Yaskawa CIMR-P7U4160 Inverter

https://www.bestcontactor.com/product/yaskawa-cimr-ab4a0018fba-inverter/

(Varispeed P7 Inverter Specialized for Fans & Pompes)

  1. Répartition du code modèle

CIMR-P7U4160 (Full name on nameplate: CIMR-P7U41600 PDF)

CIMR: Universal prefix for Yaskawa onduleurs

P7: P7 series, energy-saving V/F inverter dedicated to fans and pumps

U: 400V three-phase high-voltage model (380~480V)

4160: Power rating code, corresponding to 250HP / 160kW class

  1. Core Electrical Rated Specifications

2.1 Main Circuit Power Ratings

ArticleValeur
Input Specification3-phase AC 380~480V, 50/60Hz
Courant d'entrée nominal334 UN
Rated Output Capacity230 kVA
Courant de sortie nominal304 UN (ND Normal Duty)
Matching Motor Power250HP / 160kW 3-phase induction motor
Max Output Voltage3-phase 0 ~ input voltage (maximum. 480V)
Fréquence de sortie maximale120 Hz
Fréquence porteuseAdjustable from 2kHz to 10kHz
Accel/Decel Time Range0.0~6000s, two independent accel/decel groups

2.2 Allowable Power Supply Fluctuation

Tension: +10% / -15%

Fréquence: ±5%

2.3 Performances de contrôle

Speed Adjustment Range: 40:1 (Contrôle V/F)

Speed Control Accuracy: ±2%~±3%

Modes de contrôle: Standard V/F, Energy-saving Square V/F (for fans & pompes), Multi-point V/F curve

  1. Mécanique & Spécifications environnementales
  2. Enclosure Rating: NEMA1 wall-mounted closed cabinet
  3. Overall Weight: Environ. 170kilos
  4. Température ambiante de fonctionnement: 0℃ ~ +40℃ (déclassement requis au-dessus de 40 ℃)
  5. Humidité: ≤80%RH, pas de condensation
  6. Altitude: No derating below 1000m; déclasser 1% per additional 100m above 1000m
  7. Méthode de refroidissement: Built-in high-power cooling fan (individually replaceable)
  8. Braking Mode: Built-in DC dynamic braking; external braking unit/resistor required for high-power regenerative energy
  9. Hardware Interface Configuration

4.1 Main Circuit Terminals (R/S/T Input; U/V/W Motor Terminals; +/Unité de freinage; PE Earth)

R., S, T: 3-phase 380~480V power input

U, V, W: Connection to 3-phase induction motor

+, -: External braking resistor / regenerative unit connection

PE: Terre de protection (common ground for cabinet and main circuit)

4.2 Standard Control Circuit Configuration

Entrées numériques: 8 chaînes, switchable between NPN and PNP

Digital Relay Outputs: 2 contacts normalement ouverts (fault signal, run status signal)

Entrées analogiques: 2 chaînes (0~10V / 4~20mA frequency reference)

Analog Outputs: 2 chaînes (monitor frequency, actuel, tension)

Communication: Standard Modbus-RTU; optional Profibus & DeviceNet communication cards

Digital Operator: 5-line 16-character LCD, supports parameter upload, download and copy

  1. Scénarios d'application typiques

The P7 series is designed specifically for square-torque loads. The high-power CIMR-P7U4160 model applies to:

  1. Large cooling water circulation pumps, municipal water supply booster pumps
  2. Factory centrifugal fans, ventilateurs de tirage induits par la chaudière, main dust removal fans
  3. Central air-conditioning chiller units, large cooling tower water pumps
  4. Exploitation minière & metallurgy dust exhaust fans, wastewater treatment aeration pumps

Avantages: Built-in energy-saving square torque curve, sleep function, multi-pump rotation switching, constant pressure PID control

  1. Discontinued Replacement Solution (P7 series fully discontinued)

Direct Drop-in Upgrade: Yaskawa P1000 Series

Equivalent replacement model: CIMR-PU4A0415ABA

  1. Fully matched power rating: 304A output, compatible with 160kW motors
  2. Full function coverage: Retains all fan & pump dedicated functions of P7 (contrôle multi-pompes, PID, mode veille)
  3. Highly compatible communication protocols, terminal logic and parameter sets, low renovation workload
  4. Merits: Higher energy efficiency, filtre CEM intégré, enhanced fault diagnosis, abundant spare parts

Alternative General Heavy-Duty Option: A1000 Series

(Vector type, selected for heavy-duty or closed-loop control demands)

  1. Codes d'erreur courants & Matrice de dépannage (Universal for P7 Series)
Code d'erreurDescription du défautCause premièreMesures correctives
OC/OC1/OC2/OC3Overcurrent during Accel / Decel / Constant SpeedMotor short circuit, cable earth fault, mechanical stall, overly short accel/decel timeTester l'isolation du moteur; extend accel/decel time; inspect mechanical jamming
Petite amieOutput Ground FaultDamaged insulation on U/V/W cables, motor winding breakdown to earthDisconnect motor cables section by section and test insulation separately
UVDC Bus UndervoltageMains phase loss, excessive voltage drop, poor contact of contactorMeasure three-phase voltage of R/S/T; fasten main circuit terminals
VODC Bus OvervoltageExcessively fast deceleration, no braking resistor, haute tension secteurLengthen deceleration time; install external braking unit
OL1Surcharge du moteurCharge excessive, long-time low-speed operation, incorrect motor current parameterVerify rated motor current parameter E2-01; réduire la charge
OL2Inverter OverloadSustained 150% rated current for 1 minuteRéduire la charge, upgrade inverter size, lower carrier frequency
SPIPerte de phase d'entréeBroken wire on one R/S/T phase, blown fuseInspect input circuit breaker, terminals and three-phase voltage balance
SPOPerte de phase de sortieDisconnection of one U/V/W phase, burnt single-phase motor contactTighten motor terminals; test cable continuity
OH1/OH2Surchauffer (Heat Sink)Dust-clogged air duct, damaged cooling fan, ambient temperature over 40℃Clean air filter; replace cooling fan; improve ventilation
LFOutput Three-Phase ImbalanceDamaged motor winding, loose wiring terminalsMeasure three-phase output current; fasten all terminals
  1. Strict Wiring & Installation Prohibitions
  2. Main power cables and control signal wires must be routed in separate cable trays with a minimum spacing of 30cm; long parallel laying is forbidden.
  3. Shielded motor cables are recommended; shield shall be grounded only at the control cabinet end.
  4. Main circuit copper busbars of high-power models shall be tinned and tightened with specified torque to avoid overheating and arcing.
  5. For multi-pump linked systems, AC contactors shall not be installed on the inverter output side for frequent switching.
  6. For sites with heavy dust and moisture, clean air duct filters regularly to prevent overheat alarms.
  7. If long motor cables (>50m) sont requis, an output du/dt filter must be installed to suppress peak voltage and protect motor insulation.
  8. Key Basic Commissioning Parameters (Standard for Fan & Pump Applications)
  9. E1-06 Base Frequency: Rated 50/60Hz as marked on motor nameplate
  10. E1-13 Square V/F (Fan Energy Saving): Régler sur 2 to enable square torque curve
  11. b5 PID Pressure Closed-Loop: Set target pressure and P/I/D gains
  12. b5-17 Sleep Function: Low-frequency energy-saving sleep, auto-stop during idle periods
  13. C1-01~C1-04 Accel & Decel Time: ≥15s recommended for pumps, ≥30s for fans to avoid overcurrent
  14. E2-01 Motor Rated Current: Enter value per motor nameplate, baseline for overload protection

Complete Model List of Yaskawa Varispeed P7 Series (CIMR-P7U□4□□□) 400Série V

Remarques

  1. Series Naming Rule: `CIMR-P7U4XXX0`. The full code printed on the nameplate ends with digit 0, which is omitted as the short model number for selection (par ex., CIMR-P7U4160).
  2. U = Dedicated 3-phase 380~480V model for fans and pumps; ND Normal Duty (square-torque loads for fans & pompes).
  3. Power correspondence unit: kW / HP / Courant de sortie nominal (UN).
  4. The entire series adopts V/F control, built-in square torque curve and PID multi-pump control. This series has been fully discontinued, with replacement models CIMR-PU4A□□□□ (P1000 series).
  5. Faible & Medium Power Range (7.5kW ~ 132kW)
Full Model No.Matching Motor PowerCourant de sortie nominal (UN)
CIMR-P7U400707.5kW / 10HP18
CIMR-P7U4011011kW / 15HP24
CIMR-P7U4015015kW / 20HP30
CIMR-P7U4018018.5kW / 25HP37
CIMR-P7U4022022kW / 30HP43
CIMR-P7U4030030kW / 40HP57
CIMR-P7U4037037kW / 50HP69
CIMR-P7U4045045kW / 60HP83
CIMR-P7U4055055kW / 75HP106
CIMR-P7U4075075kW / 100HP130
CIMR-P7U4090090kW / 125HP160
CIMR-P7U41100110kW / 150HP192
CIMR-P7U41320132kW / 175HP232
  1. High Power Range (160kW ~ 400kW, including CIMR-P7U4160 you inquired)
Full Model No.Matching Motor PowerCourant de sortie nominal (UN)
CIMR-P7U41600160kW / 250HP304
CIMR-P7U42000200kW / 300HP370
CIMR-P7U42200220kW / 330HP415
CIMR-P7U42500250kW / 375HP460
CIMR-P7U43150315kW / 450HP580
CIMR-P7U43750375kW / 500HP690
CIMR-P7U44000400kW / 540HP730

Supplementary Key Remarks

  1. 200V single/3-phase P7 models (P7E / P72 series) are excluded from the above table. This list only covers mainstream industrial 400V 3-phase fan & pump models P7U.
  2. Model Abbreviation Rule: The trailing digit 0 is often omitted in engineering drawings and procurement documents. Par exemple, CIMR-P7U41600 is abbreviated as CIMR-P7U4160.
  3. Cabinet Classification: Models ≤132kW adopt standard wall-mounted cabinets; models ≥160kW (4160 et au-dessus) are large floor-standing cabinets equipped with independent high-power cooling fans.
  4. Distinction of output versions at the same power rating:

Standard built-in braking transistor; high-power models 4160 and above require an external braking unit + braking resistor to implement dynamic braking during deceleration.

  1. Discontinued Model Replacement Mapping (P7U4XXXX → P1000 PU4AXXXX)

CIMR-P7U41600 (160kW) → CIMR-PU4A0415ABA

CIMR-P7U42000 (200kW) → CIMR-PU4A0475ABA

CIMR-P7U42500 (250kW) → CIMR-PU4A0605ABA