Schneider EOCRSS-60NW7PQ

Informazioni di base sul prodotto

Marca: SAMWHA EOCR (Schneider Korea)

Tipo di prodotto: EOCR-SS Series Knob-type Electronic Motor Protector (Replaces traditional thermal overload relays)

  1. Model Code Breakdown of EOCRSS-60NW7PQ
SegmentoCodiceDefinizione
EOCRSSSerieSS Economy Integrated Through-Core Motor Protector
60Valutazione attualeBuilt-in CT, adjustable rated current: 5.0~60A, compatible with 1.5~30kW three-phase motors
NModalità di protezioneType N Fail-Safe: Contacts open and contactor trips upon protector power loss or fault; Type R does not trip when power fails
W7Alimentazione elettricaW7 = Wide Voltage AC 180~480V (Suitable for 380/400/440V industrial three-phase power grids)
PConfigurazione dei contattiP = Standard changeover contacts: 95(NC)/97(NO) (1 Normalmente aperto + 1 Normalmente chiuso)
QAdditional FunctionQ = Built-in Modbus-RTU RS485 communication; supports PLC/DCS remote monitoring, real-time current reading and fault code retrieval
  1. EOCR-SS Series Knob-type Electronic Motor ProtectorSpecifiche tecniche principali

3.1 Attuale & Time Adjustment

Intervallo corrente: 5~60A (10:1 wide adjustment ratio)

D-Time (Start Stall Delay): 0.2~30s adjustable to avoid false tripping caused by high motor starting current

O-Time (Overload Trip Delay): 0.2~30s adjustable to match motor thermal characteristic curves

3.2 Funzioni di protezione

  1. Sovraccarico & Protezione da sovracorrente (O-Time delayed trip)
  2. Three-Phase Phase Loss Protection (Instant trip)
  3. Stall Protection (D-Time + O-Time dual delay)
  4. Three-Phase Current Unbalance Protection

3.3 Specifiche elettriche

Operating Power Supply: AC 180~480V (W7 wide voltage)

Output Contacts: 5A/250VAC changeover contacts (95NC, 96COM, 97NO)

Comunicazione: RS485 Modbus RTU (Exclusive to Q suffix models)

Dielectric Withstand Voltage: 2kV for 1 minuto

Consumo energetico: ≤250mA

3.4 Ambiente & Installazione

Temperatura operativa: -20℃~+60℃; Temperatura di conservazione: -30℃~+80℃

Umidità: 30%~85%RH, senza condensa

Montaggio: Standard 35mm DIN rail or screw fixing

Circuito principale: Two through-core CTs (Pass L1 and L2 through protector windows)

  1. Front Panel Knobs & Indicators
  2. LOAD(UN): Motor rated current adjustment knob (5~60A)
  3. D-TIME: Start delay (Prevent false tripping during startup)
  4. O-TIME: Overload trip delay
  5. Green PWR LED: Power supply normal
  6. Red TRIP LED: Fault tripping (Number of flashes indicates fault type)
  7. RESET: Manual reset button; TEST: Unit self-test button
  8. Key Differences of PQ Suffix (vs Standard 60NW7)
  9. Built-in RS485 Modbus communication: Remotely read real-time operating current, fault logs and protector status; receive remote reset commands from upper computer
  10. PCB of Q model integrates communication terminals, supporting multi-protector bus networking
  11. Ideal for automated production lines, pump stations, central air conditioning and centralized monitoring control rooms
  12. Scenari applicativi tipici

380V three-phase fans, pompe dell'acqua, compressori d'aria, belt conveyors and mixing motors

Motors with rated current 5~60A, no external current transformer required

Control cabinets requiring PLC remote motor data collection and remote fault reset

  1. Linee guida per il cablaggio
  2. Circuito principale: Run motor phase wires L1 and L2 through the two CT windows of the protector; L3 does not need to pass through
  3. Power Terminals A1/A2: Connect to AC380V control power supply
  4. Circuito di controllo: 96COM as common terminal; wire 95NC normally closed contact in series with contactor coil (Type N opens on power loss); connect 97NO normally open contact to fault alarm indicator light
  5. RS485 Communication: A/B differential bus, daisy-chain wiring for multiple devices
  6. Troubleshooting Matrix
Fenomeno di guastoCausa ultimaSoluzioni
TRIP LED stays lit and cannot be resetSovraccarico continuo / motor stallRidurre il carico, increase set current, check mechanical jamming
TRIP LED flashes twicePhase lossInspect main circuit fuses, contactor contacts and motor wiring
No response after power-on, LED PWR spentoAbnormal power supply to A1/A2Measure 380V power supply, replace the protector
No Modbus communication dataA/B wires reversed / duplicate device addressesSwap RS485 A/B polarity, set unique address for each device
  1. Modelli alternativi della stessa serie
  2. Non-communication version: EOCRSS-60NW7P (No RS485, costo inferiore)
  3. 24–240V power supply version: EOCRSS-60NS7PQ (S7 = 24~240V AC/DC)
  4. Higher current rating: For motors over 60A, select EOCRSS-100 series with external CT