야스카와 CIMR-P7U4160 인버터

https://www.bestcontactor.com/product/yaskawa-cimr-ab4a0018fba-inverter/

(Varispeed P7 Inverter Specialized for Fans & 슬리퍼)

  1. 모델 코드 분석

CIMR-P7U4160 (Full name on nameplate: CIMR-P7U41600 PDF)

CIMR: Universal prefix for Yaskawa 인버터

P7: P7 series, energy-saving V/F inverter dedicated to fans and pumps

유: 400V three-phase high-voltage model (380~480V)

4160: Power rating code, corresponding to 250HP / 160kW class

  1. Core Electrical Rated Specifications

2.1 Main Circuit Power Ratings

Input Specification3-상 AC 380~480V, 50/60헤르츠
정격 입력 전류334 에이
Rated Output Capacity230 kVA
정격 출력 전류304 에이 (ND Normal Duty)
Matching Motor Power250HP / 160kW 3-phase induction motor
Max Output Voltage3-단계 0 ~ input voltage (최대. 480다섯)
최대 출력 주파수120 헤르츠
캐리어 주파수Adjustable from 2kHz to 10kHz
Accel/Decel Time Range0.0~6000s, two independent accel/decel groups

2.2 Allowable Power Supply Fluctuation

전압: +10% / -15%

빈도: ±5%

2.3 제어 성능

Speed Adjustment Range: 40:1 (V/F 제어)

속도 제어 정확도: ±2%~±3%

제어 모드: Standard V/F, Energy-saving Square V/F (for fans & 슬리퍼), Multi-point V/F curve

  1. 기계 & 환경 사양
  2. 인클로저 등급: NEMA1 wall-mounted closed cabinet
  3. 전체 중량: 대략. 170kg
  4. 작동 주변 온도: 0℃ ~ +40℃ (40℃ 이상에서는 디레이팅 필요)
  5. 습기: ≤80%RH, 결로가 없을 것
  6. 고도: No derating below 1000m; 경감하다 1% per additional 100m above 1000m
  7. 냉각방식: Built-in high-power cooling fan (individually replaceable)
  8. Braking Mode: Built-in DC dynamic braking; external braking unit/resistor required for high-power regenerative energy
  9. Hardware Interface Configuration

4.1 주회로 단자 (R/S/T Input; U/V/W Motor Terminals; +/제동 장치; PE Earth)

아르 자형, 에스, 티: 3-phase 380~480V power input

유, 다섯, 여: Connection to 3-phase induction motor

+, -: External braking resistor / regenerative unit connection

체육: 보호 접지 (common ground for cabinet and main circuit)

4.2 Standard Control Circuit Configuration

디지털 입력: 8 채널, switchable between NPN and PNP

Digital Relay Outputs: 2 일반적으로 열린 접점 (fault signal, run status signal)

아날로그 입력: 2 채널 (0~10V / 4~20mA frequency reference)

Analog Outputs: 2 채널 (monitor frequency, 현재의, 전압)

의사소통: 표준 Modbus-RTU; optional Profibus & DeviceNet communication cards

Digital Operator: 5-line 16-character LCD, supports parameter upload, download and copy

  1. 일반적인 애플리케이션 시나리오

The P7 series is designed specifically for square-torque loads. The high-power CIMR-P7U4160 model applies to:

  1. Large cooling water circulation pumps, municipal water supply booster pumps
  2. Factory centrifugal fans, 보일러 유도 통풍 팬, main dust removal fans
  3. Central air-conditioning chiller units, large cooling tower water pumps
  4. 채광 & metallurgy dust exhaust fans, wastewater treatment aeration pumps

장점: Built-in energy-saving square torque curve, sleep function, multi-pump rotation switching, constant pressure PID control

  1. Discontinued Replacement Solution (P7 series fully discontinued)

Direct Drop-in Upgrade: Yaskawa P1000 Series

Equivalent replacement model: CIMR-PU4A0415ABA

  1. Fully matched power rating: 304A output, compatible with 160kW motors
  2. Full function coverage: Retains all fan & pump dedicated functions of P7 (다중 펌프 제어, PID, 수면 모드)
  3. Highly compatible communication protocols, terminal logic and parameter sets, low renovation workload
  4. Merits: Higher energy efficiency, 내장형 EMC 필터, enhanced fault diagnosis, abundant spare parts

Alternative General Heavy-Duty Option: A1000 Series

(Vector type, selected for heavy-duty or closed-loop control demands)

  1. 일반적인 오류 코드 & 문제 해결 매트릭스 (Universal for P7 Series)
오류 코드오류 설명근본 원인교정 조치
OC/OC1/OC2/OC3Overcurrent during Accel / Decel / Constant SpeedMotor short circuit, cable earth fault, mechanical stall, overly short accel/decel time모터 절연 테스트; extend accel/decel time; inspect mechanical jamming
GFOutput Ground FaultDamaged insulation on U/V/W cables, motor winding breakdown to earthDisconnect motor cables section by section and test insulation separately
자외선DC Bus UndervoltageMains phase loss, excessive voltage drop, poor contact of contactorMeasure three-phase voltage of R/S/T; fasten main circuit terminals
OVDC Bus OvervoltageExcessively fast deceleration, no braking resistor, 높은 주전압Lengthen deceleration time; install external braking unit
OL1모터 과부하과도한 부하, long-time low-speed operation, incorrect motor current parameterVerify rated motor current parameter E2-01; 부하를 줄이다
OL2Inverter OverloadSustained 150% 정격 전류 1 분부하 감소, upgrade inverter size, lower carrier frequency
SPIInput Phase LossBroken wire on one R/S/T phase, blown fuseInspect input circuit breaker, terminals and three-phase voltage balance
SPO출력 위상 손실Disconnection of one U/V/W phase, burnt single-phase motor contactTighten motor terminals; 테스트 케이블 연속성
OH1/OH2과열 (방열판)Dust-clogged air duct, damaged cooling fan, ambient temperature over 40℃Clean air filter; replace cooling fan; 환기를 개선하다
LFOutput Three-Phase ImbalanceDamaged motor winding, loose wiring terminalsMeasure three-phase output current; fasten all terminals
  1. Strict Wiring & Installation Prohibitions
  2. Main power cables and control signal wires must be routed in separate cable trays with a minimum spacing of 30cm; long parallel laying is forbidden.
  3. Shielded motor cables are recommended; shield shall be grounded only at the control cabinet end.
  4. Main circuit copper busbars of high-power models shall be tinned and tightened with specified torque to avoid overheating and arcing.
  5. For multi-pump linked systems, AC contactors shall not be installed on the inverter output side for frequent switching.
  6. For sites with heavy dust and moisture, clean air duct filters regularly to prevent overheat alarms.
  7. If long motor cables (>50중) 필수, an output du/dt filter must be installed to suppress peak voltage and protect motor insulation.
  8. Key Basic Commissioning Parameters (Standard for Fan & 펌프 응용)
  9. E1-06 Base Frequency: Rated 50/60Hz as marked on motor nameplate
  10. E1-13 Square V/F (Fan Energy Saving): 다음으로 설정 2 to enable square torque curve
  11. b5 PID Pressure Closed-Loop: Set target pressure and P/I/D gains
  12. b5-17 Sleep Function: Low-frequency energy-saving sleep, auto-stop during idle periods
  13. C1-01~C1-04 Accel & Decel Time: ≥15s recommended for pumps, ≥30s for fans to avoid overcurrent
  14. E2-01 Motor Rated Current: Enter value per motor nameplate, baseline for overload protection

Complete Model List of Yaskawa Varispeed P7 Series (CIMR-P7U□4□□□) 400V 시리즈

메모

  1. Series Naming Rule: `CIMR-P7U4XXX0`. The full code printed on the nameplate ends with digit 0, which is omitted as the short model number for selection (예를 들어, CIMR-P7U4160).
  2. U = Dedicated 3-phase 380~480V model for fans and pumps; ND Normal Duty (square-torque loads for fans & 슬리퍼).
  3. Power correspondence unit: kW / HP / 정격 출력 전류 (에이).
  4. The entire series adopts V/F control, built-in square torque curve and PID multi-pump control. This series has been fully discontinued, with replacement models CIMR-PU4A□□□□ (P1000 series).
  5. 낮은 & Medium Power Range (7.5kW ~ 132kW)
전체 모델 번호.Matching Motor Power정격 출력 전류 (에이)
CIMR-P7U400707.5kW / 10HP18
CIMR-P7U4011011kW / 15HP24
CIMR-P7U4015015kW / 20HP30
CIMR-P7U4018018.5kW / 25HP37
CIMR-P7U4022022kW / 30HP43
CIMR-P7U4030030kW / 40HP57
CIMR-P7U4037037kW / 50HP69
CIMR-P7U4045045kW / 60HP83
CIMR-P7U4055055kW / 75HP106
CIMR-P7U4075075kW / 100HP130
CIMR-P7U4090090kW / 125HP160
CIMR-P7U41100110kW / 150HP192
CIMR-P7U41320132kW / 175HP232
  1. High Power Range (160kW ~ 400kW, including CIMR-P7U4160 you inquired)
전체 모델 번호.Matching Motor Power정격 출력 전류 (에이)
CIMR-P7U41600160kW / 250HP304
CIMR-P7U42000200kW / 300HP370
CIMR-P7U42200220kW / 330HP415
CIMR-P7U42500250kW / 375HP460
CIMR-P7U43150315kW / 450HP580
CIMR-P7U43750375kW / 500HP690
CIMR-P7U44000400kW / 540HP730

Supplementary Key Remarks

  1. 200V single/3-phase P7 models (P7E / P72 series) are excluded from the above table. This list only covers mainstream industrial 400V 3-phase fan & pump models P7U.
  2. Model Abbreviation Rule: The trailing digit 0 is often omitted in engineering drawings and procurement documents. 예를 들어, CIMR-P7U41600 is abbreviated as CIMR-P7U4160.
  3. Cabinet Classification: Models ≤132kW adopt standard wall-mounted cabinets; models ≥160kW (4160 이상) are large floor-standing cabinets equipped with independent high-power cooling fans.
  4. Distinction of output versions at the same power rating:

Standard built-in braking transistor; high-power models 4160 and above require an external braking unit + braking resistor to implement dynamic braking during deceleration.

  1. Discontinued Model Replacement Mapping (P7U4XXXX → P1000 PU4AXXXX)

CIMR-P7U41600 (160kW) → CIMR-PU4A0415ABA

CIMR-P7U42000 (200kW) → CIMR-PU4A0475ABA

CIMR-P7U42500 (250kW) → CIMR-PU4A0605ABA

이전: