OMRON NX102-1020 Modular CPU Unit - 접촉기,회로 차단기,감지기,인코더,PLC,변환기

위챗: +86-13184948252 왓츠앱: 0086-13811255435 이메일: kent@bestcontactor.com

에 대한 연락하다 |

 OMRON NX102-1020 Modular CPU Unit - 접촉기,회로 차단기,감지기,인코더,PLC,변환기

PLC/

OMRON NX102-1020 Modular CPU Unit

OMRON NX1 Series Machine Automation Controller (MAC, Modular CPU Unit) Sysmac platform, integrating logic, motion and IT communication, a multi-axis motion control model for medium and small-sized equipment. ✅ Model Code Explanation NX102: CPU of NX1 series; 1020: 2-axis synchronous interpolation + 4-axis PTP point-to-point, 총 6 physical axes (최대. 15 axes including virtual axes), ...

  • 제품 세부정보

오므론 NX1 Series Machine Automation Controller (MAC, Modular CPU Unit)

Sysmac platform, integrating logic, motion and IT communication, a multi-axis motion control model for medium and small-sized equipment.

✅ 모델 코드 설명

NX102: CPU of NX1 series; 1020: 2-axis synchronous interpolation + 4-axis PTP point-to-point, 총 6 physical axes (최대. 15 axes including virtual axes), supports direct database connection.

📌 Core Specifications

목사양
프로그램 메모리5 MB
Variable Memory33.5 MB (Retain area:1.5 MB, Non-retain area:32 MB)
Minimum Primary Task Cycle1 ms
Synchronous Axes (Interpolation Axes)2 축
PTP Point-to-Point Axes4 축
맥스. Axes including Virtual Axes15 축
EtherCATMaster station, 최대 64 EtherCAT nodes; supports EtherCAT ring redundancy
Local Expansion최대 32 NX units on NX local bus (입출력, 안전, IO-링크, 등.)
Local I/O Points1024 전철기; 확장 가능 8960 points with NX coupler
포트PORT1/PORT2: 이더넷/IP + TCP/IP; PORT3: EtherCAT
Built-in ProtocolsOPC UA Server, Direct SQL Database Connection, MQTT
프로그래밍 소프트웨어시스맥 스튜디오; Languages: 성 (구조화된 텍스트), LD (래더 다이어그램), 페이스북 (Function Block)
설치DIN 레일 장착; 치수:100(시간)×66(여)×100(디) mm; 무게:470 g
전원공급장치NX power supply unit sold separately (NX-PF series); No built-in battery; Variables backed up by capacitor

🧩 Key Features

  1. 모션 제어

EtherCAT bus servo, supports 2-axis synchronization (linear/circular interpolation) + 4-axis independent point-to-point. Suitable for transferring, picking, simple flying shear and synchronous conveying.

  1. IT Integration (Sysmac Unique Feature)

Direct SQL Connection: Read/write MySQL, SQL Server, Oracle and other databases directly without upper computer relay

OPC UA: Native OPC UA server for connecting to MES and SCADA

MQTT: Connect to cloud platform for equipment data upload

  1. 시스템 확장

NX local bus can mount digital/analog modules, safety controller NX-SL, IO-Link master station; EtherCAT can connect servos, remote I/O and sensors.

  1. Battery-free Design

Capacitor backup for retaining variables. No regular battery replacement required to reduce maintenance cost.

🛠️ Typical Application Scenarios

Medium and small automation equipment: 포장 기계, 라벨링 기계, transfer manipulators, lithium battery front-end equipment, inspection machines and small production lines.

📊 NX102 Series Comparison (For Selection Reference)

NX102-1020: 2 synchronous axes + 4 PTP axes, 총 6 physical axes (이 모델)

NX102-1100: 4 synchronous axes + 4 PTP axes, 총 8 physical axes

NX102-1200: 8 synchronous axes + 4 PTP axes, 총 12 physical axes

⚠️ Notes

  1. No built-in power supply for CPU, NX-PF power supply module must be equipped separately;
  2. SD card slot for program backup and log recording;
  3. Direct database connection and MQTT require corresponding firmware version of Sysmac Studio;
  4. Second-hand inspection points: Check firmware version, EtherCAT port, Ethernet port and SD card slot upon power-on; back up programs and test axis control.

📎 Alternative Solutions Reference

Same brand upgrade: NX102-1100 (more synchronous axes)

Lower version on same platform: NX1P series (integrated type, no NX local bus expansion capability)

OMRON NX102-1020 Troubleshooting Checklist

Troubleshooting Principle: Check LED indicators first → Read Event Log online via Sysmac Studio → Distinguish Fatal Fault (Machine Stop) / Minor Fault (Continue Running) / Information Event. Eliminate root cause before resetting instead of clearing fault codes directly. Reference Manual: W503 (NJ/NX Fault Manual), NX102 Hardware Manual

  1. Power-on Failure, CPU Not Running (POWER Off / Solid Red)
현상가능한 원인문제 해결 단계
POWER LED offDamaged NX-PF power module, no power supply, 느슨한 배선, excessive DC24V voltage drop1. Measure AC/DC input of power module; 2. Check backplane power terminals on DIN rail; 3. Test by replacing NX-PF power unit; 4. Check grounding and short circuit
POWER solid red, cannot enter RUNSerious CPU hardware fault, internal bus error, non-volatile memory damage, 온도 이상1. Power off and cool for 30 minutes then power on; 2. Check event log: 00110000(Overtemp)/000D0000(Internal Bus)/000E0000(Flash End-of-Life); 3. Remove all NX expansion modules, run minimal system with only CPU + 전원 공급 장치; 4. If fault persists under minimal system → CPU hardware failure, replace CPU
Repeated reboot after power-onInsufficient power rating, 백플레인 단락, EMC noise interference1. Calculate total power consumption of NX rack; 2. Check metal debris on backplane; 3. Separate power cables and control cables and improve grounding
  1. Cannot Connect via Sysmac Studio (PORT1/PORT2 Ethernet Port)
현상가능한 원인문제 해결 단계
Ping failure, NET ERR redIP mismatch, Windows firewall, damaged cable/connector, hardware damage of Ethernet port1. Set PC IP to same subnet, turn off Windows firewall; 2. Replace shielded cable, check L/A link lamp of PORT1/PORT2; 3. Reset CPU IP via BOOTP; 4. Test with PORT2; single port failure mostly indicates hardware damage
Ping OK but online download failedMismatched engineering version, CPU write protection, SD card abnormality1. Ensure Sysmac Studio firmware compatible with CPU firmware; 2. Check whether CPU write protection is enabled; 3. Remove SD card and retry; 4. Verify hardware configuration matches actual rack
Project download error, configuration verification failedMismatched model/quantity of NX local bus modules in project1. Verify model and position of NX modules on rack; 2. Remove redundant modules and test minimal rack; 3. Upload hardware configuration again
  1. EtherCAT Bus Fault (PORT3, Most Common in Motion Control)

NX102-1020 built-in EtherCAT master; axis control and remote I/O run on this bus. For EtherCAT fault, use Sysmac EtherCAT diagnosis and frame error counter to locate faulty segment

  1. NX Local Backplane Bus Fault (NX Rack Expansion I/O, Safety Module NX-SL)
현상가능한 원인문제 해결 단계
ERR lamp on NX expansion unit, Event Log 000D0000Poor backplane contact, damaged module, mismatched module model in configuration1. 전원 끄기, re-plug NX modules and ensure buckles locked; 2. Remove modules one by one to locate faulty unit; 3. Verify module model and position in project; 4. Replace damaged NX unit
  1. Motion Control Fault (NX102-1020: 2 Interpolation Axes +4 PTP Axes)
현상가능한 원인문제 해결 단계
Axis homing failedWiring of home sensor, limit signal, home parameter, servo not ready1. Monitor status of home, positive/negative limit I/O; 2. Check servo ready signal; 3. Verify homing mode and offset parameters; 4. Confirm no hardware limit triggered
Motion error alarm during point-to-point / 보간Soft limit, over speed/acceleration, axis lock, servo fault, insufficient task cycle1. Check motion event code; 2. Verify soft limit parameters; 3. Reduce acceleration; 4. Confirm no stop/lock command on axis
Large multi-axis synchronization deviation, flying shear synchronization failureEtherCAT cycle fluctuation, abnormal encoder feedback, incorrect sync parameter1. Monitor position feedback of each axis; 2. Check encoder wiring; 3. Adjust synchronization control parameters; 4. Eliminate bus interference
  1. Built-in Communication Fault (OPC UA / MQTT / Direct SQL Database Connection)
현상가능한 원인문제 해결 단계
OPC UA client connection failed포트, security policy, certificate, IP routing, firewall1. Confirm CPU OPC UA service enabled; 2. Verify certificate trust; 3. Check port open status; 4. Confirm network route reachable
MQTT cloud upload failedWrong Broker address/port, network unreachable, certificate, heartbeat parameter1. Ping MQTT server; 2. Verify account, password and TLS setting; 3. Check MQTT event codes in event log
SQL database read/write failureDatabase IP/port, account permission, driver, packet loss1. Confirm database allows external access; 2. Verify table name, field and SQL statement; 3. Check CPU firmware version (old firmware does not support partial databases)
  1. SD Card Related Fault
현상가능한 원인문제 해결 단계
SD card ERR alarm, backup/log recording failedDamaged SD card, incorrect format, exceeded capacity limit, 접촉 불량1. Take out SD card and reinsert; 2. Use FAT32 format and OMRON recommended industrial SD card; 3. Replace damaged card; 4. Avoid consumer SD cards which easily cause log loss
  1. 환경 & Aging Hardware Faults
  2. Overtemperature Alarm (00110000): Poor cabinet heat dissipation, dust-clogged fan, ambient temperature out of range. Clean dust, 환기를 개선하다; protection shutdown triggered above 60℃.
  3. Non-volatile Memory Life Warning (000E0000): Flash write/erase cycles exhausted. Prepare CPU replacement; frequent variable/log writing accelerates aging.
  4. Accidental shutdown due to noise interference: Power cables run in parallel with control cables, 접지 불량, no shielding. Separate wiring, single-point grounding and add surge absorber.
  5. Fast Troubleshooting Workflow (On-site Operation Sequence)
  6. Power off → Visual inspection: 배선, module buckles, damaged cables, 먼지, short-circuit traces
  7. Power on and record all LED status (POWER/RUN/ERR, EtherCAT, Ethernet L/A)
  8. Go online with Sysmac Studio, read Event Log and record hex event codes
  9. Minimal system test: NX-PF power + NX102-1020 only, remove all NX expansions and EtherCAT slaves to judge whether fault lies in CPU or external peripherals
  10. Segmented isolation: Disconnect EtherCAT segment by segment / remove NX modules one by one to locate faulty unit/cable
  11. Fix root cause → Clear fault → Reset CPU and retest
  12. 중고 / Used NX102-1020 Special Inspection Checklist
  13. 모습: Burn marks, oxidized backplane metal contacts, dents or deformation on housing
  14. Power on minimal system, confirm normal POWER without fatal hardware fault
  15. Go online to read firmware version and event log, check historical faults (flash life, overtemperature records)
  16. SD card slot read-write test
  17. Link test for PORT1/PORT2 Ethernet and PORT3 EtherCAT port
  18. Download blank project to confirm no configuration download error
  19. Connect EtherCAT servo to test axis enable and basic point-to-point motion

OMRON NX102 Full Series Model List (NX1 Modular Machine Automation CPU)

모델 코딩 규칙:

NX102-ABCD

AB: Axis specification; CD: Function version

접미사 -00 = Standard Version (No direct database connection)

접미사 -20 = DB Database Version (Support direct SQL connection & time-series data acquisition, same as NX102-1020)

All models share identical base hardware: 5MB 프로그램 메모리 / 33.5MB variable memory (1.5MB retain area), EtherCAT master, dual EtherNet/IP ports, NX local backplane bus, minimum task cycle 1ms

  1. 표준 버전 (-00, No Direct SQL Database Connection)
모델Synchronous Interpolation AxesPTP Axes맥스. Physical Axes설명
NX102-12008 축4 축12 축High-end model, 다축 동기화, flying shear, 전자 캠, for multi-axis equipment
NX102-11004 축4 축8 축Medium synchronous axes, for transfer and synchronous conveying
NX102-10002 축4 축6 축Basic interpolation model, same axis capability as NX102-1020, without database function
NX102-90000 중심선4 축4 축No interpolation, 오직 4 independent point-to-point axes; for general sequence control + simple point motion, no synchronous interpolation
  1. Database Connection Version (-20, Support Direct SQL & Time-series Data, SD Card Included)
모델Synchronous Interpolation AxesPTP Axes맥스. Physical Axes설명
NX102-12208 축4 축12 축Top model, multi-axis sync + direct database connection, MES docking and data acquisition
NX102-11204 축4 축8 축4 synchronous axes + database, for packaging and lithium battery mid-stream equipment
NX102-10202 축4 축6 축이 모델, 2-axis interpolation + 4 PTP, supports SQL, MQTT, OPC UA
NX102-90200 중심선4 축4 축No interpolation, only PTP axes, with database, for production line data acquisition + simple point motion
  1. Derivative Suffix Model (DH Version, Enhanced Time-series Data, Special Order)

NX102-1220-DH / NX102-1120-DH / NX102-1020-DH / NX102-9020-DH

DH suffix: Enhanced time-series data acquisition, designed for massive data logging projects, special order item, rarely used in standard domestic projects

  1. Special Supplementary Model

NX102-1D00: High-capacity logic CPU, no motion axes, focused on large-volume logic processing, no EtherCAT motion control. Used for logic and communication management of large production lines.

✅ Quick Selection Comparison Points

  1. 1000 /1020: 6 physical axes (2 보간 +4 PTP). Same axis performance. The only difference: NX102-1020 supports direct SQL database connection, NX102-1000 does not.
  2. 9000/9020: No interpolation function, only single-axis point motion; linear/circular interpolation and electronic cam synchronization are unavailable.
  3. All NX102 CPUs require separate NX-PF power supply module, no built-in power supply. Terminal cover NX-END02 is delivered together with CPU.
  4. Maximum total axes including virtual axes: 15 축 (sum of physical + virtual axes).
  5. Cross-reference on Same Platform (Other NX1 Series CPUs for Selection)

NX1P: Economical integrated CPU, no NX local backplane expansion, for small standalone machines

NX701: High-end NX series, 더 높은 성능, more axes, for large-scale equipment

이전:

다음:

답장을 남겨주세요

메시지를 남겨주세요