(Varispeed P7 Inverter Specialized for Fans & 슬리퍼)
- 모델 코드 분석
CIMR-P7U4160 (Full name on nameplate: CIMR-P7U41600 PDF)
CIMR: Universal prefix for Yaskawa 인버터
P7: P7 series, energy-saving V/F inverter dedicated to fans and pumps
유: 400V three-phase high-voltage model (380~480V)
4160: Power rating code, corresponding to 250HP / 160kW class
- Core Electrical Rated Specifications
2.1 Main Circuit Power Ratings
| 목 | 값 |
| Input Specification | 3-상 AC 380~480V, 50/60헤르츠 |
| 정격 입력 전류 | 334 에이 |
| Rated Output Capacity | 230 kVA |
| 정격 출력 전류 | 304 에이 (ND Normal Duty) |
| Matching Motor Power | 250HP / 160kW 3-phase induction motor |
| Max Output Voltage | 3-단계 0 ~ input voltage (최대. 480다섯) |
| 최대 출력 주파수 | 120 헤르츠 |
| 캐리어 주파수 | Adjustable from 2kHz to 10kHz |
| Accel/Decel Time Range | 0.0~6000s, two independent accel/decel groups |
2.2 Allowable Power Supply Fluctuation
전압: +10% / -15%
빈도: ±5%
2.3 제어 성능
Speed Adjustment Range: 40:1 (V/F 제어)
속도 제어 정확도: ±2%~±3%
제어 모드: Standard V/F, Energy-saving Square V/F (for fans & 슬리퍼), Multi-point V/F curve
- 기계 & 환경 사양
- 인클로저 등급: NEMA1 wall-mounted closed cabinet
- 전체 중량: 대략. 170kg
- 작동 주변 온도: 0℃ ~ +40℃ (40℃ 이상에서는 디레이팅 필요)
- 습기: ≤80%RH, 결로가 없을 것
- 고도: No derating below 1000m; 경감하다 1% per additional 100m above 1000m
- 냉각방식: Built-in high-power cooling fan (individually replaceable)
- Braking Mode: Built-in DC dynamic braking; external braking unit/resistor required for high-power regenerative energy
- Hardware Interface Configuration
4.1 주회로 단자 (R/S/T Input; U/V/W Motor Terminals; +/제동 장치; PE Earth)
아르 자형, 에스, 티: 3-phase 380~480V power input
유, 다섯, 여: Connection to 3-phase induction motor
+, -: External braking resistor / regenerative unit connection
체육: 보호 접지 (common ground for cabinet and main circuit)
4.2 Standard Control Circuit Configuration
디지털 입력: 8 채널, switchable between NPN and PNP
Digital Relay Outputs: 2 일반적으로 열린 접점 (fault signal, run status signal)
아날로그 입력: 2 채널 (0~10V / 4~20mA frequency reference)
Analog Outputs: 2 채널 (monitor frequency, 현재의, 전압)
의사소통: 표준 Modbus-RTU; optional Profibus & DeviceNet communication cards
Digital Operator: 5-line 16-character LCD, supports parameter upload, download and copy
- 일반적인 애플리케이션 시나리오
The P7 series is designed specifically for square-torque loads. The high-power CIMR-P7U4160 model applies to:
- Large cooling water circulation pumps, municipal water supply booster pumps
- Factory centrifugal fans, 보일러 유도 통풍 팬, main dust removal fans
- Central air-conditioning chiller units, large cooling tower water pumps
- 채광 & metallurgy dust exhaust fans, wastewater treatment aeration pumps
장점: Built-in energy-saving square torque curve, sleep function, multi-pump rotation switching, constant pressure PID control
- Discontinued Replacement Solution (P7 series fully discontinued)
Direct Drop-in Upgrade: Yaskawa P1000 Series
Equivalent replacement model: CIMR-PU4A0415ABA
- Fully matched power rating: 304A output, compatible with 160kW motors
- Full function coverage: Retains all fan & pump dedicated functions of P7 (다중 펌프 제어, PID, 수면 모드)
- Highly compatible communication protocols, terminal logic and parameter sets, low renovation workload
- Merits: Higher energy efficiency, 내장형 EMC 필터, enhanced fault diagnosis, abundant spare parts
Alternative General Heavy-Duty Option: A1000 Series
(Vector type, selected for heavy-duty or closed-loop control demands)
- 일반적인 오류 코드 & 문제 해결 매트릭스 (Universal for P7 Series)
| 오류 코드 | 오류 설명 | 근본 원인 | 교정 조치 |
| OC/OC1/OC2/OC3 | Overcurrent during Accel / Decel / Constant Speed | Motor short circuit, cable earth fault, mechanical stall, overly short accel/decel time | 모터 절연 테스트; extend accel/decel time; inspect mechanical jamming |
| GF | Output Ground Fault | Damaged insulation on U/V/W cables, motor winding breakdown to earth | Disconnect motor cables section by section and test insulation separately |
| 자외선 | DC Bus Undervoltage | Mains phase loss, excessive voltage drop, poor contact of contactor | Measure three-phase voltage of R/S/T; fasten main circuit terminals |
| OV | DC Bus Overvoltage | Excessively fast deceleration, no braking resistor, 높은 주전압 | Lengthen deceleration time; install external braking unit |
| OL1 | 모터 과부하 | 과도한 부하, long-time low-speed operation, incorrect motor current parameter | Verify rated motor current parameter E2-01; 부하를 줄이다 |
| OL2 | Inverter Overload | Sustained 150% 정격 전류 1 분 | 부하 감소, upgrade inverter size, lower carrier frequency |
| SPI | Input Phase Loss | Broken wire on one R/S/T phase, blown fuse | Inspect input circuit breaker, terminals and three-phase voltage balance |
| SPO | 출력 위상 손실 | Disconnection of one U/V/W phase, burnt single-phase motor contact | Tighten motor terminals; 테스트 케이블 연속성 |
| OH1/OH2 | 과열 (방열판) | Dust-clogged air duct, damaged cooling fan, ambient temperature over 40℃ | Clean air filter; replace cooling fan; 환기를 개선하다 |
| LF | Output Three-Phase Imbalance | Damaged motor winding, loose wiring terminals | Measure three-phase output current; fasten all terminals |
- Strict Wiring & Installation Prohibitions
- Main power cables and control signal wires must be routed in separate cable trays with a minimum spacing of 30cm; long parallel laying is forbidden.
- Shielded motor cables are recommended; shield shall be grounded only at the control cabinet end.
- Main circuit copper busbars of high-power models shall be tinned and tightened with specified torque to avoid overheating and arcing.
- For multi-pump linked systems, AC contactors shall not be installed on the inverter output side for frequent switching.
- For sites with heavy dust and moisture, clean air duct filters regularly to prevent overheat alarms.
- If long motor cables (>50중) 필수, an output du/dt filter must be installed to suppress peak voltage and protect motor insulation.
- Key Basic Commissioning Parameters (Standard for Fan & 펌프 응용)
- E1-06 Base Frequency: Rated 50/60Hz as marked on motor nameplate
- E1-13 Square V/F (Fan Energy Saving): 다음으로 설정 2 to enable square torque curve
- b5 PID Pressure Closed-Loop: Set target pressure and P/I/D gains
- b5-17 Sleep Function: Low-frequency energy-saving sleep, auto-stop during idle periods
- C1-01~C1-04 Accel & Decel Time: ≥15s recommended for pumps, ≥30s for fans to avoid overcurrent
- E2-01 Motor Rated Current: Enter value per motor nameplate, baseline for overload protection
Complete Model List of Yaskawa Varispeed P7 Series (CIMR-P7U□4□□□) 400V 시리즈
메모
- Series Naming Rule: `CIMR-P7U4XXX0`. The full code printed on the nameplate ends with digit 0, which is omitted as the short model number for selection (예를 들어, CIMR-P7U4160).
- U = Dedicated 3-phase 380~480V model for fans and pumps; ND Normal Duty (square-torque loads for fans & 슬리퍼).
- Power correspondence unit: kW / HP / 정격 출력 전류 (에이).
- The entire series adopts V/F control, built-in square torque curve and PID multi-pump control. This series has been fully discontinued, with replacement models CIMR-PU4A□□□□ (P1000 series).
- 낮은 & Medium Power Range (7.5kW ~ 132kW)
| 전체 모델 번호. | Matching Motor Power | 정격 출력 전류 (에이) |
| CIMR-P7U40070 | 7.5kW / 10HP | 18 |
| CIMR-P7U40110 | 11kW / 15HP | 24 |
| CIMR-P7U40150 | 15kW / 20HP | 30 |
| CIMR-P7U40180 | 18.5kW / 25HP | 37 |
| CIMR-P7U40220 | 22kW / 30HP | 43 |
| CIMR-P7U40300 | 30kW / 40HP | 57 |
| CIMR-P7U40370 | 37kW / 50HP | 69 |
| CIMR-P7U40450 | 45kW / 60HP | 83 |
| CIMR-P7U40550 | 55kW / 75HP | 106 |
| CIMR-P7U40750 | 75kW / 100HP | 130 |
| CIMR-P7U40900 | 90kW / 125HP | 160 |
| CIMR-P7U41100 | 110kW / 150HP | 192 |
| CIMR-P7U41320 | 132kW / 175HP | 232 |
- High Power Range (160kW ~ 400kW, including CIMR-P7U4160 you inquired)
| 전체 모델 번호. | Matching Motor Power | 정격 출력 전류 (에이) |
| CIMR-P7U41600 | 160kW / 250HP | 304 |
| CIMR-P7U42000 | 200kW / 300HP | 370 |
| CIMR-P7U42200 | 220kW / 330HP | 415 |
| CIMR-P7U42500 | 250kW / 375HP | 460 |
| CIMR-P7U43150 | 315kW / 450HP | 580 |
| CIMR-P7U43750 | 375kW / 500HP | 690 |
| CIMR-P7U44000 | 400kW / 540HP | 730 |
Supplementary Key Remarks
- 200V single/3-phase P7 models (P7E / P72 series) are excluded from the above table. This list only covers mainstream industrial 400V 3-phase fan & pump models P7U.
- Model Abbreviation Rule: The trailing digit 0 is often omitted in engineering drawings and procurement documents. 예를 들어, CIMR-P7U41600 is abbreviated as CIMR-P7U4160.
- Cabinet Classification: Models ≤132kW adopt standard wall-mounted cabinets; models ≥160kW (4160 이상) are large floor-standing cabinets equipped with independent high-power cooling fans.
- Distinction of output versions at the same power rating:
Standard built-in braking transistor; high-power models 4160 and above require an external braking unit + braking resistor to implement dynamic braking during deceleration.
- Discontinued Model Replacement Mapping (P7U4XXXX → P1000 PU4AXXXX)
CIMR-P7U41600 (160kW) → CIMR-PU4A0415ABA
CIMR-P7U42000 (200kW) → CIMR-PU4A0475ABA
CIMR-P7U42500 (250kW) → CIMR-PU4A0605ABA