Model: VM-5Z1 Power Supply Unit
Application: Central power supply for all VM-5 monitor cards (vibration, shaft displacement, speed, eccentricity etc.) in the same rack, designed per API 670 standard, widely used in thermal power & petrochemical turbine units.
- Model Definition
VM-5: Shinkawa VM-5 TSI monitoring series
Z: Power Supply Unit
1: Version (wide AC/DC input, different from VM-5Z2 / VM-5Z3)
Suffix `/TRP`: Tropical anti-humidity treatment option
- Key Electrical Specifications
Input power (CE compliant): 85~264VAC / 88~144VDC
Multi-way DC output: +5V, +17V, +24V, -15V, -30V (green Power OK LED on front panel)
Max power consumption: ≤265VA
Alarm relay: C-form dry contact, normally energized; contact rating: 250VAC 5A / 30VDC 5A
Contact life: ≥100,000 operations at rated load
Withstand voltage: 2000VAC, 1min between power and ground
Insulation resistance: ≥100MΩ at 500VDC
Operating temperature: 0 ~ 65℃; storage temperature: -30 ~ +85℃
Humidity: 20~95%RH, non-condensing
Weight: Max 2.2 kg
Construction: Sealed plastic housing with aluminum front panel (Munsell N-1.0 grey)
- Mounting & Compatibility
Compatible racks: VM-5H4 (10-slot), VM-5W2 (8-slot); occupies 2 module slots
Function: OK indicator turns off + relay contact trips upon power failure, sending fault signal to DCS/PLC
Comparison with other power modules
VM-5Z1: Wide AC/DC input, 0~65℃, with Power OK alarm contact
VM-5Z2: Max power ≤135W
VM-5Z3: Single 24VDC input, 0~50℃, no Power OK alarm contact
- Typical Application
Turbines, compressors, fans and other rotating machinery TSI protection systems, paired with VM-5T shaft displacement, VM-5C eccentricity, VM-5V vibration, VM-5Q speed monitor cards. Widely used for legacy TSI retrofits in thermal & petrochemical plants.
- Spare Parts & Replacement
Product status: VM-5 series is mature legacy model, gradually replaced by VM-7 series; available stock mostly includes used, refurbished and surplus new spares.
Preferred replacement: Direct same model VM-5Z1; Z2/Z3 cannot be directly swapped due to different input rating, temperature range and alarm logic.
Common faults: No multi-way DC output; Power OK lamp off; failed alarm contact; blown input fuse.
Operating Principle of Shinkawa VM-5Z1
It is an isolated multi-output switching power supply, dedicated to powering VM-5 rack TSI monitor cards (vibration, displacement, speed etc.). It is a critical component of API 670 rotating machinery protection systems with normally energized alarm relay logic (core requirement for TSI systems).
Signal Flow
Input → EMI Rectifier & Filter → High-frequency PWM Inverter → Isolation Transformer → Multi-secondary Rectifier & Stabilization → DC Outputs + Voltage Monitoring + Power OK Alarm Relay
- Input Stage (Wide AC/DC Compatibility)
Input range: 85~264VAC (47–63Hz) or 88~144VDC, shared input circuit for AC & DC power.
First stage: EMI filter, surge suppression and input fuse.
AC input: Converted to high-voltage DC via rectifier bridge.
DC input: Bypass rectifier directly to post stage.
Core difference between VM-5Z1 and Z2/Z3: universal wide AC/DC input.
- High-frequency Inversion & Isolation (Switching Power Core)
High-voltage DC feeds PWM switching tubes to generate high-frequency square waves driving the isolation transformer.
The transformer provides galvanic isolation between primary power side and secondary sensor/card power side (2000VAC withstand voltage).
The primary PWM chip automatically adjusts duty cycle to stabilize all secondary outputs, adopting a multi-output common voltage regulation architecture.
- Independent Secondary Rectification, Filtering & Stabilization
Multiple independent secondary windings generate 5 DC power rails for rack logic and sensor circuits:
+5V: Digital circuits, CPU and logic chips (Power OK indicator is powered by this rail, main judgment reference)
+17V: Signal conditioning circuits on monitor boards
+24V: Partial sensor excitation & loop power supply
-15V, -30V: Eddy current probe preamplifiers & analog op-amp negative power
Each rail has independent LC filtering and current limiting to keep low ripple for weak eddy current signal acquisition.
- Voltage Monitoring & Power OK Alarm Circuit (Key Feature)
Built-in comparator circuit continuously monitors all 5 output voltages:
All outputs within tolerance window: Green OK lamp ON, relay remains energized (Normally Energized).
Any rail under/over voltage, power loss or internal failure: OK lamp OFF, relay de-energizes and trips, C-form dry contact sends fault signal to DCS.
✅ Critical point: Normally Energized. Relay stays energized under normal operation; releases upon power loss or fault. This is the industry standard fail-safe alarm logic required by TSI systems to avoid missing power failure alarms caused by broken wiring.
- Built-in Protection Functions
Output overcurrent & short-circuit protection: Current limiting hiccup mode, auto recovery after fault cleared.
Overvoltage protection: Latch shutdown, requires power cycle reset.
Overheat protection: Shuts down output when overtemperature occurs.
The whole unit is fully potted and sealed for anti-vibration and anti-humidity, suitable for power plant and petrochemical field environments; the `/TRP` suffix stands for tropical anti-humidity version.
- Coordination with VM-5 Rack
VM-5Z1 occupies 2 slots on VM-5W2 (10-slot) / VM-5H4 (8-slot) rack. Multi-way DC power is distributed to all VM-5 cards via backplane copper busbars, eliminating separate power supplies for each monitor card.
Redundant dual power configuration (two VM-5Z1 units) is supported with backplane current sharing; single power failure will not interrupt TSI monitoring & protection output, complying with API 670 requirements.
- Fault Troubleshooting Based on Operating Principle
- OK lamp off with no alarm: Main +5V rail undervoltage, monitoring circuit triggers fault directly.
- Lamp ON but DCS reports power fault: Burnt relay coil or oxidized contacts (high failure point for long-term energized relays).
- One rail low voltage while others normal: Failed rectifier diode or aging filter capacitor on that secondary winding.
- Hiccup protection immediately after power-on: Short circuit on backplane caused by faulty monitor card pulling down the power supply.
Full VM-5 TSI Rack Configuration List (Matching VM-5Z1 Power Supply)
Rack: VM-5W2 (10-slot, supports dual redundant power) / VM-5H4 (8-slot, single power common)
Core layout constraint: One VM-5Z1 occupies 2 slots
- All VM-5 Monitor Card Models & Functions
| Model | Description | Channels | Measurement Application | Sensor Type |
| VM‑5V | Shaft Vibration Monitor | Dual Channel | Radial relative shaft vibration | VK / FK Eddy Current Probe |
| VM‑5T | Thrust / Shaft Position Monitor | Dual Channel | Thrust bearing axial displacement | VK / FK Eddy Current Probe |
| VM‑5C | Rotor Eccentricity Monitor | Dual Channel | Rotor eccentricity (barring & startup) | Eddy current + speed pulse |
| VM‑5D | Differential Expansion Monitor | Dual Channel | Rotor‑casing differential expansion | Eddy Current Probe |
| VM‑5E | Casing Expansion Monitor | Dual Channel | Absolute casing thermal growth | Eddy current / LVDT |
| VM‑5Q | Speed / Zero Speed Monitor | Dual Channel | Rotational speed, direction, zero speed, overspeed protection | Magnetic pickup, gear tooth probe |
| VM‑5M | Composite Vibration Monitor | Dual Channel | Relative + absolute vibration (shaft + bearing housing vibration) | Eddy current + velocity transducer |
| VM‑5X | Valve Position Monitor | Dual Channel | Control valve opening, actuator travel | LVDT |
Backplane Accessories (No front panel slot occupation)
VM-5Y1 / VM-5Y2 / VM-5Y3: Relay Output Unit, aggregates Alert/Danger dry contacts from all cards and sends unified alarm signals to DCS/ETS; C-form contacts with normally energized logic.
VM-5COM: Communication Module (RS485 Modbus RTU), uploads 4-20mA measured values and alarm status to RV-200 diagnostic host.
VM-5Z0: Power failure hold-up unit (0.2s buffer for momentary power loss, optional for critical units).
Scheme A: VM-5W2 (10-slot)|Single Power Configuration (1×VM-5Z1)
VM-5Z1 occupies 2 slots; remaining 8 slots for monitor cards
Standard Turbine TSI Layout (10 slots)
- Slot 1~2: VM-5Z1 (Power Supply Unit)
- Slot 3: VM-5T Thrust Shaft Displacement
- Slot 4: VM-5C Rotor Eccentricity
- Slot 5: VM-5Q Speed / Overspeed
- Slot 6: VM-5D Differential Expansion
- Slot 7: VM-5E Casing Expansion
- Slot 8: VM-5V Shaft Vibration 1
- Slot 9: VM-5V Shaft Vibration 2
- Slot 10: VM-5M Composite Vibration (Bearing Vibration spare)
Backplane accessories: VM-5Y Relay Unit + VM-5COM Communication Module (backplane mounted, no slot occupied)
Scheme B: VM-5W2 (10-slot)|Dual Redundant Power (API670 Standard, Most Popular for Power Plants)
Two VM-5Z1 units (2 slots each) → total 4 slots occupied; 6 slots left for monitor cards
- Slot 1-2: VM-5Z1 1 (Main Power)
- Slot 3-4: VM-5Z1 2 (Standby Power, hot redundant with backplane current sharing)
- Slot 5: VM-5T Thrust Displacement
- Slot 6: VM-5C Rotor Eccentricity
- Slot 7: VM-5Q Rotational Speed
- Slot 8: VM-5D Differential Expansion
- Slot 9: VM-5V Shaft Vibration A
- Slot 10: VM-5V Shaft Vibration B
✅ Redundancy Logic: Two independent power inputs with diode current sharing on backplane. Failure of one VM-5Z1 triggers Power OK alarm without interrupting TSI monitoring & protection output, fully complying with API670 rotating machinery protection standard.
Scheme C: VM-5H4 (8-slot)|Single VM-5Z1 (Small Turbines, Compressors & Fans)
VM-5Z1 occupies 2 slots; remaining 6 slots available
Compact Compressor/Fan TSI Configuration
- Slot 1-2: VM-5Z1
- Slot 3: VM-5V Shaft Vibration 1
- Slot 4: VM-5V Shaft Vibration 2
- Slot 5: VM-5T Shaft Displacement
- Slot 6: VM-5Q Rotational Speed
- Slot 7: VM-5M Composite Vibration
- Slot 8: Spare monitor card slot
Front-end Sensor Matching List
VK-202A / VK-302P / VK-602P: Eddy current displacement probes (shaft vibration, position, eccentricity, differential expansion)
FK series: High-temperature eddy current probes (high-temperature casing area)
RV Magnetic Pickup: Speed input for VM-5Q monitor
Velocity Transducer: Bearing vibration input for VM-5M
LVDT: VM-5E casing expansion & VM-5X valve position measurement
Selection & Layout Pitfall Avoidance
- VM-5Z1 always occupies 2 slots; cannot be treated as single-slot module. Z2/Z3 also take 2 slots and cannot be mixed due to different input rating and alarm contact logic.
- All monitor cards have two fully independent channels, each with separate Alert (Pre-alarm) and Danger (Trip) C-form normally energized relay contacts; supports latching or auto reset.
- 4-20mA analog output: Each card has built-in recorder output; alternatively all values can be uploaded centrally via Modbus through VM-5COM.
- Tropical version: Add `/TRP` suffix to all card models for coastal & high-humidity power plants (anti-corrosion & anti-moisture treatment).
- Expansion limit: Dual power 10-slot rack can only accommodate max 6 monitor cards; additional VM-5 racks are required for more measurement points.
Recommended Spare Parts Kit for One Rack
VM-5Z1 Power Supply Unit (full spare)
Common monitor cards: VM-5V, VM-5T, VM-5Q
Eddy current probes, extension cables and preamplifiers
VM-5Y relay unit & VM-5COM communication card
Full VM-5 TSI I/O List (VM-5W2 10-slot Rack, Dual Redundant VM-5Z1 Power Supply)
Rack Layout Recap: Slot1-2 VM-5Z11; Slot3-4 VM-5Z12; Slot5 VM-5T; Slot6 VM-5C; Slot7 VM-5Q; Slot8 VM-5D; Slot9 VM-5V(A); Slot10 VM-5V(B)
Backplane Modules: VM-5Y (Alarm Aggregation Relay), VM-5COM (Modbus RTU Communication)
Rules:
- Every monitor card has two independent channels CH1 / CH2. Each channel has separate Alert (Pre-alarm) & Danger (Trip) C-form normally energized dry contacts plus one isolated 4-20mA analog output.
- Modbus: VM-5COM acts as Modbus slave; register addresses shown below are reference offsets (final addresses follow Shinkawa manual 6H14).
- Dry contacts are divided into two groups: Local card alarm contacts and VM-5Y aggregated alarm contacts (to ETS/DCS).
- Power failure signals: Independent Power OK contacts from each VM-5Z1; only digital alarm, no analog output.
Part 1: Dry Contact List (C-form, Normally Energized)
| Card Model | Channel | Signal Name | Contact Type |
| VM‑5Z1 #1 | — | Power Supply #1 Fault (Power Fail) | C‑form, Normally Energized |
| VM‑5Z1 #2 | — | Power Supply #2 Fault (Power Fail) | C‑form, Normally Energized |
| VM‑5T Thrust Displacement | CH1 | Thrust Displacement A Alert (Pre‑alarm) | C‑form, Normally Energized |
| VM‑5T Thrust Displacement | CH1 | Thrust Displacement A Danger (Trip) | C‑form, Normally Energized |
| VM‑5T Thrust Displacement | CH2 | Thrust Displacement B Alert (Pre‑alarm) | C‑form, Normally Energized |
| VM‑5T Thrust Displacement | CH2 | Thrust Displacement B Danger (Trip) | C‑form, Normally Energized |
| VM‑5C Eccentricity | CH1 | Rotor Eccentricity A Alert | C‑form, Normally Energized |
| VM‑5C Eccentricity | CH1 | Rotor Eccentricity A Danger | C‑form, Normally Energized |
| VM‑5C Eccentricity | CH2 | Rotor Eccentricity B Alert | C‑form, Normally Energized |
| VM‑5C Eccentricity | CH2 | Rotor Eccentricity B Danger | C‑form, Normally Energized |
| VM‑5Q Speed / Zero Speed | CH1 | Speed A Alert | C‑form, Normally Energized |
| VM‑5Q Speed / Zero Speed | CH1 | Speed A Danger (Overspeed Trip) | C‑form, Normally Energized |
| VM‑5Q Speed / Zero Speed | CH2 | Speed B Alert | C‑form, Normally Energized |
| VM‑5Q Speed / Zero Speed | CH2 | Speed B Danger (Overspeed Trip) | C‑form, Normally Energized |
| VM‑5D Differential Expansion | CH1 | Differential Expansion A Alert | C‑form, Normally Energized |
| VM‑5D Differential Expansion | CH1 | Differential Expansion A Danger | C‑form, Normally Energized |
| VM‑5D Differential Expansion | CH2 | Differential Expansion B Alert | C‑form, Normally Energized |
| VM‑5D Differential Expansion | CH2 | Differential Expansion B Danger | C‑form, Normally Energized |
| VM‑5V Shaft Vibration A | CH1 | Shaft Vibration A‑X Alert | C‑form, Normally Energized |
| VM‑5V Shaft Vibration A | CH1 | Shaft Vibration A‑X Danger | C‑form, Normally Energized |
| VM‑5V Shaft Vibration A | CH2 | Shaft Vibration A‑Y Alert | C‑form, Normally Energized |
| VM‑5V Shaft Vibration A | CH2 | Shaft Vibration A‑Y Danger | C‑form, Normally Energized |
| VM‑5V Shaft Vibration B | CH1 | Shaft Vibration B‑X Alert | C‑form, Normally Energized |
| VM‑5V Shaft Vibration B | CH1 | Shaft Vibration B‑X Danger | C‑form, Normally Energized |
| VM‑5V Shaft Vibration B | CH2 | Shaft Vibration B‑Y Alert | C‑form, Normally Energized |
| VM‑5V Shaft Vibration B | CH2 | Shaft Vibration B‑Y Danger | C‑form, Normally Energized |
| Alarm Aggregation Unit | — | TSI System General Danger Alarm | C‑form |
| Alarm Aggregation Unit | — | TSI System General Pre‑alarm | C‑form |
Contact rating: 250VAC 5A / 30VDC 5A. Normally Energized = Closed under normal operation, open upon fault / power loss, fully complying with API670 fail-safe alarm requirement.
Part 2: 4-20mA Analog Output List (Isolated AO on each card)
| Slot | Card Model | Channel | Signal Name | Typical Range (Configurable on card) | Output |
| 5 | VM‑5T | CH1 | Thrust Displacement A | -1.0 ~ +1.0 mm | 4‑20mA |
| 5 | VM‑5T | CH2 | Thrust Displacement B | -1.0 ~ +1.0 mm | 4‑20mA |
| 6 | VM‑5C | CH1 | Rotor Eccentricity A | 0 ~ 0.2 mm | 4‑20mA |
| 6 | VM‑5C | CH2 | Rotor Eccentricity B | 0 ~ 0.2 mm | 4‑20mA |
| 7 | VM‑5Q | CH1 | Rotational Speed A | 0 ~ 6000 rpm | 4‑20mA |
| 7 | VM‑5Q | CH2 | Rotational Speed B | 0 ~ 6000 rpm | 4‑20mA |
| 8 | VM‑5D | CH1 | Differential Expansion A | -5 ~ +25 mm | 4‑20mA |
| 8 | VM‑5D | CH2 | Differential Expansion B | -5 ~ +25 mm | 4‑20mA |
| 9 | VM‑5V | CH1 | Shaft Vibration A X‑axis | 0 ~ 200 μm | 4‑20mA |
| 9 | VM‑5V | CH2 | Shaft Vibration A Y‑axis | 0 ~ 200 μm | 4‑20mA |
| 10 | VM‑5V | CH1 | Shaft Vibration B X‑axis | 0 ~ 200 μm | 4‑20mA |
| 10 | VM‑5V | CH2 | Shaft Vibration B Y‑axis | 0 ~ 200 μm | 4‑20mA |
Note: 4mA = lower range limit; 20mA = upper range limit. Two independent AO channels per card. This analog signal is physically separated from Modbus communication for redundant data acquisition.
Part 3: Modbus RTU Point List (VM-5COM, 16-bit Holding Registers)
Default communication parameters: 9600, 8, N, 1; slave address set via DIP switch; register addresses are reference values (final mapping follows Shinkawa manual 6H14).
Data type: Measured values (INT16 with scaling factor); alarm status (Bit mapped UINT16).
| Register Address | Tag Name | Description | Data Type |
| 40001 | Thrust_Displacement_A_CH1 | Axial displacement measurement | INT16 |
| 40002 | Thrust_Displacement_B_CH2 | Axial displacement measurement | INT16 |
| 40003 | Eccentricity_A_CH1 | Rotor eccentricity measurement | INT16 |
| 40004 | Eccentricity_B_CH2 | Rotor eccentricity measurement | INT16 |
| 40005 | Speed_A_CH1 | Rotational speed measurement | INT16 |
| 40006 | Speed_B_CH2 | Rotational speed measurement | INT16 |
| 40007 | Diff_Expansion_A_CH1 | Differential expansion measurement | INT16 |
| 40008 | Diff_Expansion_B_CH2 | Differential expansion measurement | INT16 |
| 40009 | Shaft_Vib_A_X_CH1 | Shaft vibration peak‑peak value | INT16 |
| 40010 | Shaft_Vib_A_Y_CH2 | Shaft vibration peak‑peak value | INT16 |
| 40011 | Shaft_Vib_B_X_CH1 | Shaft vibration peak‑peak value | INT16 |
| 40012 | Shaft_Vib_B_Y_CH2 | Shaft vibration peak‑peak value | INT16 |
| 40100 | Channel_Alarm_Word_1 | Bit0~Bit11: Channel Alert/Danger + sensor break | UINT16 |
| 40101 | Power_Status_Word | Bit0: VM‑5Z1#1 Fault; Bit1: VM‑5Z1#2 Fault | UINT16 |
| 40102 | Rack_System_Status | Communication, card self‑test & backplane fault flags | UINT16 |
Bit Definition for Register 40100 (Channel Alarm Word)
Bit0: VM-5T CH1 Alert
Bit1: VM-5T CH1 Danger
Bit2: VM-5T CH2 Alert
Bit3: VM-5T CH2 Danger
Bit4: VM-5C CH1 Alert
Bit5: VM-5C CH1 Danger
Bit6: VM-5C CH2 Alert
Bit7: VM-5C CH2 Danger
Subsequent bits follow in sequence and can be extended according to actual measurement points.
Part 4: Design Notes & Signal Redundancy
- ETS Trip Logic: All Danger trip contacts shall adopt 1-out-of-2 or 2-out-of-2 voting logic per turbine protection standards. Power fault contacts shall only generate alarm, not initiate ETS trip.
- Triple Redundant Signal Path: Hard relay contacts (safety trip) + 4-20mA analog (DCS trend) + Modbus RTU (host diagnostic data) are fully independent physical links.
- Sensor Break Detection: Every monitor card has built-in probe break detection; open circuit will trigger Alert/Danger alarm and set corresponding bit in Modbus status word.
- If you need a simplified I/O list for single-power VM-5W2 / VM-5H4 rack, I can provide a trimmed version immediately.
Part 5: I/O Quantity Summary (Dual Power Scheme)
Power digital contacts: 2 points
Channel Alert pre-alarm contacts: 12 points
Channel Danger trip contacts: 12 points
VM-5Y aggregated alarm contacts: 2 points
4-20mA analog output channels: 12 channels
Modbus measurement registers: 12 pcs; status registers: 3 pcs