Nom du produit: NTC Water Capteur de température (Copper Immersion Temperature Probe)
Genuine OEM spare part for YORK centrifugal chillers, part of the sensor series for YMC2 magnetic bearing centrifugal chillers
✅ Spécifications de base
Taper: NTC thermistor sensor
Nominal resistance: 3K @25°C (NTC3855)
Sonde: Copper encapsulated immersion probe with fast response
Equipped with original factory connector, directly pluggable into the unit’s OptiView control board
Application: Supply/return chilled water, cooling water, température de décharge, drive module temperature measurement and freeze protection
📌 Suffix Differentiation for the Same Series (Critical for Replacement)
025W29964-000: Basic water temperature probe
025W29964-001: Same electrical curve, differs in cable length and connector assembly
025W29964-002: Standard probe for VSD drive cooling protection kit, most widely used for YMC2
025W29964-004: Upgraded replacement version, accuracy ±2°C, interchangeable with 002
Note: 000, 001, 002, 004 share identical electrical curves. Differences lie in cable length, connector sheath and mounting base. Direct interchange is not allowed on some unit models. Always purchase according to the unit spare parts list.
Unités compatibles
YORK YMC2 magnetic bearing centrifugal chillers (Johnson Controls magnetic levitation chillers). Also applicable to selected YK and YV centrifugal models for evaporator/condenser water temperature and VSD variable frequency drive temperature monitoring.
🛠️ Fault Diagnosis
- Controller reports temperature sensor fault, unstable temperature reading or reading stuck at extreme values
- Measurement with multimeter resistance mode: environ. 3kΩ at 25°C; resistance decreases as temperature rises
- Common failures: dommages au câble, water ingress and corrosion at connector, thermistor drift inside copper probe
📎 Remarks
Marking notation: `025W29964-000` / `025-29964-000` refer to the same part; W is just a separator variant
Replacement guideline: Genuine OEM part is preferred. Alternative sensors must match the 3K NTC3855 curve, otherwise the chiller will trigger faults and false freeze protection
025W29964-000 (NTC3855, R25=3000Ω, B25/50=3855K)
For YORK YMC2 magnetic bearing chiller, original curve for multimeter maintenance reference. Plage de température: -20°C ~ 80°C (normal operating water temperature range of the unit)
| Temp°C | Resistance kΩ | Temp°C | Resistance kΩ |
| -20 | 17.92 | 35 | 2.34 |
| -15 | 14.7 | 40 | 2.05 |
| -10 | 12.12 | 45 | 1.81 |
| -5 | 10.05 | 50 | 1.6 |
| 0 | 8.38 | 55 | 1.42 |
| 5 | 7.04 | 60 | 1.27 |
| 10 | 5.96 | 65 | 1.14 |
| 15 | 5.08 | 70 | 1.03 |
| 20 | 4.36 | 75 | 0.93 |
| 25 | 3 | 80 | 0.85 |
| 30 | 2.64 |
Notes complémentaires
- Power off the unit and isolate the probe from the chiller, wait until temperature stabilizes before measurement, to avoid reading deviation caused by board power supply and self-heating effect
- Tolérance: Original ±1%. Replacement sensors must strictly comply with NTC3855 / 3K@25°C. Mismatched B-value will trigger sensor faults
- Shared curve for freeze protection and VSD drive temperature probes
- Temperatures below -20°C and above 80°C are rarely used on the unit. Portée étendue (-40~120°C) table is available upon request
Quick Fault Judgement
Measured resistance deviates significantly from 3kΩ at 25°C → Failed probe
Résistance infinie: Internal open circuit; Resistance close to 0: Court-circuit interne
YORK (Contrôles Johnson) Chiller Temperature Sensor List (025 Série, mainly for centrifugal / magnetic bearing chillers, including 025W29964)
Note: Two writing formats for part numbers 025-XXXX-XXX/ 025WXXXX-XXX represent the same spare part. All are NTC thermistors, sorted by compatible unit and measurement location
- Sensors for YMC2 Magnetic Bearing Centrifugal Chiller (3K@25°C, B=3855, same series as the referenced model)
| Numéro de pièce. | Description | Remarques |
| 025W29964-000 | Immersion water temperature sensor (evaporator/condenser/drive cooling) | Modèle de base, 3K NTC3855 |
| 025W29964-001 | Water temperature probe with identical curve | Variation in cable and sheath |
| 025W29964-002 | Drive module cooling temperature probe (standard for kit) | Most popular for YMC2 |
| 025W29964-004 | Upgraded replacement | Can replace 002, accuracy ±2°C |
- YK Traditional Centrifugal Chiller (R134a/R1234ze) Eau & Refrigerant Temperature Probes
| Numéro de pièce. | Description | Remarques |
| 025-47669-000 | Fournir & return water temperature sensor | YK evaporator inlet / outlet water |
| 025-47673-000 | Refrigerant temperature sensor | Décharge / saturated refrigerant temperature |
| 025-28935-000 | Water temperature NTC probe | Older YK F/G/H models |
| 025-34159-000 | Refrigerant temperature sensor | Early YK units |
| 025-52739-000 | Fournir & return water probe | New generation YK |
| 025-52740-000 | Spare water temperature probe | Assorti à 52739 |
| 025-53145-000 | Fournir & return water temperature sensor | Replacement for 025-52739-000 |
- Oil Temperature & Bearing Temperature Sensors (Centrifugal Compressor Dedicated)
| Numéro de pièce. | Description | Remarques |
| 025-34177-000 | Oil sump temperature sensor | YK oil tank temperature |
| 025L02246-000 | Bearing temperature probe | Compressor bearing temperature monitoring |
| 025-39517-000 | Oil supply temperature sensor | Oil system monitoring |
- YV Variable Speed Centrifugal, YVAA/YVFA Water-Cooled Chillers
| Numéro de pièce. | Description | Remarques |
| 025W39721-001 | Water temperature probe | YV series |
| 025W39721-002 | Immersion water temperature sensor | YVAA/YVFA |
| 025-40334-000 | Refrigerant temperature sensor | YV compressor discharge |
- Screw Chiller (YS/YEWS) Capteurs de température
| Numéro de pièce. | Description | Remarques |
| 025W48195-001 | Eau / discharge temperature sensor | YS screw chiller |
| S1-025-49696-000 | Coil temperature sensor (10K) | Commercial air-cooled screw & heat pump |
- Johnson Controls Standalone BAS Sensors (A99 / TE Series, not built-in chiller spare parts, pour l'immotique)
These are Johnson Controls branded sensors, not YORK 025-series chiller OEM spares, used for BAS systems:
A99LY-200C, A99LY-300C: PTC duct & pipe temperature sensors
TE-6361A-1, TE-6361M-1: 10K Type II NTC duct probes
✅ Sourcing & Règles de remplacement (For Maintenance)
- Interchangeability only when B-value matches: All variants of 025W29964 (000/001/002/004) are 3K NTC3855
- Many probes for YK/YV/YS are 10K NTC, not compatible with 3K YMC2 probes; direct installation will trigger faults
- Distinguish types: Water immersion probe (copper tube), refrigerant probe (high-pressure resistant package), oil temperature probe (oil-resistant package). Similar appearance but different pressure and medium resistance
- Complete OEM kit: 325-29964-604 (YK water side full sensor kit including 4 pcs 025W29964-002)
📌 Supplementary Notes
Full YORK spare parts database is available in HVAC Navigator, the correct probe can be locked by unit serial number
The above list covers high-volume models commonly seen on site, not the complete Johnson Controls part library
Si nécessaire, I can export separate data: NTC resistance (R25), B-value, Steinhart-Hart coefficients and HS code for each part number
Champs applicables (For 3K@25°C, B=3855, YORK 025W29964-000 YMC2 NTC)
Condition préalable: This resistance-temperature table is only valid for NTC with R25=3kΩ and B-value=3855K. Not applicable for NTC with different B-values.
- CVC & Réfrigération (Primary Original Application)
Maintenance and testing of YORK YMC2 magnetic bearing centrifugal chillers, YK/YV centrifugal chillers
On-site multimeter comparison to check open circuit, court-circuit, resistance drift and aging
Calibration for chilled water, cooling water, VSD temperature and freeze protection loops
Chiller retrofit, alternative sensor selection and incoming inspection of replacement probes
Troubleshooting and commissioning for building cooling stations and central air conditioning control cabinets
- Automatisation industrielle & Programmation API
API (Siemens, Mitsubishi, Allen‑Bradley etc.) analog acquisition and NTC temperature conversion programming
Curve lookup calibration for temperature controllers and custom replacement mainboards
Temperature conversion logic for SCADA and HMI (lookup table method reduces computing load vs real-time exponential calculation)
Note: The original controller uses Steinhart-Hart equation. This B-value table is for simple acquisition and maintenance reference only. Not recommended for high-precision chiller firmware
- Spare Parts Foreign Trade, Approvisionnement & Contrôle qualité (Ideal for your industrial spare parts website)
Technical specifications, datasheets, quality inspection notes and SEO knowledge base content for product pages
Incoming quality control for suppliers: sampling inspection of NTC resistance
Technical reference for overseas clients and maintenance subcontractors
Attachment for alternative sensor datasheets and technical agreements
- Laboratoire, Metrology & Incoming Testing
Fast screening of NTC thermistor samples and preliminary failure judgement
Comparative test with constant temperature bath to preliminarily verify B-value 3855
Note: Not for official metrology certification. Formal calibration requires certified calibration reports
- Other Equipment Compatible with 3K3855 NTC (Non-YORK Units)
Many industrial temperature control devices adopt the same NTC specification:
Industrial chillers, oil chillers, laser cooling units and spindle cooling systems
Battery cooling systems and thermal management (some older BMS)
Mold temperature controllers and small industrial heat pumps
⚠️ Important reminder: Most new energy storage NTCs are 10K, 5K or 10K3950, this table cannot be used
❌ Scénarios inappropriés
- High-precision metrology, third-party certification and factory calibration (Steinhart-Hart coefficients + multi-point calibration required)
- Other NTC specifications: 10K3950, 5K, 20K, CTP, PT100/PT1000 RTD
- Safety interlock and freeze protection firmware development (YORK mainboard uses Steinhart-Hart; B-value table brings deviation at low temperature and may cause false alarms)
- Medical equipment and precision laboratory instruments requiring ultra-high accuracy
On-site maintenance, essai multimètre, incoming QC, simple PLC programming and spare parts documentation → B-value resistance-temperature table can be used
Chiller mainboard firmware, high-precision acquisition and OEM-level replacement development → Steinhart-Hart coefficients are preferred
Industries applicables (For 3K@25°C B3855 NTC, YORK 025W29964-000 R-T Table)
Condition préalable: Only valid for NTC thermistor with R25=3kΩ and B-value=3855K. Not applicable for other NTC specifications.
- CVC & Industrie du froid (Native Application)
Maintenance of centrifugal chillers, magnetic bearing chillers, screw chillers, industrial chillers, oil chillers, heat pumps and cooling stations; service troubleshooting, incoming inspection of spare parts, validation of alternative probes and freeze protection commissioning. Same NTC specification widely adopted by YORK, Contrôles Johnson, Trane, McQuay and other large water-cooled chiller OEMs and after-sales service.
- Industrial Automation Industry
API, contrôleurs de température, custom control boards, SCADA and HMI programming; equipment thermal retrofit, control cabinet integration and temperature acquisition logic debugging; cooling water, hydraulic oil and lube oil temperature monitoring.
- Industrial Spare Parts Trading & Import/Export Industry
Datasheets, documents techniques, pre-sales technical support, maintenance reference for overseas clients and incoming QC standards. Suitable for foreign trade websites, spare parts distributors and engineering subcontractors.
- Laser Equipment Industry
Laser chillers, laser spindle cooling and fiber laser cooling units; many water cooling systems adopt 3K3855 NTC.
- Mold Temperature Control Industry
Water and oil mold temperature machines, water side temperature monitoring and over-temperature protection loop testing.
- Stockage d'énergie & Battery Thermal Management Industry (Selected Legacy Models)
Battery cooling plate and liquid cooling thermal loops (only older BMS versions; most new designs use 10K3950, verify parameters before selection).
- Machine-outil & Spindle Industry
CNC spindle water cooling, hydraulic station cooling system temperature monitoring and oil over-temperature protection.
- Conditionnement & Industrie du plastique
Chillers for extruders and injection molding machines, cooling loop temperature verification.
- Metrology Testing (Rough Screening, Not Legal Metrology)
Fast screening of NTC components by manufacturers and third-party labs; for engineering reference only, not for metrology certification reports.
❌ Industries & Scenarios Where This Table Is Not Suitable
Medical devices and precision instruments (require high accuracy calibration with Steinhart-Hart coefficients)
Mainstream new energy BMS and charging piles (mostly 10K3950)
Food sterilization, precision cold chain verification and laboratory metrology calibration
Equipment using PT100/PT1000 RTD and PTC sensors
Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur