Relais de contrôle Schneider CA4KN31BW3

CA4KN: TeSys K series control relay 31: Configuration des contacts: 3 NON + 1 NC B: 24 V DC low-consumption coil with built-in bidirectional freewheeling diode W3: Screw clamping terminals Core Technical Parameters Coil: 24 V DC low-power coil, integrated bidirectional peak suppression diode Contact arrangement: 3 Normalement ouvert + 1 Normalement fermé (3NON+1NC), 4-pole Conventional ...

  • Détails du produit

CA4KN: TeSys K series control relay

31: Configuration des contacts: 3 NON + 1 Caroline du Nord

B: 24 V DC low-consumption coil with built-in bidirectional freewheeling diode

W3: Screw clamping terminals

Paramètres techniques de base

Bobine: 24 V DC low-power coil, integrated bidirectional peak suppression diode

Modalités de contact: 3 Normalement ouvert + 1 Normalement fermé (3NON+1NC), 4-pôle

Courant thermique conventionnel Ith: 10 UN (à 50 °C)

Tension assignée d'isolement Ui: 690 V

Utilisation category: AC-15 / DC-13 (standard control circuit loads)

Montage: DIN35 rail mounting or base plate fixing

Câblage: Bornes à vis, couple de serrage 1.3 N·m

Dimensions: W45 mm × H58 mm × D57 mm

Endurance mécanique: 20 millions d'opérations

Recommended protection: 10 A gG fuse

Origine: Indonésie

Applications typiques

PLC digital output expansion, signal isolation & transfer, logic interlocking, indicator lamp driving, small solenoid/coil actuation. It is an auxiliary control relay, not intended for high-power main circuits. It shares the same footprint as TeSys K contactors and can be installed side-by-side.

Cross-reference for Replacement & Sélection

CA4KN22BW3: 2NON+2NC, 24 À DC, bornes à vis

CA4KN40BW3: 4NON, 24 À DC, bornes à vis

CA4KN31BN3: Spring-cage terminal version (replaces W3)

Code SH des douanes

HS code: 85364190 (Electromagnetic relays, rated voltage ≤60 V)

Common Replacements

Alternatives nationales: Chint / Délicieux 24 V DC control relays with 3NO+1NC contact configuration.

Schneider direct upgrade: other coil variants within the CA4KN series (par ex., 110 À DC).

Typical Application Cases for CA4KN31BW3 (3NON+1NC, 24 V DC Low-Consumption Control Relay)

Avantages clés: built-in bidirectional freewheeling diode, faible consommation d'énergie de la bobine, direct PLC DO driving; 3NO+1NC allows 3 output channels plus 1 feedback channel; AC-15/DC-13 rated, fréquence de fonctionnement maximale: 180 cycles par minute.

Cas 1: PLC Digital Output Port Expansion (Le plus courant)

Scénario: Insufficient PLC DO points; DO ports have low current capacity (<0.5 UN) and need to drive multiple contactor coils and solenoid valves simultaneously.

Câblage: API 24 V DO connected to relay coil terminals A1/A2

Contact assignment:

NON1: Drive LC1D contactor coil

NO2: Conduire 24 V DC solenoid valve

NO3: Run indicator lamp

NC1: Feedback to PLC DI for relay status monitoring (rupture de fil / contact sticking diagnosis)

Points forts: Low-power coil avoids overloading PLC outputs; built-in diode eliminates external surge suppression circuits; same TeSys K form factor for neat cabinet layout, standard panel builder solution.

Secteurs: Machines-outils, machines d'emballage, assembly line control cabinets.

Cas 2: Auxiliary Logic Interlock & Status Collection for Main Contactors

Scénario: Main LC1D contactors have insufficient built-in auxiliary contacts; additional interlocking, fault feedback and on/off indication are required.

Driving signal: Emergency stop circuit / safety relay output energises the CA4KN coil

Contact assignment:

NON1: Enable forward rotation circuit

NO2: Enable reverse rotation circuit

NO3: Contactor ON run lamp

NC1: Wired into reverse circuit for hardware interlock (prevents simultaneous forward & reverse operation)

Note: This is only control-circuit interlocking and cannot replace main-circuit electrical interlocks.

Secteurs: Équipement de transport, small lifting mechanisms, ventilateur & pump control panels.

Cas 3: Ventilateur & Damper Interlock Control for HVAC Air Handling Units

Scénario: DDC controller outputs control damper actuators, fan contactors and alarm lamps, with one status feedback channel to the building BA system.

Driving signal: 24 V DC output from DDC energises CA4KN31BW3

Contact assignment:

NON1: Damper open command

NO2: Fan contactor coil

NO3: Running status lamp

NC1: DI input to BA system for stop / fault feedback

Avantages: High noise immunity with built-in diode, suitable for frequent switching in weak-current building control loops; large plage de températures de fonctionnement (-25 °C ~ +50 °C) for indoor plant rooms.

Secteurs: Automatisation des bâtiments, clean air conditioning, fresh air handling units.

Cas 4: Primaire & Standby Pump Rotation Control Relay

Scénario: Level controller / PLC output switches main pump, standby pump and alarm circuits with independent status feedback.

Logique: High water level signal energises the relay coil

NON1: Main pump start

NO2: Standby pump activation (coordinated with delay circuit)

NO3: Overflow alarm lamp

NC1: Relay fault detection signal to PLC

Secteurs: Sewage lifting, traitement de l'eau, water supply control panels.

Cas 5: Signal Expansion after Safety Relay Outputs

Scénario: XPS safety relay has limited output contacts; safety OK signals need to be duplicated to inverter enable, alarm and HMI status channels.

Driving signal: Safety relay OK output energises CA4KN coil

NON1: Inverter STO / enable signal

NO2: Safety OK indicator lamp

NO3: HMI DI safety status input

NC1: Safety circuit trip alarm

Critical reminder: Safety judgment remains the responsibility of the XPS safety relay; CA4KN only serves as signal transfer and cannot be used as a safety component alone.

Secteurs: Lignes de production automatisées, robot peripherals, cutting machinery.

Cas 6: Isolated Passive Signal Transfer for Variable Frequency Drives / Démarreurs progressifs

Scénario: VFD relay output is a dry contact; multiple isolated signals need to be sent to PLC, local alarms and data loggers, with mixed AC/DC circuits.

Driving signal: VFD “Courir” dry contact controls the relay coil

NON1: PLC DI running signal

NO2: Local AC220 V run indicator

NO3: Remote SCADA transmission signal

NC1: Stop status signal

Valeur: Galvanic isolation between 24 V coil side and contact side, preventing electrical noise from coupling into the VFD mainboard.

Sélection & Application Best Practices (Frequent Engineering Pitfalls)

  1. Type de charge: Only for control circuit loads (bobines de contacteur, solénoïdes, voyants lumineux); never for main power circuits. Courant thermique nominal: 10 UN, utilisation category AC-15.
  2. Coil note: BW3 = 24 V DC low-consumption with built-in bidirectional diode. Do NOT add external LAD4RC surge suppressors, as specified in Schneider official documentation.
  3. Terminaux: W3 = screw terminals; spring-cage alternative: CA4KN31BN3.
  4. Contact logic for 3NO+1NC: 3 output channels + 1 feedback channel, the most widely used contact allocation for automation panels.
  5. Montage: DIN35 rail installation; can be mounted side-by-side with LC1K contactors for consistent cabinet layout.

TeSys K Control Relays (CA2KN / CA3KN / CA4KN) – Full Model Coding Rule

Format de modèle complet: CAu KNvw + voltage code + terminal suffix

  1. u = Coil Type

CA2KN: Bobine CA (50/60 Hz)

CA3KN: Standard DC coil (normal power consumption)

CA4KN: Low-consumption DC coil (built-in bidirectional freewheeling diode, PLC direct drive preferred; CA4KN31BW3 falls into this category)

  1. vw = Contact Combination (seulement 3 fixed configurations)

40: 4NON (4 Normalement ouvert)

31: 3NON+1NC (3 Ouvrir + 1 Fermé, le plus populaire)

22: 2NON+2NC (2 Ouvrir + 2 Fermé)

  1. Code de tension + Terminal Suffix (Key Part)

W3: Screw clamping terminals

N3: Bornes à ressort

Suffixe “3” = built-in surge suppression diode

Configuration des contacts (Seulement 3 Options for the Whole Series)

  1. 40 = 4NO
  2. 31 = 3NO+1NC (CA4KN31BW3 uses this configuration)
  3. 22 = 2NO+2NC

Liste complète des modèles: CA4KN Low-Consumption DC Coil (PLC Version, Built-in Diode)

Bobine: DC low power, integrated bidirectional freewheeling diode; Terminaux: W3 screw / N3 spring cage

1) 24 À DC (Les plus populaires: BW3 / BN3)

Configuration des contactsBornes à vis (W3)Spring Terminals (N3)
4NONCA4KN40BW3CA4KN40BN3
3NON+1NCCA4KN31BW3 (Votre modèle)CA4KN31BN3
2NON+2NCCA4KN22BW3CA4KN22BN3

2) 48 À DC (EW3 / EN3)

CA4KN40EW3 / CA4KN40EN3

CA4KN31EW3 / CA4KN31EN3

CA4KN22EW3 / CA4KN22EN3

3) 72 À DC (SW3 / SN3)

CA4KN40SW3 / CA4KN40SN3

CA4KN31SW3 / CA4KN31SN3

CA4KN22SW3 / CA4KN22SN3

Note: CA4KN series only offers 12/24/48/72 V DC low-consumption variants; no AC coil versions. CA4KN was discontinued at the end of 2024; new projects shall adopt CA3KN models with suffix “3” as direct replacements.

CA3KN Standard DC Coil (Normal Power, Built-in Diode Suffix “3”)

Voltage Codes (Vis: BD/ED/FD…; Printemps: BD3/ED3…)

12 À DC: JD / JD3

24 À DC: BD / BD3 (Top replacement: CA3KN31BD3 for CA4KN31BW3)

48 À DC: ED / ED3

110 À DC: FD / FD3

125 À DC: DG / GD3

220 À DC: MARYLAND / MD3

Full Model Examples (3 Contact Types)

  1. 24 V DC screw terminals (with built-in diode)

CA3KN40BD3 (4NON)

CA3KN31BD3 (3NON+1NC, direct replacement for CA4KN31BW3)

CA3KN22BD3 (2NON+2NC)

  1. Bornes à ressort: keep the voltage code unchanged, only adjust terminal suffix; par ex., CA3KN31BD3 (vis) and spring-cage variant share the same voltage code.

CA2KN AC Coil (50/60 Hz, Main Control Circuits)

Common Voltage Codes

24 V et: B7

48 V et: E7

110 V et: F7

220/230 V et: M7 / P7 (most used: CA2KN31P7)

380 V et: Q7

Full Contact Models (Bobine CA)

4NON: CA2KN40B7 / CA2KN40P7

3NON+1NC: CA2KN31B7 / CA2KN31P7

2NON+2NC: CA2KN22B7 / CA2KN22P7

Terminal Differentiation (W3/N3 vs Non-Suffix “3”)

  1. W3 = Screw clamping terminals (CA4KN31BW3)
  2. N3 = Spring-cage quick connect terminals (remplacement: CA4KN31BN3)
  3. Models without trailing “3”: No built-in diode; external RC snubber is mandatory for DC circuits – not recommended for direct PLC DO driving.

Discontinuation Replacement Solution (Field Retrofit)

Modèle original: CA4KN31BW3 (24 V DC low-consumption, 3NON+1NC, bornes à vis)

✅ Direct drop-in replacement: CA3KN31BD3 (24 V DC standard coil + diode intégrée, 3NON+1NC, bornes à vis; empreinte identique, plug-and-play interchange)

Spécifications techniques générales (Uniform for All TeSys K Control Relays)

Contact utilisation category: AC-15 / DC-13 (control circuit only)

Courant thermique conventionnel: 10 UN (à 50 °C)

Tension d'isolement nominale: 690 V

Montage: DIN35 rail or base plate fixing

Largeur hors tout: 45 mm, same form factor as LC1K contactors for side-by-side mounting

Endurance mécanique: 20 millions d'opérations