NXC-65 from the Kunlun Series by CHINT Electric is a 3-pole AC contactor, rated at 65A in the NXC series. The full model is typically expressed as NXC-65 [Coil Voltage] [Frequency] (e.g., NXC-65 220V 50Hz). It is mainly used for frequent starting and control of AC motors, as well as remote making and breaking of circuits.
Core Electrical Parameters
| Item | Specification | Description |
| Rated Operational Current (Ie) | 65A | Rated current of the main circuit |
| Conventional Thermal Current (Ith) | 80A | Maximum continuous operating current |
| Rated Operational Voltage (Ue) | 220V~690V | Voltage range of the main circuit |
| Number of Poles | 3P | Three-phase main contact design |
| Main Contact Configuration | 3NO (3 Normally Open) | Standard for connecting three-phase power |
| Auxiliary Contacts | 1NO + 1NC | Built-in 1 NO and 1 NC, expandable |
| Coil Voltage | AC24V/127V/220V/380V, etc. | Multiple voltages available for various control systems |
| Mechanical Life | 1,200,000 operations | Mechanical operating cycles |
| Electrical Life | 100,000 operations | Electrical cycles under rated load |
| Applicable Standards | GB/T 14048.1/IEC 60947-1, GB/T 14048.4/IEC 60947-4-1 | National and international standards |
Product Features
- Compact structure: Kunlun series design, small size, low installation space requirement
- High reliability: Made of high-quality materials with precision manufacturing, suitable for harsh industrial environments
- Low power consumption: Low coil power loss, obvious energy-saving effect
- Easy installation & maintenance: Standard 35mm DIN rail mounting, clear terminals for easy operation
- Strong expandability: Optional auxiliary contacts, air delay modules and other accessories available
- Good safety performance: Excellent arc extinguishing performance and high breaking capacity
Applications
AC motor control: Frequent start, stop and reversing control for three-phase asynchronous motors up to approx. 30kW
Industrial automation systems: Control of production lines, conveyors, fans, pumps, etc.
Electrical control systems: Combined with thermal overload relays to form magnetic starters for motor overload protection
Building electrical: Air conditioning systems, fire equipment, water pump control systems
New energy equipment: Auxiliary control circuits for charging piles, PV inverters, etc.
Partial List of CHINT NXC Series Models
| Model | Rated Current | Conventional Thermal Current | Typical Motor Power | Notes |
| NXC-06 | 6A | 10A | Up to 2.2kW | Minimum rating |
| NXC-12 | 12A | 16A | Up to 5.5kW | |
| NXC-18 | 18A | 25A | Up to 7.5kW | |
| NXC-25 | 25A | 32A | Up to 11kW | |
| NXC-32 | 32A | 40A | Up to 15kW | |
| NXC-40 | 40A | 50A | Up to 18.5kW | |
| NXC-50 | 50A | 63A | Up to 22kW | |
| NXC-65 | 65A | 80A | Up to 30kW | |
| NXC-80 | 80A | 100A | Up to 37kW | |
| NXC-95 | 95A | 125A | Up to 45kW | |
| NXC-115 | 115A | 140A | Up to 55kW | |
| NXC-150 | 150A | 175A | Up to 75kW |
Cross-Brand Comparison (Equivalent AC Contactors)
Below is a comparison between CHINT NXC-65 and equivalent contactors from major brands, all functionally compatible:
| CHINT | Schneider | Siemens | ABB | Delixi | Compatibility |
| NXC-65 | LC1D65M7C | 3RT2036-1AP00 | A63-30-10 | CJX2-6511 | Functionally compatible, slight dimensional differences, mounting may need adjustment |
Brand Feature Comparison
| Brand | Core Strengths | Typical Applications |
| CHINT | Cost-effective, extensive after-sales network | General industrial control, civil & building electrical |
| Schneider | International brand, mature technology, high reliability | High-end industrial automation, critical equipment |
| Siemens | High intelligence, strong communication functions | Industry 4.0, intelligent manufacturing |
| ABB | High performance, robust in harsh environments | Heavy industry, new energy, rail transit |
| Delixi | Affordable, high domestic market share | SMEs, civil electrical systems |
Important Notes
- Ensure the coil voltage matches the control system to avoid malfunction.
- Use the contactor with protective devices such as thermal overload relays for motor overload protection.
- For high-frequency operation, select models with longer electrical life or increase maintenance frequency.
- Ensure firm wiring of main and control circuits to prevent failures caused by poor contact.
CHINT Contactor Full Series Coding System & Cross-Brand Reference
- CHINT Contactor Series Overview & Naming Rules
1.1 Main Series Classification
| Series | Positioning | Current Range | Typical Applications |
| NXC Series | Kunlun, new flagship | 6A~630A | General industrial control, motor starting, power distribution |
| NC1 Series | Economic basic series | 9A~95A | Small equipment, lighting control |
| NC2 Series | Standard industrial series | 9A~630A | General industrial & motor control |
| NC8 Series | High-performance series | 6A~100A | Frequent operation, precision control |
| CJX2 Series | Classic predecessor of NXC | 9A~95A | Traditional industrial equipment, small motors |
| CJ20 Series | High-current series | 10A~630A | High-power motors, heavy-duty equipment |
| CJ19 Series | Capacitor switching dedicated | 16A~100A | Reactive power compensation, capacitor cabinets |
| NCH8 Series | Household / civil use | 16A~63A | Smart home, small appliances |
| NXJ Series | Mini electromagnetic relay | 5A~10A | Control circuits, signal switching |
| CKJ Series | Vacuum contactor | 63A~630A | High-voltage applications, frequent starting |
1.2 CHINT Contactor Model Naming Rules
NXC Series Format
NXC □□□ [M] [Coil Voltage] [Frequency]
│ │ │ │ │
│ │ │ │ └─ Coil frequency (50Hz/60Hz, default 50Hz)
│ │ │ └─ Coil voltage (AC24V/110V/220V/380V or DC24V/110V/220V)
│ │ └─ M = reversing contactor; blank = non-reversing
│ └─ Rated operational current (A)
└─ Brand code + product type (CHINT + AC contactor)
Auxiliary Contact Marking
Base model: default 1NO + 1NC (11)
Extended format: NXC-□□□-[XX], where XX = contact combination (01=0NO1NC, 22=2NO2NC)
Special Function Codes
Z: DC-operated contactor
N: Reversing contactor (NS = horizontal, NC = vertical)
-12: Newer version with improved performance
- Complete CHINT Contactor Model List
2.1 Full NXC Series (Kunlun)
| Model | Rated Current | Thermal Current | Typical Motor Power (AC-3, 380V) | Base Aux. Contacts |
| NXC-06 | 6A | 10A | Up to 2.2kW | 1NO+1NC |
| NXC-09 | 9A | 12.5A | Up to 3kW | 1NO+1NC |
| NXC-12 | 12A | 16A | Up to 5.5kW | 1NO+1NC |
| NXC-18 | 18A | 25A | Up to 7.5kW | 1NO+1NC |
| NXC-25 | 25A | 32A | Up to 11kW | 1NO+1NC |
| NXC-32 | 32A | 40A | Up to 15kW | 1NO+1NC |
| NXC-40 | 40A | 50A | Up to 18.5kW | 1NO+1NC |
| NXC-50 | 50A | 63A | Up to 22kW | 1NO+1NC |
| NXC-65 | 65A | 80A | Up to 30kW | 1NO+1NC |
| NXC-80 | 80A | 100A | Up to 37kW | 1NO+1NC |
| NXC-95 | 95A | 125A | Up to 45kW | 1NO+1NC |
| NXC-115 | 115A | 140A | Up to 55kW | 1NO+1NC |
| NXC-150 | 150A | 175A | Up to 75kW | 1NO+1NC |
| NXC-185 | 185A | 210A | Up to 90kW | 1NO+1NC |
| NXC-225 | 225A | 250A | Up to 110kW | 1NO+1NC |
| NXC-265 | 265A | 300A | Up to 132kW | 1NO+1NC |
| NXC-300 | 300A | 350A | Up to 160kW | 1NO+1NC |
| NXC-370 | 370A | 400A | Up to 200kW | 1NO+1NC |
| NXC-400 | 400A | 450A | Up to 220kW | 1NO+1NC |
| NXC-500 | 500A | 560A | Up to 250kW | 1NO+1NC |
| NXC-630 | 630A | 700A | Up to 315kW | 1NO+1NC |
2.2 Core Models of Other Series
| Series | Core Models | Current Range | Key Features |
| NC1 | NC1-09/12/18/25/32/40 /50/65/80/95 | 9A~95A | Compact, economical |
| NC2 | NC2-09~150 | 9A~150A | Standard design, versatile |
| NC8 | NC8-06~100 | 6A~100A | Low power, long mechanical life |
| CJX2 | CJX2-09~95 | 9A~95A | Mounting compatible with Schneider LC1-D |
| CJ20 | CJ20-10~630 | 10A~630A | High current carrying capacity |
| CJ19 | CJ19-16~100 | 16A~100A | Special arc quenching for capacitor switching |
- Cross-Brand Reference for CHINT Contactors
3.1 General Contactor Cross Reference (AC-3, 380V)
| CHINT | Schneider | Siemens | ABB | Delixi | Functional Compatibility |
| NXC-06 | LC1D0610M5C | 3RT2015-1AP00 | A6-30-10 | CJX2-0610 | Fully compatible, minor dimensional differences |
| NXC-09 | LC1D0910M5C | 3RT2016-1AP00 | A9-30-10 | CJX2-0910 | Fully compatible, minor dimensional differences |
| NXC-12 | LC1D1210M5C | 3RT2017-1AP00 | A12-30-10 | CJX2-1210 | Fully compatible, minor dimensional differences |
| NXC-18 | LC1D1810M5C | 3RT2026-1AP00 | A18-30-10 | CJX2-1810 | Fully compatible, minor dimensional differences |
| NXC-25 | LC1D2510M5C | 3RT2027-1AP00 | A26-30-10 | CJX2-2510 | Fully compatible, minor dimensional differences |
| NXC-32 | LC1D3210M5C | 3RT2036-1AP00 | A30-30-10 | CJX2-3210 | Fully compatible, minor dimensional differences |
| NXC-40 | LC1D4010M5C | 3RT2037-1AP00 | A40-30-10 | CJX2-4010 | Fully compatible, minor dimensional differences |
| NXC-50 | LC1D5010M5C | 3RT2040-1AP00 | A50-30-10 | CJX2-5010 | Fully compatible, minor dimensional differences |
| NXC-65 | LC1D6510M5C | 3RT2046-1AP00 | A63-30-10 | CJX2-6510 | Fully compatible, minor dimensional differences |
| NXC-80 | LC1D8010M5C | 3RT2056-1AP00 | A75-30-10 | CJX2-8010 | Fully compatible, minor dimensional differences |
| NXC-95 | LC1D9510M5C | 3RT2066-1AP00 | A95-30-10 | CJX2-9510 | Fully compatible, minor dimensional differences |
| NXC-115 | LC1D11510M5C | 3RT2076-1AP00 | A110-30-10 | CJX2-11510 | Generally compatible, mounting may need adjustment |
| NXC-150 | LC1D15010M5C | 3RT2086-1AP00 | A145-30-10 | CJX2-15010 | Generally compatible, mounting may need adjustment |
3.2 Brand Technical Comparison
| Brand | Technical Features | Strengths | Price Position |
| CHINT | Modular Kunlun design, low-power coil, long-life contacts | General industry, building electrics | Mid-low, cost-effective |
| Schneider | TeSys series, intelligent control, rich communication | High-end automation, critical loads | Mid-high, leading tech |
| Siemens | 3RT series, high reliability, integrated protection | Industry 4.0, smart manufacturing | High, stable |
| ABB | Modular, high noise immunity, eco-friendly materials | Heavy industry, new energy, transit | High, premium performance |
| Delixi | CJX2 compatible with CHINT | SMEs, civil installations | Low, affordable |
- Selection & Replacement Guidelines
4.1 Key Selection Parameters
- Rated current (Ie): Select according to load; for motors, Ie ≥ 1.2 × motor rated current.
- Coil voltage: Must match control system (AC/DC not interchangeable).
- Operating frequency: For >1200 operations/hour, use long-life models.
- Auxiliary contacts: Choose based on control logic (default 1NO+1NC).
- Mounting: Standard 35mm DIN rail; high-current models may use bolt mounting.
4.2 Cross-Brand Replacement Notes
- Mechanical compatibility
NXC mostly compatible with Schneider LC1-D mounting, but hole positions differ slightly.
Models above 100A vary greatly; brackets may need modification.
- Electrical compatibility
Coil voltage and frequency must match exactly.
Auxiliary contact ratings differ (CHINT ~5A, some Schneider ~10A).
Short-circuit coordination with fuses/circuit breakers should be rechecked.
- Performance differences
NXC: mechanical life 1.2 million, electrical life 100,000 (AC-3).
Premium Schneider/Siemens models reach 200,000 electrical cycles for ultra-frequent use.
4.3 NXC vs CJX2 Replacement
| CHINT CJX2 | Equivalent NXC | Upgrade Benefits |
| CJX2-09 | NXC-09 | Smaller, lower power, longer life |
| CJX2-12 | NXC-12 | Smaller, lower power, longer life |
| CJX2-18 | NXC-18 | Smaller, lower power, longer life |
| CJX2-25 | NXC-25 | Smaller, lower power, longer life |
| CJX2-32 | NXC-32 | Smaller, lower power, longer life |
| CJX2-40 | NXC-40 | Smaller, lower power, longer life |
| CJX2-50 | NXC-50 | Smaller, lower power, longer life |
| CJX2-65 | NXC-65 | Smaller, lower power, longer life |
| CJX2-80 | NXC-80 | Smaller, lower power, longer life |
| CJX2-95 | NXC-95 | Smaller, lower power, longer life |
- Quick Motor Selection Table
| Motor Power (kW) | Rated Current (A) | Recommended CHINT | Schneider | Siemens | ABB |
| 2.2 | 5 | NXC-06 | LC1D0610 | 3RT2015 | A6-30-10 |
| 3 | 6.5 | NXC-09 | LC1D0910 | 3RT2016 | A9-30-10 |
| 5.5 | 12 | NXC-12 | LC1D1210 | 3RT2017 | A12-30-10 |
| 7.5 | 16 | NXC-18 | LC1D1810 | 3RT2026 | A18-30-10 |
| 11 | 23 | NXC-25 | LC1D2510 | 3RT2027 | A26-30-10 |
| 15 | 32 | NXC-32 | LC1D3210 | 3RT2036 | A30-30-10 |
| 18.5 | 39 | NXC-40 | LC1D4010 | 3RT2037 | A40-30-10 |
| 22 | 47 | NXC-50 | LC1D5010 | 3RT2040 | A50-30-10 |
| 30 | 63 | NXC-65 | LC1D6510 | 3RT2046 | A63-30-10 |
| 37 | 78 | NXC-80 | LC1D8010 | 3RT2056 | A75-30-10 |
| 45 | 94 | NXC-95 | LC1D9510 | 3RT2066 | A95-30-10 |
CHINT contactors cover a full range from 6A to 630A. The NXC (Kunlun) series offers greatly improved performance, reliability and compatibility, and can directly replace the CJX2 series and equivalent products from other brands. For cross-brand replacement, verify rated current, coil voltage, mounting dimensions and auxiliary contact configuration to ensure stable system operation.
Contactor,circuit breaker,solar inverter,electric meter,solar batteries



















NH42-63-318x560.png)