Status: Discontinued (Last Order Date: 29 September 2023). No direct replacement officially recommended by Panasonic
Type: 48×48mm panel-mounted PID temperature controller
✅ Model Code Breakdown (AKT4R 1 1 1 1 00)
- AKT4R: KT4R series, 48×48 size
- 1st digit: Power supply 1 = AC100–240V
- 2nd digit: Input 1 = Multi-input (TC / RTD / DC voltage / DC current)
- 3rd digit: Main control output 1 = Relay contact output
- 4th digit: Alarm output 1 = 1-point relay alarm
- 5th–6th digits: 00 = No RS485 communication, no heating/cooling control, no heater burnout alarm
📋 Key Specifications
Overall dimension: 48 × 48 × 58.8 mm, panel mounting
Power supply: AC 100–240V (50/60Hz), power consumption approx. 8VA
Input types (multi-input):
Thermocouple: K, J, R, S, B, E, T, N, PL-II, W
RTD (Resistance Temperature Detector)
DC voltage / DC current analog signal
Control output: Relay contact output
Alarm: 1-point relay alarm output
Functional limitations: No heating/cooling dual control, no heater burnout alarm, no communication port
Control mode: PID
Accuracy: ±0.2% FS of full range
Ambient conditions: 0~50℃, 35~85%RH (non-condensing)
Weight: Approx. 120g
Front panel: With sealing gasket, IP66 rating (panel side)
⚠️ Application & Replacement Notes
Typical applications: Ovens, heating molds, small heat treatment equipment, packaging machinery single-path constant temperature control
No official direct replacement; compatible engineering alternatives:
New Panasonic KT4 series (AKT4□ series; check terminals, logic and panel cutout size)
OMRON E5CC / E5CB, Fuji PXR4, RKC RH400 (all 48×48 relay output temperature controllers)
Replacement verification points: input type, relay capacity, alarm logic, PID parameter settings, panel cutout dimension
📌 Same Series Reference Models
AKT4R111100: No communication
AKT4R1111001: Same specs + RS485 communication port
(Equivalent to AKT4R111100: 48×48, AC100–240V, multi-input, relay main output, 1-point alarm, no communication, no heating/cooling function)
Important: No pin-to-pin direct plug-and-play replacement. Terminal definitions differ on all alternatives; re-wiring and PID reconfiguration are mandatory.
- Japanese Imported Models (Original Equipment Replacement, High Stability, Preferred for Foreign Trade)
- OMRON E5CC-RX2ASM-800
Specs: 48×48, AC100–240V, multi-input, OUT1 relay output, 1-channel alarm, PID auto-tuning
Difference: Different terminal layout and alarm menu; identical panel cutout for direct panel installation
Best for packaging machines, ovens, mold temperature control; most widely used for overseas equipment repairs
- RKC RH400 (RH400 FK02-MAN)
Specs: 48×48, multi-input, relay output, single alarm, AC100–240V
Feature: PID algorithm closest to Panasonic KT4R; easy for technicians familiar with older Panasonic controllers
- Fuji PXR4TCY1-8V000
Specs: 48×48, relay output, multi-input, single alarm
Advantage: Mid-range price between OMRON and RKC; large stock availability for spare parts
- Autonics TK4S-24RN (Korean brand)
Specs: 48×48, AC100–240V, relay output, multi-input, 1 alarm
High cost-performance; popular for Southeast Asia & Central Asia projects
- Delta DTA4848R0
Specs: 48×48, relay output, multi-input, single alarm
Taiwanese brand, stable supply, lower cost than Japanese models
- High-compatibility Chinese Models (Cost Priority, Domestic Retrofit & Low-budget Modification)
- Yudian AI-208D2G (48×48, relay output)
Multi-input, PID auto-tuning, single alarm; widely used domestically with abundant spare parts
- TQDEC CD101 FK02-MVAN
48×48, relay output, multi-input; same cutout for direct panel replacement
- REX-C100 (Multi-input version only)
Note: Many low-cost REX-C100 only support K-type thermocouple; strictly select the universal multi-input version
III. Panasonic Brand Upgrade Options (Same Manufacturer; Requires Wiring & Program Evaluation)
New Panasonic KT4 series (AKT4□ such as AKT4111100)
Note: Same 48×48 cutout, but terminal definitions and menu structure have been revised. Not pin-to-pin direct replacement; only for customers who insist on keeping Panasonic brand.
✅ Pre-replacement Verification Checklist
Panel cutout: 45×45mm (1/16 DIN; all above models meet this requirement)
Power supply: AC100–240V (do not select 24V DC/AC versions)
Input: Universal multi-input (TC + PT100 + analog signal); avoid single K-type input only
Main control output: Relay (not SSR voltage or 4–20mA current output)
Alarm: Minimum 1 relay alarm output (AKT4R111100 only has 1 alarm point)
Communication: Original unit has no RS485. You can choose non-comm versions or communication-ready units for future upgrades
Restriction: AKT4R111100 has no heating/cooling dual output and no heater burnout (HBA) detection. Do not select high-end models with extra HBA or dual heating/cooling functions to avoid over-specification.
⚠️ Critical Reminder
No model offers pin-to-pin plug-and-play replacement. All alternatives have different terminal assignments. You must rewire the controller and reconfigure sensor type, PID parameters, alarm mode and alarm thresholds.
For bulk export equipment (bestcontactor foreign trade business), top recommended models: E5CC-RX2ASM-800, RH400, TK4S-24RN.
Quick Selection Guide by Application Scenario
Overseas/EU clients, quality first: E5CC-RX2ASM-800
Old equipment maintenance, matching Panasonic PID response: RKC RH400
Central Asia/Southeast Asia projects, balanced budget: Autonics TK4S-24RN
Domestic retrofit, tight budget: Yudian AI-208D2G
Full Panasonic KT Series Temperature Controller List (AKT Prefix, Industrial PID, Foreign Trade Spare Parts Version)
Note: KT4R (AKT4R) is discontinued; KT4B / KT4H / KT7 / KT8 / KT9 / KT2 are the current production sub-series. Unified model coding rule:
AKTxx + Power + Input + Main Output + Alarm + Heating/Cooling + Heater Burnout + Communication (suffix 1 = RS485)
Code Definition:
Power: 1=AC100–240V|2=AC/DC24V
Input: 1=Multi-input (TC/RTD/DC voltage/current)
Main Output: 1=Relay|2=SSR voltage drive|3=4–20mA current
Alarm: 1=1-point alarm|2=2-point alarm
Heating/Cooling & Heater Burnout: 0=None
Suffix: No suffix = No communication; 001 = RS485 communication
- KT4R Series (48×48, slim body, DISCONTINUED | Your target series)
Dimension: 48×48×58.8mm
AKT4R111100 ✅ Your model: AC100–240V, multi-input, relay output, 1 alarm, no heating/cooling, no HBA, no communication
AKT4R1111001: Same specs + RS485 communication
AKT4R112100: SSR voltage output, 1 alarm, no communication
AKT4R1121001: SSR output, 1 alarm, RS485
AKT4R112200: SSR output, 2-point alarm, no communication
AKT4R113100: 4–20mA current output, 1 alarm
AKT4R113200: 4–20mA current output, 2 alarms
AKT4R211100: AC/DC24V power supply, relay, 1 alarm
- KT4B / KT4H Series (48×48, thick body, upgraded replacement for KT4R)
Dimension: 48×48×95mm
AKT4B111100: Relay output, 1 alarm, no communication
AKT4B1111001: Relay output, 1 alarm, RS485
AKT4B111200: Relay output, 2 alarms
AKT4B1112001: Relay output, 2 alarms, RS485
AKT4B112100: SSR voltage output, 1 alarm
AKT4B1121001: SSR voltage output, 1 alarm, RS485
AKT4B112200: SSR voltage output, 2 alarms
AKT4B1122001: SSR voltage output, 2 alarms, RS485
AKT4B113100: Current output, 1 alarm
AKT4B1131001: Current output, 1 alarm, RS485
AKT4B113200: Current output, 2 alarms
AKT4B211100: AC/DC24V, relay, 1 alarm
AKT4H111105, AKT4H1122041 etc. (models with HBA heater burnout detection)
- KT8R Series (48×96, vertical type)
Dimension: 48×96×58.8mm
AKT8R111100: Relay output, 1 alarm, no communication
AKT8R1111001: Relay output, 1 alarm, RS485
AKT8R111200: Relay output, 2 alarms
AKT8R112100: SSR output, 1 alarm
AKT8R112200: SSR output, 2 alarms
AKT8R113100: Current output, 1 alarm
- KT9R Series (96×96, large square panel)
Dimension: 96×96×58.8mm
AKT9R111100: Relay output, 1 alarm, no communication
AKT9R1111001: Relay output, 1 alarm, RS485
AKT9R111200: Relay output, 2 alarms
AKT9R112100: SSR output, 1 alarm
AKT9R112200: SSR output, 2 alarms
AKT9R113100: Current output, 1 alarm
- KT7 Series (22.5mm ultra-narrow DIN rail panel type)
Dimension: 22.5×75×100mm
AKT711100: AC100–240V, relay, 1 alarm
AKT711200: AC100–240V, SSR voltage output
AKT711300: AC100–240V, current output
AKT721100: AC/DC24V, relay output
Feature: Supports HBA heater burnout detection with optional CT current transformer
- KT2 Series (48×24, ultra-flat horizontal type)
Dimension: 48×24×98.5mm
AKT211100: AC100–240V, relay output
AKT211200: AC100–240V, SSR output
AKT211300: AC100–240V, current output
AKT221100: AC/DC24V, relay output
AKT2111001: RS485 communication version
- Matching Accessories (Commonly sold together for foreign trade spare parts)
AKT4H801: Terminal cover for KT4R
AKT8R801: Terminal cover for KT8R
AKT9R801: Terminal cover for KT9R
AKW4822: 48×48 mounting frame
AKW8822: 48×96 mounting frame
AKT4810: Shunt resistor (for DC current input)
AKT4H820: Programming cable for KT4H
CT1 / CT2: Current transformers for HBA heater burnout monitoring
- Series Lifecycle Summary (Key for spare parts business)
- KT4R (AKT4Rxxxxxx): Discontinued. Last order date: 29 September 2023. Only surplus new stock & second-hand units available on the market.
- KT4B/KT4H: Same cutout upgrade model for KT4R; terminal pinout differs, not pin-to-pin direct replacement
- KT2 / KT7 / KT8R / KT9R: Main active production series
- Quick Cutout Reference
KT4R / KT4B / KT4H: 48×48 (1/16 DIN)
KT8R: 48×96 (1/8 DIN vertical)
KT9R: 96×96 (1/4 DIN)
KT2: 48×24
KT7: 22.5mm narrow width
Contactor,circuit breaker,sensor,Encoder,PLC,Converter