Informations de base sur le produit
Marque: SAMWHA EOCR (Schneider Korea)
Type de produit: EOCR-SS Series Knob-type Electronic Motor Protector (Replaces traditional thermal overload relays)
- Model Code Breakdown of EOCRSS-60NW7PQ
| Segment | Code | Définition |
| EOCRSS | Série | SS Economy Integrated Through-Core Motor Protector |
| 60 | Note actuelle | Built-in CT, adjustable rated current: 5.0~60A, compatible with 1.5~30kW three-phase motors |
| N | Mode de protection | Type N Fail-Safe: Contacts open and contactor trips upon protector power loss or fault; Type R does not trip when power fails |
| W7 | Alimentation | W7 = Wide Voltage AC 180~480V (Suitable for 380/400/440V industrial three-phase power grids) |
| P. | Configuration des contacts | P = Standard changeover contacts: 95(Caroline du Nord)/97(NON) (1 Normalement ouvert + 1 Normalement fermé) |
| Q | Additional Function | Q = Built-in Modbus-RTU RS485 communication; supports PLC/DCS remote monitoring, real-time current reading and fault code retrieval |
Spécifications techniques de base
3.1 Actuel & Time Adjustment
Plage actuelle: 5~60A (10:1 wide adjustment ratio)
D-Time (Start Stall Delay): 0.2~30s adjustable to avoid false tripping caused by high motor starting current
O-Time (Overload Trip Delay): 0.2~30s adjustable to match motor thermal characteristic curves
3.2 Fonctions de protection
- Surcharge & Protection contre les surintensités (O-Time delayed trip)
- Three-Phase Phase Loss Protection (Instant trip)
- Stall Protection (D-Time + O-Time dual delay)
- Three-Phase Current Unbalance Protection
3.3 Spécifications électriques
Operating Power Supply: AC 180~480V (W7 wide voltage)
Output Contacts: 5A/250VAC changeover contacts (95Caroline du Nord, 96COM, 97NON)
Communication: RS485 Modbus RTU (Exclusive to Q suffix models)
Dielectric Withstand Voltage: 2kV for 1 minute
Consommation d'énergie: ≤250mA
3.4 Environnement & Installation
Température de fonctionnement: -20℃~+60℃; Température de stockage: -30℃~+80℃
Humidité: 30%~85% HR, sans condensation
Montage: Standard 35mm DIN rail or screw fixing
Circuit principal: Two through-core CTs (Pass L1 and L2 through protector windows)
- Front Panel Knobs & Indicators
- LOAD(UN): Motor rated current adjustment knob (5~60A)
- D-TIME: Start delay (Prevent false tripping during startup)
- O-TIME: Overload trip delay
- Green PWR LED: Alimentation normale
- Red TRIP LED: Fault tripping (Number of flashes indicates fault type)
- RÉINITIALISER: Manual reset button; TEST: Unit self-test button
- Key Differences of PQ Suffix (vs Standard 60NW7)
- Built-in RS485 Modbus communication: Remotely read real-time operating current, fault logs and protector status; receive remote reset commands from upper computer
- PCB of Q model integrates communication terminals, supporting multi-protector bus networking
- Ideal for automated production lines, stations de pompage, central air conditioning and centralized monitoring control rooms
- Scénarios d'application typiques
380V three-phase fans, pompes à eau, compresseurs d'air, belt conveyors and mixing motors
Motors with rated current 5~60A, no external current transformer required
Control cabinets requiring PLC remote motor data collection and remote fault reset
- Directives de câblage
- Circuit principal: Run motor phase wires L1 and L2 through the two CT windows of the protector; L3 does not need to pass through
- Power Terminals A1/A2: Connect to AC380V control power supply
- Circuit de contrôle: 96COM as common terminal; wire 95NC normally closed contact in series with contactor coil (Type N opens on power loss); connect 97NO normally open contact to fault alarm indicator light
- RS485 Communication: A/B differential bus, daisy-chain wiring for multiple devices
- Matrice de dépannage
| Phénomène de défaut | Cause première | Solutions |
| TRIP LED stays lit and cannot be reset | Continuous overload / motor stall | Réduire la charge, increase set current, check mechanical jamming |
| TRIP LED flashes twice | Phase loss | Inspect main circuit fuses, contactor contacts and motor wiring |
| No response after power-on, LED PWR éteinte | Abnormal power supply to A1/A2 | Measure 380V power supply, replace the protector |
| No Modbus communication data | A/B wires reversed / duplicate device addresses | Swap RS485 A/B polarity, set unique address for each device |
- Alternative Models in the Same Series
- Non-communication version: EOCRSS-60NW7P (No RS485, moindre coût)
- 24–240V power supply version: EOCRSS-60NS7PQ (S7 = 24~240V AC/DC)
- Higher current rating: For motors over 60A, select EOCRSS-100 series with external CT