Convertitore di segnale Pepperl+Fuchs KFU8-FSSP-1.D-Y - Contattore,interruttore automatico,sensore,Codificatore,PLC,Convertitore

Wechat: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Di Contatto |

Convertitore di segnale Pepperl+Fuchs KFU8-FSSP-1.D-Y - Contattore,interruttore automatico,sensore,Codificatore,PLC,Convertitore

PLC/

Convertitore di segnale Pepperl+Fuchs KFU8-FSSP-1.D-Y

Nome e cognome: Frequency/Voltage/Current (10 kHz Version) KFU8 series DIN rail signal conditioning module, designed for frequency/speed acquisition from encoders and pulse sensors, converting pulse signals into standard analog signals, with an optional frequency-divided pulse output. Distinzione: KFU8-FSSP-1.D-Y = 10 kHz maximum input frequency KFU8-FSSP-1.D-Y322444 = 40 kHz high-speed version Many suppliers mix these two models; ...

  • Dettagli del prodotto

Nome e cognome: Frequency/Voltage/Current (10 kHz Version)

KFU8 series DIN rail signal conditioning module, designed for frequency/speed acquisition from encoders and pulse sensoreS, converting pulse signals into standard analog signals, with an optional frequency-divided pulse output.

Distinzione:

KFU8-FSSP-1.D-Y = 10 kHz maximum input frequency

KFU8-FSSP-1.D-Y322444 = 40 kHz high-speed version

Many suppliers mix these two models; confirm the frequency limit during selection.

✅ Funzioni principali

  1. Two measurement modes: Frequenza (Hz) / Velocità di rotazione (giri/min)

Gamma di frequenza: 0.001 Hz~ 9999 Hz

Gamma di velocità: 0.02 rpm ~ 9999 giri/min

  1. Configurable analog output (selectable via menu):

0…10 V / 2…10 V

0…20 mA / 4…20 mA

  1. Frequency-divided pulse output: division ratio 1~9999, isolated pulse signal for PLC or secondary instruments
  2. Integrato 24 V DC auxiliary sensor power supply; compatible with 2/3/4-wire proximity switches and NPN/PNP incremental encoders
  3. 4-digit red LED display; shows input Hz/rpm or output V/mA. 4-button local programming with one-touch Teach-In calibration
  4. Period measurement method, optimized for low-speed pulse signals

📌 Electrical Specifications

Alimentazione elettrica: 24 A DC

Consumo energetico: <5 W

Max input frequency: 10 kHz (questo modello); minimum pulse width ≥40 μs

Precisione: ≤0.2% FS

Processing response: 5 ms internal update; display refresh adjustable from 0.01~2.5 s (no impact on signal conversion)

Isolamento: Galvanic isolation between input and analog output

Classe di protezione: IP20 (solo montaggio in armadio)

Montaggio: Snap-on 35 Guida DIN da mm

Terminali: Removable coded terminals, wire cross-section 0.2~2.5 mm²

Temperatura operativa: -25 ℃ ~ +40 ℃ (senza condensa)

Temperatura di conservazione: -40 ℃~+85 ℃

📋 Terminal Assignment

terminaleSegnale
1Sensor GND
2Uscita a impulsi
5Uscita analogica +
6Uscita analogica – (Voltaggio)
4Uscita analogica – (Attuale)
7Sensore 24 V+
11Power Supply L+ 24 A DC
12Power Supply L- 0 V
14NPN/PNP Input – (Cathode)
15NPN/PNP Input + (Anodo)
13Sensor GND
Remaining terminalsNC (Not Connected)

⚙️ Factory Default Parameters

Modalità: giri/min (Velocità di rotazione)

Pulse per revolution (PPR): 1

Full Scale Range: 9999

Uscita analogica: 0…10 V

Display Refresh Time: 0.33 S

Division Ratio: 1

Salva parametri: Long-press Enter + + to store into EEPROM (power-down retention)

🛠 Typical Applications

Speed measurement for conveyors, tifosi, pumps and roller tables

Converting pulse signals from flowmeters into 4–20 mA analog signals for DCS/PLC

Encoder signal division, local speed display + analog transmission

Stable measurement of low-frequency pulse signals (period measurement outperforms frequency counting at low speeds)

⚠️ Guida alla risoluzione dei problemi

ColpaPossibili cause & Rimedi
Nessun potere, nessuna visualizzazione1. Controllo 24 V DC at terminals 11/12; 2. Terminali allentati; 3. Reverse polarity protection activated
Signal present but reading always zero1. NPN/PNP wiring reversed; 2. Pulse width ≥40 μs; 3. NO 24 V on sensor supply terminal 7; 4. Wrong measurement mode (rpm/Hz)
Letture fluttuanti1. Increase display refresh time; 2. Use shielded cable with single-end grounding; 3. Check voltage drop on encoder supply; 4. Ensure high level ≥16 V DC, low level ≤6 V DC
Analog output stuck1. Match current/voltage output type with AI card; 2. Max load resistance ≤600 Ω for current output; 3. Re-run Teach-In calibration
Display overflow1. Actual speed exceeds set RANGE; 2. Incorrect PPR setting (value too large)
No pulse output on terminal 21. Division ratio ≠ 1; 2. Open-collector output requires external pull-up resistor on PLC side; 3. Input frequency below lower limit
Self-test error Err on power-upEEPROM checksum failure; power cycle first; repeated error means hardware failure, replace the module
Poor low-speed accuracyThis module uses period measurement; ensure pulse width ≥40 μs; avoid ultra-narrow pulses

📎 Cross-model & Opzioni di sostituzione

Stessa serie: KFU8-FSSP-1.D-Y322444 (40 kHz, for high-speed encoders)

Alternative domestiche: CZJ, UBE frequency/speed isolators (must support period measurement + frequency-divided pulse output)

  1. Istruzioni di cablaggio (KFU8-FSSP-1.D-Y)

Full Terminal List

terminaleDefinizione del segnaleNota
1Sensor GNDSpare sensor ground
2Frequency-divided Pulse OutputIsolated pulse for PLC high-speed counter
4Current Output I-Negative terminal for 4…20 mA
5Analog U+/I+Common positive for voltage & current output
6Voltage Output U-Negative terminal for 0…10 V
7Sensore 24 V+Encoder/proximity sensor supply, massimo. 30 mA
8NAMUR Input –NAMUR sensor channel
9NAMUR Input +NAMUR sensor channel
11Module Power L+ 24 A DCMain power positive
12Module Power L- 0 VMain power negative
13Sensor GNDSensor power ground
14NPN/PNP Input – (Cathode)Pulse negative
15NPN/PNP Input + (Anodo)Pulse positive
AltriNCDo not connect

Standard Wiring Schemes

  1. 3-wire PNP Encoder (Più comune)

Brown wire → Terminal 7 (24 V+)

Blue wire → Terminal 13 (GND)

Black signal wire → Terminal 15; terminale 14 shorted to 13 (GND)

  1. 3-wire NPN Encoder

Marrone → 7; Blu → 13

Black signal → 14; terminale 15 shorted to 7 (24 V+)

  1. 4–20 mA analog to DCS AI card

terminale 5 → AI+; terminale 4 → AI-

  1. 0…10 V voltage output

terminale 5 → AI+; terminale 6 → AI-

  1. Frequency-divided pulse output

terminale 2 to PLC high-speed counter; fit external pull-up resistor on PLC side

Avviso importante: Max sensor supply current = 30 mA; do not drive multiple encoders. Use shielded cable for long-distance pulse wiring, ground the shield only at one end.

  1. Button Operation & Parameter Setup

4 front-panel keys: Modalità (Menu), ◀, +, Entra

  1. Accendere; wait for self-test then enter measurement display (Hz/rpm)
  2. Short press Mode to switch menu items; ◀ = shift digit; + = change value
  3. Salva parametri: Long press Enter + + together to write into EEPROM (mantenuto dopo la perdita di potenza)
  4. Exit menu: Long press Mode to return to measurement screen

Menu Items (English Original)

  1. MODALITÀ: Measurement Mode

rpm = Rotational Speed (Encoder application recommended)

Hz = Frequency (Pulse flowmeter)

  1. PULSE: Pulses Per Revolution (PPR)

Esempio: 1000-line encoder → set PULSE=1000

  1. RANGE: Full Scale Value

Esempio: 0~1500 rpm → set RANGE=1500

  1. FUORI: Tipo di uscita

0-10V / 2-10V / 0-20mA / 4-20mA

  1. DIV: Division Ratio (1~9999)

Output pulse = Input pulse ÷ DIV; set DIV=1 if no division required

  1. DISP: Display Refresh Time (0.01~2.5 s)

Increase to 0.5~1 s to stabilize low-speed readings; impostato 0.1 s for high speed

  1. TEACH: One-touch Calibration (Teach-In)

Run equipment to full-scale speed, enter TEACH and press Enter; auto-set upper range (zero point fixed at 0)

Impostazioni di fabbrica: MODE=rpm, PULSE=1, RANGE=9999, OUT=0…10V, DIV=1, DISP=0.33 s

Factory Reset Procedure

Accendere, hold Mode + Enter for 5 seconds until FACT appears; confirm to restore all factory settings. All custom parameters will be erased.

  1. Tabella per la risoluzione dei problemi
SintomoPassaggi per la risoluzione dei problemi
Nessuna visualizzazione dopo l'accensione1. Misura 24 V DC between terminals 11 & 12; 2. Check loose terminals; 3. Reverse polarity protection triggered
Nessuna lettura, display stays zero1. Verify NPN/PNP wiring polarity; 2. Ensure pulse width ≥40 μs; 3. Controllo 24 V output on terminal 7; 4. Confirm correct MODE (rpm/Hz)
Instabile, flickering readings1. Increase DISP refresh time; 2. Shield cable single-end grounded; 3. Check voltage drop on encoder supply; 4. High level ≥16 V DC, low level ≤6 V DC
Analog output locked and unchanged1. Match OUT type with AI card (current/voltage cannot be mixed); 2. Current output load resistance ≤600 Ω; 3. Re-run TEACH calibration
Display over-range overflow1. Actual speed exceeds RANGE setting; 2. PPR value set too high
No pulse output on terminal 21. DIV ratio not equal to 1; 2. Open-collector output requires external power/pull-up resistor on PLC; 3. Input frequency below lower limit
Err code on power-up self-testEEPROM data error; restart first; repeated error = hardware damage, sostituire il modulo
Inaccurate low-speed measurementThis module uses period measurement (good for low speed); ensure pulse width ≥40 μs, avoid ultra-narrow pulses
  1. Parameter Table (Chinese ↔ English, Exportable)
Chinese ParameterEnglish TagAllineareOsservazioni
测量模式MODALITÀgiri/min / HzVelocità / Frequenza
每转脉冲数PULSE1~9999Encoder PPR value
满量程RANGE1~9999Corresponds to full-scale analog output
输出类型FUORI0-10V,2-10V,0-20mA,4-20mAAnalog signal selection
分频系数DIV1~9999Pulse output division
显示刷新时间DISP0.01~2.5 sOnly affects display, no impact on conversion speed
一键标定TEACH—Dynamic full-scale calibration
精度Precisione≤0.2%FSFull-scale accuracy
最大输入频率Fmax10 kHzFor model Y only (not Y322444)
  1. Procedura di messa in servizio (On-site Sequence)
  2. Wire with power disconnected; double-check power, encoder and analog terminals
  3. Accendere; verificare 24 V DC on sensor supply terminal 7
  4. Set MODE, PPR, RANGE and OUT type
  5. Rotate the encoder and confirm reading follows actual speed
  6. Measure analog output with multimeter, verify zero and full-scale values
  7. If pulse division is needed: connect PLC high-speed counter and test terminal 2 pulse signal
  8. Save parameters and record settings; commissioning complete

Pepperl+Fuchs KFU8 Series DIN Rail Signal Converter Order List

Descrizione: KFU8 = K-System local-display programmable signal conditioners; divided into standard type and Ex intrinsically safe barrier type.

Suffix rules:

1.D = 1-channel; 2.D = 2-channel

Y = 10 kHz input; Y322444 = 40 kHz (only for FSSP models)

Ex = Intrinsically safe for hazardous area Zone 0/1/2

Order Part NumberNome del prodottoBrief FunctionA prova di esplosione
KFU8-FSSP-1.D-YFrequency/Speed Converter (10 kHz)Encoder pulse → analog 0-10V/4-20mA, with frequency-divided pulse output & visualizzazione localeNO
KFU8-FSSP-1.D-Y322444Frequency/Speed Converter (40 kHz)Same as FSSP, massimo 40 kHz for high-speed encodersNO
KFU8-DW-1.DSpeed MonitorOverspeed/underspeed monitoring with relay alarm output; massimo 40 kHz, period measurementNO
KFU8-UFC-1.DFrequency Converter with Limit Alarms1 mHz~10 kHz; NAMUR/dry contact input; 4-20mA + relè + uscita a transistor; SIL2NO
KFU8-UFC-1.D.FAConvertitore di frequenza (Vecchia versione)Modello legacy; phase-out, replace with UFC-1.DNO
KFU8-UFC-Ex1.DIntrinsically Safe Frequency BarrierEx ia, Zona 0/1/2, Ingresso NAMUR, SIL2SÌ (Ex ia)
KFU8-UFT-2.DDual-channel Frequency/Slip/Speed Direction MonitorDual NAMUR/dry contact input; detect rotation direction, slip and synchronous deviation; analogico + uscita relèNO
KFU8-UFT-Ex2.DExplosion-proof Dual-channel Direction/Slip BarrierHazardous area dual-channel rotation monitoringSÌ (Ex ia)
KFU8-USC-1.DUniversal Voltage/Current Signal ConverterIsolamento & scaling for 0/4-20mA & 0-10V analog signals; with limit relay alarmNO
KFU8-GUT-Ex1.DIntrinsically Safe Universal Temperature TransmitterRTD/Thermocouple input, dual relay alarm, SIL2SÌ (Ex ia)

Regola di codifica del modello

KFU8 [Codice funzione] [Canale].[Versione] [-Suffisso]

FSSP: Frequency Speed → Speed transmission with divided pulse output

DW: Speed Watch → Speed monitoring & allarme

UFC: Universal Frequency Converter → Frequency conversion + limit alarm

UFT: Universal Frequency Twin → Dual-channel frequency, direzione & slip monitoring

USC: Universal Signal Converter → Standard analog signal isolation

GUT: Universal Temperature → Temperature signal transmission

Ex: Intrinsically safe explosion-proof barrier

1.D = Single channel; 2.D = Dual channel

Y = 10 kHz; Y322444 = 40 kHz (FSSP exclusive suffix)

KFU8 Series Common Accessories

K-CJC-EX: Cold-junction compensation terminal (for GUT temperature modules)

KF-ST-5BU / KF-ST-5GN: Removable coded terminals (blue/grey)

Power Rail: K-series power bus for multi-module parallel power supply

Guida alla selezione rapida

  1. Speed transmission + divided pulse output → FSSP (Y / Y322444)
  2. Overspeed/underspeed alarm (no divided pulse) → DW-1.D
  3. NAMUR proximity switch frequency input + alarm → UFC / UFC-Ex
  4. Dual encoders, slip & rotation direction detection → UFT-2.D / UFT-Ex2.D
  5. Analog 4-20mA/0-10V isolation, ridimensionamento & alarm → USC-1.D
  6. RTD/TC temperature measurement in hazardous area → GUT-Ex1.D

Note supplementari

All KFU8 modules: 40 larghezza mm, 35 Montaggio su guida DIN da mm, 4-visualizzazione delle cifre + 4-button programming; different from non-display KFD0 / KFA5 barriers.

Alimentazione elettrica: Most models support 20~90 V DC / 48~253 V AC; FSSP model only supports 24 A DC.

Avviso di fine vita: UFC-1.D.FA is obsolete; select UFC-1.D for new projects.