Numéro de commande: 2864794, Modèle de remplacement: 2905025 MINI MCR-2-UNI-UI-2UI-C
Taper: 4-way isolated analog signal duplicator / isolation amplifier (connexion à vis, custom configuration version)
Fonction principale
It accepts 1 channel of standard analog input signal and replicates it into 2 mutually independent current outputs after galvanic isolation. It realizes signal isolation, conversion, amplification, filtering and 1-in-2-out signal duplication. The measuring range is configured via DIP switches, with 4-way isolation (saisir / sortir 1 / sortir 2 / power supply isolated from each other).
Suitable for splitting transmitter signals to PLC + paperless recorder, anti-interference isolation and instrument loop distribution.
📌 Principales spécifications électriques
Alimentation: 19.2–30 VCC, nominal 24 V CC; power consumption <600mW, current <30mA @24V (including load)
Saisir (selectable via DIP switch): 0…20 mA / 4…20 mA / 0…10V / 1…5V
Input impedance for voltage signal ≈100kΩ; input impedance for current signal ≈50Ω
Sortir: 2 independent current outputs, 0…20mA /4…20mA; maximum. output ≈22mA; load ≤250Ω@20mA
Précision: Max.. transmission error ≤0.2%FS, typical <0.1%FS; temperature drift <0.01%/K
Bande passante (-3dB): ≈35Hz; step response (0–99%) ≈10ms
Isolation test voltage: 1.5kV AC 60s between input, sortie et alimentation, basic insulation per EN61010
Classe de protection: IP20; température de fonctionnement -20 ~ +60℃, storage temperature -40~85℃, sans condensation
📐 Mechanical Data
Montage: 35mm rail DIN (EN60715), any mounting orientation
Largeur: 6.2 mm (ultra-slim design for dense installation); 93.1(H) ×102.5(D) mm
Connexion: Bornes à vis M3, conductor 0.2–2.5mm² (AWG26–12), stripping length 12mm
Logement: PBT, RAL6021 green; net weight 73.3g, gross weight 89.7g
📋Attestation
CE, UL508, Classe I Div.2, GL marine approval, II 3G Ex nA IIC T4 Gc X (explosion protection)
🧩 Series Identification & Des pièces de rechange
2864794: MINI MCR-SL-UI-2I made-to-order configuration, non-returnable
2864176: MINI MCR-SL-UI-2I-NC standard pre-configured version
2864804: MINI MCR-SL-UI-2I-SP special version
Matching bus base: 2869728 MOI 6,2 TBUS-2 (DIN rail power bus connector)
Matching power terminal: 2864134 MINI MCR-SL-PTB
The original part number 2864794 is no longer available for regular supply. Pour les nouveaux projets, use the replacement 2905025 MINI MCR-2-UNI-UI-2UI-C (new-generation MINI MCR-2 series, fully compatible with upgraded performance).
Application Scenarios for 2864794 (MINI MCR-SL-UI-2I)
Positionnement de base: 1 entrée analogique, galvanically isolated duplication into 2 independent 4/0–20mA current signals, 4-manière d'isolement (Saisir / Sortie1 / Sortie2 / Pouvoir), signal conversion + noise immunity. Ultra-slim 6.2mm width for dense cabinet layout, certified for installation in Zone 2 zones dangereuses.
- Split One Sensor Signal into Two Outputs (Cas d'utilisation le plus courant)
- API + Paperless Recorder / Data Logger
Pression, température, level and flow transmitters with only one 4–20mA output can feed the PLC for control meanwhile send a copy to the recorder for data archiving and traceability. The two outputs are galvanically isolated; a fault on the recorder side will not drag down the transmitter loop or affect control.
- DCS Main System + Independent SIS Safety Interlock
One process measurement point sends one signal to DCS for monitoring and the isolated second signal to the independent SIS safety loop. Physical signal separation meets the independence requirement for functional safety.
- Dual PLC / Dual Controller Redundant Acquisition
Primary and backup controllers acquire the same field instrument signal at the same time. Isolated dual outputs prevent cross-interference caused by ground potential difference between controllers.
- SCADA Host Collection + IHM locale / Secondary Indicator
One channel feeds the PLC for SCADA upload, the other goes to local digital indicator or analog pointer meter for on-site display.
Input compatibility: 0/4–20mA, 0–10V, 1–5V; both outputs are current-only (0/4–20mA). Measuring ranges are freely combined via DIP switches.
- Ground Loop Elimination & Noise Isolation
When transmitters are installed near high-power motors, frequency converters or medium-frequency furnaces, long cable runs introduce ground potential difference and common-mode interference, resulting in signal jumping and drift. This module breaks ground loops and stabilizes analog signals.
Cross-cabinet signal transmission between cabinets with different potential (LV cabinet, VFD cabinet, DCS cabinet). It isolates potential offset and protects PLC analog channels from common-mode overvoltage damage.
- Signal Type Conversion
Field transmitters output voltage signals (0–10V/1–5V), while the two downstream receiving devices only accept 4–20mA current input. This unit converts the voltage input into two isolated current outputs.
- Applications spécifiques à l'industrie
Chimique, Traitement de l'eau & Municipal Wastewater: Niveau, pH, turbidité, débit et pression. Many projects require simultaneous control and data logging; suitable for Zone 2 pose d'armoire (Zone 2 seulement, NOT intrinsic safety barrier).
Pouvoir & Nouvelle énergie (PV / Stockage d'énergie / Distribution d'énergie): Bus voltage, transducer signals, cooling water temperature, split to PLC and waveform recording device.
CVC, Automatisation des bâtiments & Salles blanches: Température, humidity and differential pressure transmitters, split for BA controller and independent monitoring system.
Marin & Chemin de fer (GL Marine Certificate): Cabin pressure and temperature monitoring. Ultra-slim footprint saves cabinet space for marine control cabinets.
Conditionnement, Caoutchouc & Plastiques, Machines-outils & Automatisation personnalisée: Tension, pressure and displacement sensors. One output for motion control PLC, the other for quality inspection recording system.
- Limites de sélection & Remarques
- Both outputs are current only, voltage output is not supported. Do not select this model if one current + one voltage split is required.
- It is an isolated duplication amplifier, not an intrinsically safe barrier. It cannot directly connect to IS instruments in Zone 0 / Zone 1; it may only be fitted inside Zone 2 hazardous-area cabinets.
- Excellent for slim cabinets and high-density I/O layouts. TBUS bus bases support daisy-chain rail power supply to reduce wiring work.
Phénix Contact Analog Signal Duplicator (1-in-2-out Signal Repeater) Order List
Two major series: Legacy MINI MCR-SL (6.2mm ultra fin, y compris 2864794, suppression progressive) and New MINI MCR-2 / MINI Analog Pro (replacement series, freely configurable current/voltage output, NFC configuration supported)
Définition: Signal Duplicator (1-in-2-out isolated repeater). Pure 1-in-1-out isolators are excluded from this table.
- Legacy MINI MCR-SL Series | UI-2I (UI Input, Dual Current Output 4/0–20mA)
| Numéro de commande. | Modèle complet | Description | Statut |
| 2864794 | MINI MCR-SL-UI-2I | Custom configuration, non-returnable | Obsolète, recommander 2905025 |
| 2864176 | MINI MCR-SL-UI-2I-NC | Standard pre-configured, regular stock | Obsolète |
| 2864804 | MINI MCR-SL-UI-2I-SP | Custom configuration, non-returnable | Obsolète, recommander 2905027 |
| 2864189 | MINI MCR-SL-UI-2I-SP-NC | Standard pre-configured | Obsolète |
Common limitation for legacy models: dual outputs are current only, voltage output unavailable; 4-manière d'isolement (Saisir / Sortie1 / Sortie2 / Power isolated).
- New MINI MCR-2 Universal Duplicator UNI-UI-2UI (Entrée universelle de l'interface utilisateur, Two Outputs Independently Configurable for Voltage or Current)
| Numéro de commande. | Modèle complet | Type de connexion | Description |
| 2905026 | MINI MCR-2-UNI-UI-2UI | Vis | Standard pre-configured NC |
| 2905025 | MINI MCR-2-UNI-UI-2UI-C | Vis | Custom configuration C (remplace l'héritage 2864794) |
| 2905028 | MINI MCR-2-UNI-UI-2UI-PT | Enfichable | Standard pre-configured NC |
| 2905027 | MINI MCR-2-UNI-UI-2UI-PT-C | Enfichable | Custom configuration C (remplace l'héritage 2864804) |
Upgrade highlights for new series: each output independently configurable as current or voltage, TREMPER + NFC + software configuration, diagnostic des pannes, improved accuracy.
- Additional 1-in-2-out Duplicators in Family (Loop-Powered Version)
| Numéro de commande. | Modèle complet | Description |
| 2905628 | MINI MCR-2-RPSS-I-2I | Alimenté par boucle, 1 current input, 2 current outputs, connexion à vis |
| 2905629 | MINI MCR-2-RPSS-I-2I-PT | Alimenté par boucle, 1 current input, 2 current outputs, Enfichable |
- Accessoires assortis (Bus Power Base for Duplicators)
| Numéro de commande. | Nom | But |
| 2869728 | MOI 6,2 TBUS-2 1,5/5-ST-3,81 GN | TBUS rail bus connector for parallel power supply, compatible with slim MINI MCR-SL |
| 2864134 | MINI MCR-SL-PTB | Power terminal block |
Quick Cross Reference for Replacement
2864794 (vis, coutume) → 2905025
2864176 (vis, standard) → 2905026
2864804 (cage à ressort, coutume) → 2905027
2864189 (cage à ressort, standard) → 2905028
MINI MCR-SL-UI-UI-NC (2864150): 1-in-1-out isolator, NOT a duplicator, excluded
MACX series are mostly high-withstand, SIL functional safety or explosion-proof isolators, not general signal duplicators.
Phoenix MINI MCR-2 / MINI Analog Pro Analog Signal Duplicator (1-in-2-out Isolated Repeater) Order List
Remarques: MINI MCR-2 belongs to the MINI Analog Pro platform; supports NFC / logiciel / DIP configuration, diagnostic de panne, 4-manière d'isolement. Split into universal UI input duplicator and loop-powered HART RPSS-I-2I. PT = Push-in quick connection; no PT suffix = screw connection; suffix -C = made-to-order custom configuration (non-returnable).
- Universal Multi-Range Type: MINI MCR-2-UNI-UI-2UI (Universal UI Input, Two Outputs Independently Selectable for Current / Tension)
| Numéro de commande. | Modèle complet | Description | Remplacement hérité |
| 2905026 | MINI MCR-2-UNI-UI-2UI | Standard pre-configured NC, regular stock | 2864176 |
| 2905025 | MINI MCR-2-UNI-UI-2UI-C | Custom configuration C, parameters specified on order, non-returnable | 2864794 (your original part) |
| 2905028 | MINI MCR-2-UNI-UI-2UI-PT | Standard pre-configured NC | 2864189 |
| 2905027 | MINI MCR-2-UNI-UI-2UI-PT-C | Custom configuration C, non-returnable | 2864804 |
Caractéristiques: Input accepts 0/4–20mA, 0–10V, 1–5V; OUT1 and OUT2 can be independently set to current or voltage, mixed output allowed. Supports HART pass-through, Configuration mobile NFC, alarme de panne, Zone 2 Ex certification.
- Loop-Powered Type: MINI MCR-2-RPSS-I-2I (4–20mA Loop Powered, HART Transparent, 1-in-2-out Current)
| Numéro de commande. | Modèle complet | Type de connexion | Description |
| 2905628 | MINI MCR-2-RPSS-I-2I | Vis | Alimenté par boucle, HART transparent, dual current output |
| 2905629 | MINI MCR-2-RPSS-I-2I-PT | Enfichable | Alimenté par boucle, HART transparent, dual current output |
Caractéristiques: Powered directly from transmitter loop, independent 24V supply not required. Two passive 4–20mA outputs. Ideal for 2-wire HART transmitters, shared measurement points for DCS/SIS. Max.. load per channel up to 500Ω.
- Accessoires assortis (General for MINI Analog Pro Platform)
| Numéro de commande. | Nom | But |
| 2902066 | MINI MCR-2-PTB | Screw-type power terminal for rail bus daisy-chain power supply |
| 2902067 | MINI MCR-2-PTB-PT | Push-in power terminal |
| 2904504 | MINI MCR-2-FM-RC | Screw fault collective alarm module |
| 2904508 | MINI MCR-2-FM-RC-PT | Push-in fault collective alarm module |
| 2905634 | MINI MCR-2-V8-MOD-RTU | Modbus-RTU communication adapter, prend en charge jusqu'à 8 modules in network |
| 2905635 | MINI MCR-2-V8-MOD-TCP | Modbus-TCP communication adapter, prend en charge jusqu'à 8 modules in network |
- Guide de sélection & Éviter les pièges
- UNI-UI-2UI: Requires separate 24VDC supply, universal voltage/current input, two outputs can mix voltage + actuel. Direct upgrade replacement for legacy MINI MCR-SL-UI-2I.
- RPSS-I-2I: Alimenté par boucle, current input only, dual current output only. Preferred for HART projects; cannot be used for voltage signal splitting.
- 1-in-1-out isolators of the same series (par exemple. MINI MCR-2-UI-UI) are not duplicators and excluded from this list.
- Code SH: 85437090, Pays d'origine: Allemagne (DE)