OMRON NX102-1020 모듈러 CPU 유닛 - 접촉기,회로 차단기,감지기,인코더,PLC,변환기

위챗: +86-13184948252 왓츠앱: 0086-13811255435 이메일: kent@bestcontactor.com

에 대한 연락하다 |

 OMRON NX102-1020 모듈러 CPU 유닛 - 접촉기,회로 차단기,감지기,인코더,PLC,변환기

PLC/

OMRON NX102-1020 모듈러 CPU 유닛

OMRON NX1 Series Machine Automation Controller (MAC, 모듈러 CPU 유닛) Sysmac platform, integrating logic, motion and IT communication, a multi-axis motion control model for medium and small-sized equipment. ✅ Model Code Explanation NX102: CPU of NX1 series; 1020: 2-axis synchronous interpolation + 4-axis PTP point-to-point, 총 6 physical axes (최대. 15 axes including virtual axes), ...

  • 제품 세부정보

오므론 NX1 Series Machine Automation Controller (MAC, 모듈러 CPU 유닛)

Sysmac platform, integrating logic, motion and IT communication, a multi-axis motion control model for medium and small-sized equipment.

✅ 모델 코드 설명

NX102: CPU of NX1 series; 1020: 2-axis synchronous interpolation + 4-axis PTP point-to-point, 총 6 physical axes (최대. 15 axes including virtual axes), supports direct database connection.

😀 핵심사양

목사양
프로그램 메모리5 MB
Variable Memory33.5 MB (Retain area:1.5 MB, Non-retain area:32 MB)
Minimum Primary Task Cycle1 ms
Synchronous Axes (Interpolation Axes)2 축
PTP Point-to-Point Axes4 축
맥스. Axes including Virtual Axes15 축
EtherCAT마스터 스테이션, 최대 64 EtherCAT nodes; supports EtherCAT ring redundancy
Local Expansion최대 32 NX units on NX local bus (입출력, 안전, IO-링크, 등.)
Local I/O Points1024 전철기; 확장 가능 8960 points with NX coupler
포트PORT1/PORT2: 이더넷/IP + TCP/IP; PORT3: EtherCAT
Built-in ProtocolsOPC UA 서버, Direct SQL Database Connection, MQTT
프로그래밍 소프트웨어시스맥 스튜디오; 언어: 성 (구조화된 텍스트), LD (래더 다이어그램), 페이스북 (Function Block)
설치DIN 레일 장착; 치수:100(시간)×66(여)×100(디) mm; 무게:470 g
전원공급장치NX power supply unit sold separately (NX-PF series); No built-in battery; Variables backed up by capacitor

🧩 Key Features

  1. 모션 제어

EtherCAT 버스 서보, supports 2-axis synchronization (linear/circular interpolation) + 4-axis independent point-to-point. Suitable for transferring, picking, simple flying shear and synchronous conveying.

  1. IT Integration (Sysmac Unique Feature)

Direct SQL Connection: Read/write MySQL, SQL Server, Oracle and other databases directly without upper computer relay

OPC UA: Native OPC UA server for connecting to MES and SCADA

MQTT: Connect to cloud platform for equipment data upload

  1. 시스템 확장

NX local bus can mount digital/analog modules, safety controller NX-SL, IO-Link master station; EtherCAT can connect servos, remote I/O and sensors.

  1. Battery-free Design

Capacitor backup for retaining variables. No regular battery replacement required to reduce maintenance cost.

🛠️ 일반적인 적용 시나리오

중소형 자동화 장비: 포장 기계, 라벨링 기계, 전송 조작기, 리튬 배터리 프런트엔드 장비, 검사 기계 및 소규모 생산 라인.

📊 NX102 시리즈 비교 (선택 참고용)

NX102-1020: 2 동기 축 + 4 PTP 축, 총 6 physical axes (이 모델)

NX102-1100: 4 동기 축 + 4 PTP 축, 총 8 physical axes

NX102-1200: 8 동기 축 + 4 PTP 축, 총 12 physical axes

⚠️ 메모

  1. CPU용 전원 공급 장치가 내장되어 있지 않음, NX-PF 전원 공급 모듈을 별도로 장착해야 합니다.;
  2. 프로그램 백업 및 로그 기록을 위한 SD 카드 슬롯;
  3. 직접 데이터베이스 연결 및 MQTT에는 해당 펌웨어 버전의 Sysmac Studio가 필요합니다.;
  4. 중고검사 포인트: 펌웨어 버전 확인, EtherCAT 포트, 전원을 켤 때 이더넷 포트 및 SD 카드 슬롯; 백업 프로그램 및 테스트 축 제어.

📎 대체 솔루션 참조

동일 브랜드 업그레이드: NX102-1100 (더 많은 동기 축)

동일한 플랫폼의 낮은 버전: NX1P 시리즈 (일체형, NX 로컬 버스 확장 기능 없음)

OMRON NX102-1020 문제 해결 체크리스트

문제 해결 원리: LED 표시등을 먼저 확인 → Sysmac Studio를 통해 온라인으로 이벤트 로그 읽기 → 치명적인 오류 식별 (기계 정지) / 사소한 결함 (계속 달리기) / 정보 이벤트. 오류 코드를 직접 삭제하는 대신 재설정하기 전에 근본 원인을 제거하세요.. 참조 매뉴얼: W503 (NJ/NX 오류 매뉴얼), NX102 하드웨어 매뉴얼

  1. 전원 켜기 실패, CPU가 실행되지 않음 (전원 끄기 / 단색 빨간색)
현상가능한 원인문제 해결 단계
전원 LED 꺼짐손상된 NX-PF 전원 모듈, 전원 공급 장치 없음, 느슨한 배선, 과도한 DC24V 전압 강하1. 전원 모듈의 AC/DC 입력 측정; 2. DIN 레일의 백플레인 전원 터미널을 확인하세요.; 3. NX-PF 전원 장치를 교체하여 테스트; 4. 접지 및 단락을 확인하십시오.
POWER 단색 빨간색, RUN에 들어갈 수 없습니다심각한 CPU 하드웨어 결함, 내부 버스 오류, 비휘발성 메모리 손상, 온도 이상1. 전원을 끄고 냉각하세요. 30 분 후 전원을 켜세요; 2. 이벤트 로그 확인: 00110000(과열)/000D0000(내부 버스)/000E0000(플래시 수명 종료); 3. 모든 NX 확장 모듈 제거, CPU만으로 최소한의 시스템 실행 + 전원 공급 장치; 4. 최소 시스템에서 장애가 지속되는 경우 → CPU 하드웨어 장애, CPU 교체
전원을 켠 후 재부팅이 반복됨전력 등급이 충분하지 않음, 백플레인 단락, EMC 잡음 간섭1. NX 랙의 총 전력 소비량 계산; 2. 백플레인의 금속 파편을 확인하세요.; 3. 전원선, 제어선 분리 및 접지 개선
  1. Sysmac Studio를 통해 연결할 수 없습니다 (PORT1/PORT2 이더넷 포트)
현상가능한 원인문제 해결 단계
핑 실패, NET ERR 빨간색IP 불일치, 윈도우 방화벽, 손상된 케이블/커넥터, 이더넷 포트의 하드웨어 손상1. PC IP를 동일한 서브넷으로 설정, Windows 방화벽을 꺼주세요; 2. 차폐 케이블 교체, PORT1/PORT2의 L/A 링크 램프를 확인하세요.; 3. BOOTP를 통해 CPU IP 재설정; 4. PORT2로 테스트; 단일 포트 오류는 대부분 하드웨어 손상을 나타냅니다.
Ping은 정상이지만 온라인 다운로드에 실패했습니다.일치하지 않는 엔지니어링 버전, CPU 쓰기 방지, SD 카드 이상1. Sysmac Studio 펌웨어가 CPU 펌웨어와 호환되는지 확인하세요.; 2. CPU 쓰기 방지가 활성화되어 있는지 확인하십시오.; 3. SD 카드를 제거하고 다시 시도하세요.; 4. 하드웨어 구성이 실제 랙과 일치하는지 확인
프로젝트 다운로드 오류, 구성 확인 실패프로젝트 내 NX 로컬 버스 모듈의 모델/수량이 일치하지 않습니다.1. 랙에 있는 NX 모듈의 모델 및 위치 확인; 2. 중복 모듈 제거 및 최소 랙 테스트; 3. 하드웨어 구성을 다시 업로드하세요.
  1. EtherCAT 버스 결함 (PORT3, 모션 제어에서 가장 일반적)

NX102-1020 내장 EtherCAT 마스터; 축 제어 및 원격 I/O는 이 버스에서 실행됩니다.. EtherCAT 결함의 경우, Sysmac EtherCAT 진단 및 프레임 오류 카운터를 사용하여 결함이 있는 세그먼트를 찾습니다.

  1. NX 로컬 백플레인 버스 오류 (NX 랙 확장 I/O, 안전 모듈 NX-SL)
현상가능한 원인문제 해결 단계
NX 확장 유닛의 ERR 램프, 이벤트 로그 000D0000백플레인 접촉 불량, 손상된 모듈, mismatched module model in configuration1. 전원 끄기, re-plug NX modules and ensure buckles locked; 2. Remove modules one by one to locate faulty unit; 3. Verify module model and position in project; 4. Replace damaged NX unit
  1. Motion Control Fault (NX102-1020: 2 Interpolation Axes +4 PTP Axes)
현상가능한 원인문제 해결 단계
Axis homing failedWiring of home sensor, limit signal, home parameter, servo not ready1. Monitor status of home, positive/negative limit I/O; 2. Check servo ready signal; 3. Verify homing mode and offset parameters; 4. Confirm no hardware limit triggered
Motion error alarm during point-to-point / 보간Soft limit, over speed/acceleration, axis lock, servo fault, insufficient task cycle1. Check motion event code; 2. Verify soft limit parameters; 3. Reduce acceleration; 4. Confirm no stop/lock command on axis
Large multi-axis synchronization deviation, flying shear synchronization failureEtherCAT cycle fluctuation, abnormal encoder feedback, incorrect sync parameter1. Monitor position feedback of each axis; 2. Check encoder wiring; 3. Adjust synchronization control parameters; 4. Eliminate bus interference
  1. Built-in Communication Fault (OPC UA / MQTT / Direct SQL Database Connection)
현상가능한 원인문제 해결 단계
OPC UA client connection failed포트, security policy, certificate, IP routing, 방화벽1. Confirm CPU OPC UA service enabled; 2. Verify certificate trust; 3. Check port open status; 4. Confirm network route reachable
MQTT cloud upload failedWrong Broker address/port, network unreachable, certificate, heartbeat parameter1. Ping MQTT server; 2. Verify account, password and TLS setting; 3. Check MQTT event codes in event log
SQL database read/write failureDatabase IP/port, account permission, 운전사, 패킷 손실1. Confirm database allows external access; 2. Verify table name, field and SQL statement; 3. Check CPU firmware version (old firmware does not support partial databases)
  1. SD Card Related Fault
현상가능한 원인문제 해결 단계
SD card ERR alarm, backup/log recording failed손상된 SD 카드, incorrect format, 용량 한도 초과, 접촉 불량1. SD 카드를 꺼냈다가 다시 삽입하세요.; 2. FAT32 형식과 OMRON 권장 산업용 SD 카드를 사용하세요.; 3. 손상된 카드 교체; 4. 로그 손실을 쉽게 일으키는 소비자 SD 카드를 피하세요
  1. 환경 & 노화된 하드웨어 결함
  2. 과열 경보 (00110000): 열악한 캐비닛 열 방출, 먼지가 막힌 팬, 주변 온도가 범위를 벗어났습니다.. 깨끗한 먼지, 환기를 개선하다; 60℃ 이상에서 보호 차단이 발생함.
  3. 비휘발성 메모리 수명 경고 (000E0000): 플래시 쓰기/삭제 주기가 소진되었습니다.. CPU 교체 준비; 변수/로그를 자주 작성하면 노화가 가속화됩니다..
  4. 소음 간섭으로 인한 우발적인 종료: 전원 케이블은 제어 케이블과 병렬로 연결됩니다., 접지 불량, 차폐 없음. 별도의 배선, 단일 지점 접지 및 서지 흡수 장치 추가.
  5. 빠른 문제 해결 워크플로 (현장 작업 순서)
  6. 전원 끄기 → 육안 검사: 배선, 모듈 버클, 손상된 케이블, 먼지, 단락 흔적
  7. 전원을 켜고 모든 LED 상태를 기록합니다. (전원/실행/오류, EtherCAT, 이더넷 L/A)
  8. Sysmac Studio로 온라인에 접속하세요, 이벤트 로그를 읽고 16진수 이벤트 코드를 기록합니다.
  9. 최소 시스템 테스트: NX-PF 전력 + NX102-1020 전용, CPU 또는 외부 주변 장치에 결함이 있는지 판단하기 위해 모든 NX 확장 및 EtherCAT 슬레이브를 제거합니다.
  10. 분할된 격리: 세그먼트별로 EtherCAT 세그먼트 연결 해제 / 결함이 있는 장치/케이블을 찾기 위해 NX 모듈을 하나씩 제거합니다.
  11. 근본 원인 수정 → 오류 삭제 → CPU 재설정 및 다시 테스트
  12. 중고 / 중고 NX102-1020 특별점검 체크리스트
  13. 모습: 화상 자국, 산화된 백플레인 금속 접점, 하우징의 찌그러짐 또는 변형
  14. 최소 시스템 전원 켜기, 치명적인 하드웨어 결함 없이 정상적인 POWER를 확인합니다.
  15. 펌웨어 버전 및 이벤트 로그를 읽으려면 온라인으로 이동하세요., 역사적 결함을 확인하다 (플래시 라이프, 과열 기록)
  16. SD 카드 슬롯 읽기-쓰기 테스트
  17. PORT1/PORT2 이더넷 및 PORT3 EtherCAT 포트에 대한 링크 테스트
  18. 구성 다운로드 오류가 없는지 확인하려면 빈 프로젝트를 다운로드하세요.
  19. EtherCAT 서보를 테스트 축 활성화 및 기본 지점 간 모션에 연결하십시오.

OMRON NX102 전체 시리즈 모델 목록 (NX1 모듈형 기계 자동화 CPU)

모델 코딩 규칙:

NX102-ABCD

AB: 축 사양; CD: 기능 버전

접미사 -00 = 표준 버전 (직접적인 데이터베이스 연결 없음)

접미사 -20 = DB 데이터베이스 버전 (직접 SQL 연결 지원 & 시계열 데이터 수집, NX102-1020과 동일)

모든 모델은 동일한 기본 하드웨어를 공유합니다.: 5MB 프로그램 메모리 / 33.5MB 가변 메모리 (1.5MB 보유 영역), EtherCAT 마스터, 듀얼 EtherNet/IP 포트, NX 로컬 백플레인 버스, 최소 작업 주기 1ms

  1. 표준 버전 (-00, 직접 SQL 데이터베이스 연결 없음)
모델동기 보간축PTP Axes맥스. 물리적 축설명
NX102-12008 축4 축12 축고급 모델, 다축 동기화, 플라잉 전단, 전자 캠, 다축 장비용
NX102-11004 축4 축8 축중간 동기 축, 이송 및 동기식 이송용
NX102-10002 축4 축6 축기본 보간 모델, NX102-1020과 동일한 축 기능, 데이터베이스 기능 없음
NX102-90000 중심선4 축4 축보간 없음, 오직 4 독립적인 지점 간 축; 일반 시퀀스 제어용 + 간단한 포인트 모션, 동기 보간 없음
  1. 데이터베이스 연결 버전 (-20, 직접 SQL 지원 & 시계열 데이터, SD 카드 포함)
모델동기 보간축PTP Axes맥스. 물리적 축설명
NX102-12208 축4 축12 축상위 모델, 다축 동기화 + 직접 데이터베이스 연결, MES 도킹 및 데이터 수집
NX102-11204 축4 축8 축4 동기 축 + 데이터 베이스, 패키징 및 리튬 배터리 미드스트림 장비용
NX102-10202 축4 축6 축이 모델, 2-축 보간 + 4 PTP, SQL을 지원합니다, MQTT, OPC UA
NX102-90200 중심선4 축4 축보간 없음, PTP 축만, 데이터베이스 포함, 생산 라인 데이터 수집용 + 간단한 포인트 모션
  1. 파생 접미사 모델 (DH 버전, 향상된 시계열 데이터, 특별 주문)

NX102-1220-DH / NX102-1120-DH / NX102-1020-DH / NX102-9020-DH

DH 접미사: 향상된 시계열 데이터 수집, 대규모 데이터 로깅 프로젝트를 위해 설계됨, 특별 주문 품목, 표준 국내 프로젝트에서는 거의 사용되지 않습니다.

  1. 특수 보충 모델

NX102-1D00: 대용량 로직 CPU, 동작 축 없음, 대용량 로직 처리에 중점, EtherCAT 모션 제어 없음. 대규모 생산 라인의 논리 및 통신 관리에 사용됩니다..

✅ 빠른 선택 비교 포인트

  1. 1000 /1020: 6 physical axes (2 보간 +4 PTP). 동일축 성능. 유일한 차이점: NX102-1020은 직접 SQL 데이터베이스 연결을 지원합니다., NX102-1000은 그렇지 않습니다..
  2. 9000/9020: 보간 기능 없음, 단일 축 포인트 모션만 가능; 선형/원형 보간 및 전자 캠 동기화를 사용할 수 없습니다..
  3. 모든 NX102 CPU에는 별도의 NX-PF 전원 공급 장치 모듈이 필요합니다., 내장 전원 공급 장치 없음. 단자 커버 NX-END02는 CPU와 함께 배송됩니다..
  4. 가상 축을 포함한 최대 전체 축: 15 축 (육체적인 합 + 가상 축).
  5. 동일한 플랫폼에서의 상호 참조 (기타 NX1 시리즈 CPU 선택)

NX1P: 경제적인 통합 CPU, NX 로컬 백플레인 확장 없음, 소형 독립형 기계용

NX701: 하이엔드 NX 시리즈, 더 높은 성능, 더 많은 축, 대규모 장비용

이전:

다음:

답장을 남겨주세요

메시지를 남겨주세요