ground❌ No channel isolation
Vitesse de réponseLent: millisecond level (mechanical contact)Fast: microsecond levelFast: microsecond level
Durée de vieMechanical life ~10⁷ operations (low frequency)Nearly unlimited electronic life, high frequency capableNearly unlimited electronic life
Charge typiqueAC220V solenoid valves, bobines de contacteur, audible/visual alarms, dry-contact interlockDC24V solenoid valves, voyants lumineux, sensor power supplyHigh-current DC24V loads, DC solenoid valves
Base Color CodeCC40CC01CC01
  1. When to select 【6ES7132-6HD01-0BB1 Relay Module】

✅ Recommandé

  1. Load voltage is AC220V, no extra intermediate relay required on site
  2. Galvanic isolation required, heavy field interference, prevent high voltage from damaging PLC IO bus
  3. Need passive dry contact output for hard-wired interlock to 3rd-party DCS / protection relays
  4. Low switching frequency (triggered every few minutes/hours, not frequent on/off)
  5. Chargements mixtes: both AC220V and DC loads up to 120V

❌ Non recommandé

  1. Commutation fréquente: multiple start-stop per second (rapid contact wear and shortened lifetime)
  2. Pure DC24V loads with large point count requirement (transistor modules cheaper, higher channel density)
  3. High-speed pulse & motion control output (relay cannot generate pulses)
  4. SIL safety circuits (Failsafe F-series modules required)

III. When to select 【Transistor DQ Module】

✅ Recommandé

  1. All loads are DC24V, frequent switching (continuous actuation of cylinder solenoids)
  2. Requirement for high-speed switching signals or pulse outputs
  3. Large I/O point count, high channel density to save cabinet space
  4. Field loads are low-current DC components without isolation requirement

❌ Non recommandé

  1. AC220V loads: must add external intermediate relays
  2. Severe field high-voltage interference without isolation; risk of IO module burnout
  3. Quick Selection Rule

Charger: AC220V, low frequency, isolation required → 6ES7132-6HD01-0BB1

Charger: DC24V, frequent operation → Transistor DQ (6BH01 for many points / 6BD20 for high per-channel current)

  1. Additional Selection Notes
  2. Charges inductives (électrovannes, contacteurs) need absorption components: varistor in parallel for AC loads, freewheeling diode for DC loads to suppress back EMF and extend contact life.
  3. Relay module base color code CC40, not interchangeable with transistor DQ base CC01.
  4. Cost reference: Relay modules usually cost more for same channel quantity. Cependant, overall system cost may be lower when eliminating external intermediate relays.
  5. Failure characteristics: Relay contacts risk sticking; transistor modules mostly fail by breakdown with no mechanical sticking risk.
  6. Special Alternatives

Failsafe output: 6ES7136-6DB00-0CA0 (F-DQ for safety circuits)

Solid-state relay output (no moving contacts, suitable for high-frequency AC switching): ET200SP RQ solid-state relay models