ABB AX09-30-10-80 Contactor - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

chatear: +86-13184948252 Whatsapp: 0086-13811255435 Correo electrónico: kent@bestcontactor.com

Acerca de Contacto |

 ABB AX09-30-10-80 Contactor - contactor,cortacircuitos,inversor solar,medidor electrico,baterias solares

contactor/

ABB AX09-30-10-80 Contactor

The AX09-30-10-80 is a general-purpose 3-pole AC contactor of ABB AX series, the official successor to the classic A9 contactor from the former A series. It is designed for controlling low-power loads in general industrial applications, mainly used for direct start and stop of three-phase asynchronous motors, as well as switching of AC distribution circuits, ...

  • Detalles del producto

The AX09-30-10-80 is a general-purpose 3-contactor de CA de polo de TEJIDO Serie AX, the official successor to the classic A9 contactor from the former A series. It is designed for controlling low-power loads in general industrial applications, mainly used for direct start and stop of three-phase asynchronous motors, as well as switching of AC distribution circuits, inductive and resistive loads.

Equipped with a conventional AC coil, this contactor features compact structure and small footprint. It supports mounting on standard 35 mm DIN rails, and offers long mechanical service life, high operating frequency and excellent environmental adaptability. It is widely applied in building HVAC systems, light automation systems, OEM equipment assembly, municipal power distribution and other fields.

  1. Interpretación del código modelo

Modelo completo: AX09-30-10-80

  1. HACHA: código de serie, representing AX series general-purpose AC contactors (replacement for legacy A series).
  2. 09: Rated current class. Rated operational current is 9 A under utilization category AC-3 at 400 V.
  3. 30: Configuración del contacto principal. 3 normally open main contacts with no normally closed main contacts (the first digit = number of main poles; the second digit = number of normally closed main contacts).
  4. 10: Configuración de contactos auxiliares. 1 normally open auxiliary contact with no normally closed auxiliary contacts (the first digit = number of normally open auxiliary contacts; the second digit = number of normally closed auxiliary contacts).
  5. 80: Coil code, corresponding to standard AC coil: 220-230 V y 50 Hz / 230-240 V y 60 Hz.
  6. Parámetros técnicos básicos

3.1 Parámetros del circuito principal

ArtículoEspecificación
polacos & Configuración de contacto3PAG, 3 Normally Open main contacts
Corriente Térmica Convencional (Ith)24 A (Ambient temperature ≤ 40 ℃)
Corriente operativa nominal (AC-1)22 A (≤ 690 V y, ≤ 40 ℃); 18 A (≤ 70 ℃)
Corriente operativa nominal (AC-3)9 A (≤ 440 V y, ≤ 55 ℃); 7 A (≤ 690 V y, ≤ 55 ℃)
Maximum Rated Operational Voltage (ue)690 V y
Rated Control Power (AC-3)4 kW @ 400 V; 5.5 kW @ 690 V
Capacidad de ruptura nominal (AC-3)8 × Ie
Tensión nominal de resistencia al impulso (árbitro)6 kV
Categoría de sobretensiónCategoría III
Conexión del circuito principalScrew terminal connection, suitable for solid/stranded copper conductors
Torque for Main Terminals1.2 ~ 1.5 Nuevo Méjico

3.2 Parámetros del circuito de control

ArtículoEspecificación
Rated Coil Voltage (uc)220~230 V AC 50 Hz; 230~240 V AC 60 Hz
Rango de voltaje de captación0.85 Uc ~ 1.1 uc
Rango de voltaje de caída0.2 Uc ~ 0.75 uc
Tipo de bobinaConventional AC excitation coil
Standard Auxiliary Contact1 NO, compatible with AC-15 / DC-13 control circuits
Rated Capacity of Auxiliary ContactAC-15: 10 A / 220 V; DC-13: 0.55 A / 220 V
Conexión del circuito de controlTerminales de tornillo

3.3 Mecánico & Parámetros ambientales

ArtículoEspecificación
Dimensiones generales (Ancho × Alto × Fondo)44 milímetros × 74 milímetros × 74 milímetros
Peso netoAprox.. 0.326 kilos
Clase de protecciónIP20 (cuerpo principal)
Temperatura ambiente de funcionamiento-25 ℃ ~ +55 ℃ (Full rating within 55 ℃; current derating required at 70 ℃)
Installation AltitudeNo current derating up to 3000 metro
Método de montajeEstándar 35 mm montaje en carril DIN; vertical screw mounting available
CertificacionesCEI 60947-4-1, CCC, CE, UL, RoHS

3.4 Vida útil & Parámetros de rendimiento

ArtículoEspecificación
Vida mecánica10,000,000 ciclos de operación
Vida eléctrica (Servicio AC-3)1,000,000 ciclos de operación
Maximum Operating Frequency1200 ciclos por hora
Pick-up Time7 ~ 21 EM
Drop-out Time4 ~ 11 EM
  1. Modelos alternativos & Cross-Series Reference

4.1 ABB Equivalent Replacements

  1. Replacement for Discontinued Models: Direct replacement for legacy A series A9-30-10. Fully compatible with original mounting holes and rail dimensions, with upgraded electrical life and overall reliability.
  2. Same Current Rating with Different Coils:

AX09-30-10-81: 24 V y 50/60 Hz coil

AX09-30-10-84: 110 V y 50 Hz / 110~120 V 60 Hz coil

AX09-30-01-80: Same main circuit, fitted with 1 Contacto auxiliar NC

  1. Higher Current Models in the Same Series: AX12-30-10-80 (12 A), AX18-30-10-80 (18 A). Identical mounting width for direct replacement and capacity upgrade.

4.2 Equivalent Products from Other Brands

Electricidad Schneider: LC1D09M7C

siemens: 3RT6015-1AN21

chint: NXC-09 (220 bobina en V)

> Nota: All cross-brand models support 35 mm DIN rail mounting for direct replacement. Please verify auxiliary contact configuration and coil voltage before installation.

  1. Full List of AX Series 3-Pole Contactors (220 V Coil)
ModeloCorriente nominal (AC-3 @ 400 V)Corresponding Motor Power @ 400 VStandard Auxiliary Contacts
AX09-30-10-809 A4 kilovatios1 NO
AX12-30-10-8012 A5.5 kilovatios1 NO
AX18-30-10-8018 A7.5 kilovatios1 NO
AX25-30-10-8025 A11 kilovatios1 NO
AX32-30-10-8032 A15 kilovatios1 NO
AX40-30-10-8040 A18.5 kilovatios1 NO
AX50-30-11-8050 A22 kilovatios1 NO + 1 CAROLINA DEL NORTE
AX65-30-11-8065 A30 kilovatios1 NO + 1 CAROLINA DEL NORTE
AX80-30-11-8080 A37 kilovatios1 NO + 1 CAROLINA DEL NORTE
AX95-30-11-8095 A45 kilovatios1 NO + 1 CAROLINA DEL NORTE

Accesorios comunes

Relé de sobrecarga térmica: Serie TA25DU (p.ej. TA25DU-9M). Direct plug-in bottom mounting for motor overload protection.

Auxiliary Contact Blocks: CA5X series front-mounted modules (CA5X-10E, CA5X-01mi, CA5X-22E), ampliable hasta 4 pairs of auxiliary contacts.

Supresor de sobretensiones: RV5X series, absorbs switching overvoltage of coils to protect PLC control circuits.

Enclavamiento mecánico: VB5X series, provides mechanical interlock for forward/reverse operation of two contactors.

Terminal Shroud: Improves protection level and prevents accidental contact.

  1. Ámbito de aplicación & Operating Limits

6.1 Aplicaciones típicas

  1. Control de motores pequeños: Direct start/stop of three-phase asynchronous motors such as small fans, bombas de agua, transportadores, roller table motors and mini compressors, suitable for loads up to 4 kilovatios.
  2. Edificio & Sistemas HVAC: Control of terminal units of central air conditioning, fresh air units, fire exhaust fans, suministro de agua & drainage pumps and fire dampers. It acts as a key actuator for power distribution circuits in building automation.
  3. Equipos OEM: Power circuit control for packaging machinery, maquinaria textil, pequeñas máquinas herramienta, food processing equipment and other automated machinery. The compact size saves cabinet space.
  4. Distribución de energía & Control de iluminación: Remote switching of high-capacity lighting circuits and small distribution feeders; switching of low-capacity capacitor banks in low-voltage reactive power compensation cabinets.
  5. Automation Logic Control: Acts as a power amplifier for PLC outputs to drive solenoid valves, indicator lights and other small actuators.

6.2 Requisitos ambientales

Install indoors inside switchgear or control boxes. Outdoor exposure to rain and direct sunlight is prohibited.

Pollution level shall not exceed Class 3; no highly corrosive gas, explosive gas or conductive dust present.

No severe impact or vibration on mounting surface; vibration acceleration ≤ 20 m/s².

Current derating is required when installation altitude exceeds 3000 m or ambient temperature exceeds 55 ℃, refer to official manual for calculation.

  1. Troubleshooting Matrix
Fenómeno de fallaCausa principalSoluciones
Contactor fails to close with no sound1. Sin fuente de alimentación, loose or broken wiring in control circuit1. Cut off power and perform safety check; inspect wiring at terminals A1/A2 and re-measure coil voltage
2. Burnt or broken coil2. Test coil resistance with multimeter; replace coil or complete unit if open circuit occurs
3. Armature mechanical jam or foreign obstruction3. Manually operate armature after power-off, clean dust and foreign matters on core pole faces
4. Supply voltage far below rated value4. Adjust supply voltage to rated range and eliminate line voltage drop
Continuous buzzing noise after closure1. Oil and dust on core pole faces causing poor contact1. Dismantle core after power-off and clean oil & dirt on pole faces
2. Broken or detached shading coil2. Replace core or complete unit if shading coil is damaged
3. Insufficient suction due to low supply voltage3. Increase supply voltage to rated range
Abnormal overheating at main terminals / contactos1. Loose terminal screws leading to high contact resistance1. Retighten terminals to specified torque after power-off
2. Continuous overload with current exceeding rated value2. Measure load current, check model selection and replace with higher-rated model if necessary
3. Contact ablation and poor conduction3. Polish slightly ablated contacts; replace complete unit for severe damage
Abnormal signal from auxiliary contacts, no feedback to PLC1. Ablation or poor contact of auxiliary contacts1. Test on-off performance of auxiliary contacts after power-off and replace faulty blocks
2. Loose or broken cables2. Inspect wiring and PLC input circuit to fix line faults
3. Improper installation of auxiliary contact block3. Reinstall auxiliary contact block and ensure firm connection
Severe coil overheating, burning smell or smoke1. Supply voltage exceeds coil rating1. Cut off power immediately, verify supply voltage and rule out wrong high-voltage connection
2. Coil inter-turn short circuit2. Medir la resistencia de la bobina; replace coil if inter-turn short circuit is confirmed
3. Long-term operation under undervoltage condition with excessive current3. Maintain supply voltage within rated range and avoid prolonged undervoltage operation
Failure to open or slow release after power cut1. Adhesion caused by oil on core pole faces1. Clean oil on core pole faces and check residual magnetism
2. Welded main contacts2. Inspect main contacts after power-off; replace contacts or complete unit if welding occurs
3. Fatigue failure of return spring3. Replace return spring or complete contactor

Anterior:

Deja una respuesta

Dejar un mensaje